KE2 Temp + Valve Controller User Guide

June 2, 2024
KE2

KE2 Temp + Valve Controller

This reference should remain on site with the installed KE2 Temp + Valve controller.

KE2 Temp+Valve Control
For Temp. Air Defrost, and Electronic Valve Control Condensed Quick Start Guide KIT PN 21301

What’s in the KE2 Temp + Valve kit, pn 21301

KE2-Temp+Valve-Controller-FIG-3

  • A (1) KE2 Temp + Valve controller (pn21393 – controller only)
  • B (1)10’ pressure transducer
  • C (1) temperature sensor – 45”
  • D (1) temperature sensor – 10’
  • E (4) self-tapping mounting screws
  • F (1) sensor ziptie
  • G (1) screwdriver
  • H (2) screws for high voltage shield

Supplies List

Truck stock items are required to install the controller:

  • conduit between the controller & evaporator
  • (2) conduit connectors (straight or elbow as required)
  • (4) high voltage wires (matched to LLS/compressor contactor & the controller load)
  • wire labeling (numbers colors etc
  • additional wire ties
  • 18 gauge twisted shielded pair (if extending sensor wires)
  • Cat5e (if adding communication)
  • foam insulation (if running wires outside the space)
  • silicone (for sealing any box penetrations)

Complete Instructions

Please visit:

http://ke2therm.com/product/ke2-temp-valve-control/

scroll down the page and click

Link to Literature

— OR —

use this QR code.

Wiring Diagram

KE2-Temp+Valve-Controller-FIG-4

Alternate Wiring Method

Basic Menu: “Out of Box” or if Superheat (SHt)

Setpoint Description Range Default
CtL Control Type – EEV+Temp, EEV Only, EEPR, EHGBP, Subcool SHt, SH, EPr,
HGb, SUb SHt

Edt

(Expansion device type)

| Valve Type: Mechanical (tHr), KE2- HSV (HS), KE2-RSV (rS), SEI, SER,

Carel (CrL), Custom (CUS)

| tHr, HS, rS, SEi ,SEr CrL, CUS*| rS
Only if CUS

is used for Edt

(valve type)

| Sr| Step Rate| 30 – 400| 30
SFS| Steps Full Stroke| 200- 6400| 500
Ub| Motor Type| Uni-(unipolar), bi (bipolar)| Unipolar
Only if inP (input) is

Pt under Advanced

Menu

| rFg| Refrigerant Type| See Refrigerant List below| 404
SSP| Superheat Setpoint| 5ºF (2.8K) to 50ºF (28K)| 8°F (4.4K)
tS| Temperature Setpoint| -50°F (-45°C) to 100°F (38°C)| 35°F (9.7°C)
AdF| Air Temperature Differential| 1°F (0.5K) to 30°F (17K)| 2°F (1.1K)
CSH| Compressor Starts/Hour Maximum| 5 (Off)** to 10| 6
dPd| Defrost Per Day| 0 to 12, CUS
| 4
Only if
dPd** (Defrosts

per Day) is CUS

| tOd| Time of Day| 00:00 to 23:59| 12:00
d1 to d12| Start time of Defrost #1 – #12| 00 – 23| diS (disabled)
dFt| Defrost Time| 6 min to 720 min| 45 min

  • Selecting CUS (custom) unlocks additional Setpoints.
    ** Min. superheat in Subcool control.
    *** Selecting fewer than 5 compressor starts per hour results in the starts per hour feature being turned off. The compressor will then function on temperature only.

Controller Navigation

The display will show room temp (rtp), superheat (SH), sution pressure (PrS) or leaving liquid temp (LLT) depending on control type and setup.

Indicator lights

  • Red light – Critical alarm (system is NOT running).
  • Yellow light – Non-critical alarm (system running).
  • Green light – Liquid Line Solenoid (LLS) relay energized.
  • Green blinking – Waiting on min. run or min. off timer to energize/de-energize LLS relay.
  1. Access Setpoint mode by pressing and holding until (CtL ontrol type) displays on the screen
  2. Use and to advance through available setpoints.
  3. Press to view the current setting.
  4. Press to move between digits to accelerate the changes.
  5. Use and to change the setpoint
  6. Press and hold to confirm each setpoint change
  7. Press back to escape.

Service Call Saver- Post Defrost Indicator
The display will switch between room temp and dEF after a defrost. The controller will refrigerate as normal, and dEF will clear automatically.

Accessing the Menus

For a complete list of setpoints and descriptions see Q.3.49.

Footnotes

  1. Not shown if in EEPR, EHGBP, SH, or SUb control, and input is pressure.
  2. Only shown if SUb control is selected.
  3. Only shown if SH, SHt, or SUb control is selected.
  4. Only if SH, SHt, or SUb and Pt control is selected .
  5. Only shown if input is pressure for EEPR or EHGBP
  6. Only shown if in SH, SHt, or SUB control and tt selected.
  7. P ress & hold ENTER for 3 seconds to activate.
  8. Press BACK button to return to normal operation.
  9. Press ENTER to enter manual valve control, & to adjust, and press BACK to exit.

Alarm List

Refrigerant List

Refrigerant Abbreviation
R-22 R22
R-134a 134
R-404A 404
R-407A 40A
R-407C 40C
R-410A 410
R-717 717
R-422A 42A
R-422D 42d
R-507 507
Refrigerant Abbreviation
--- ---
R-448A 448
R-449A 449
R-450A 450
R-438A 438
R-408A 408
R-409A 409
R-407F 407
R-744 744
R-513A 513
R-458A 458

© Copyright 2021 KE2 Therm Solutions, Inc., Washington, Missouri 63090 Q.3.66 June 2021 supersedes all prior publications.
KE2 Therm Solutions
12 Chamber Drive . Washington, MO 63090 1.888.337.3358 . www.ke2therm.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals