KE2 Temp + Valve Controller User Guide
- June 2, 2024
- KE2
Table of Contents
- KE2 Temp + Valve Controller
- What’s in the KE2 Temp + Valve kit, pn 21301
- Supplies List
- Complete Instructions
- Wiring Diagram
- Alternate Wiring Method
- Controller Navigation
- Indicator lights
- Accessing the Menus
- Alarm List
- Refrigerant List
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
KE2 Temp + Valve Controller
This reference should remain on site with the installed KE2 Temp + Valve controller.
KE2 Temp+Valve Control
For Temp. Air Defrost, and Electronic Valve Control Condensed Quick Start
Guide KIT PN 21301
What’s in the KE2 Temp + Valve kit, pn 21301
- A (1) KE2 Temp + Valve controller (pn21393 – controller only)
- B (1)10’ pressure transducer
- C (1) temperature sensor – 45”
- D (1) temperature sensor – 10’
- E (4) self-tapping mounting screws
- F (1) sensor ziptie
- G (1) screwdriver
- H (2) screws for high voltage shield
Supplies List
Truck stock items are required to install the controller:
- conduit between the controller & evaporator
- (2) conduit connectors (straight or elbow as required)
- (4) high voltage wires (matched to LLS/compressor contactor & the controller load)
- wire labeling (numbers colors etc
- additional wire ties
- 18 gauge twisted shielded pair (if extending sensor wires)
- Cat5e (if adding communication)
- foam insulation (if running wires outside the space)
- silicone (for sealing any box penetrations)
Complete Instructions
Please visit:
http://ke2therm.com/product/ke2-temp-valve-control/
scroll down the page and click
Link to Literature
— OR —
use this QR code.
Wiring Diagram
Alternate Wiring Method
Basic Menu: “Out of Box” or if Superheat (SHt)
Setpoint | Description | Range | Default |
---|---|---|---|
CtL | Control Type – EEV+Temp, EEV Only, EEPR, EHGBP, Subcool | SHt, SH, EPr, | |
HGb, SUb | SHt |
Edt
(Expansion device type)
| Valve Type: Mechanical (tHr), KE2- HSV (HS), KE2-RSV (rS), SEI, SER,
Carel (CrL), Custom (CUS)
| tHr, HS, rS, SEi ,SEr CrL, CUS*| rS
Only if CUS
is used for Edt
(valve type)
| Sr| Step Rate| 30 – 400| 30
SFS| Steps Full Stroke| 200- 6400| 500
Ub| Motor Type| Uni-(unipolar), bi (bipolar)| Unipolar
Only if inP (input) is
Pt under Advanced
Menu
| rFg| Refrigerant Type| See Refrigerant List below| 404
SSP| Superheat Setpoint| 5ºF (2.8K) to 50ºF (28K)| 8°F (4.4K)
tS| Temperature Setpoint| -50°F (-45°C) to 100°F (38°C)| 35°F (9.7°C)
AdF| Air Temperature Differential| 1°F (0.5K) to 30°F (17K)| 2°F (1.1K)
CSH| Compressor Starts/Hour Maximum| 5 (Off)** to 10| 6
dPd| Defrost Per Day| 0 to 12, CUS| 4
Only if dPd** (Defrosts
per Day) is CUS
| tOd| Time of Day| 00:00 to 23:59| 12:00
d1 to d12| Start time of Defrost #1 – #12| 00 – 23| diS (disabled)
dFt| Defrost Time| 6 min to 720 min| 45 min
- Selecting CUS (custom) unlocks additional Setpoints.
** Min. superheat in Subcool control.
*** Selecting fewer than 5 compressor starts per hour results in the starts per hour feature being turned off. The compressor will then function on temperature only.
Controller Navigation
The display will show room temp (rtp), superheat (SH), sution pressure (PrS) or leaving liquid temp (LLT) depending on control type and setup.
Indicator lights
- Red light – Critical alarm (system is NOT running).
- Yellow light – Non-critical alarm (system running).
- Green light – Liquid Line Solenoid (LLS) relay energized.
- Green blinking – Waiting on min. run or min. off timer to energize/de-energize LLS relay.
- Access Setpoint mode by pressing and holding until (CtL ontrol type) displays on the screen
- Use and to advance through available setpoints.
- Press to view the current setting.
- Press to move between digits to accelerate the changes.
- Use and to change the setpoint
- Press and hold to confirm each setpoint change
- Press back to escape.
Service Call Saver- Post Defrost Indicator
The display will switch between room temp and dEF after a defrost. The
controller will refrigerate as normal, and dEF will clear automatically.
Accessing the Menus
For a complete list of setpoints and descriptions see Q.3.49.
Footnotes
- Not shown if in EEPR, EHGBP, SH, or SUb control, and input is pressure.
- Only shown if SUb control is selected.
- Only shown if SH, SHt, or SUb control is selected.
- Only if SH, SHt, or SUb and Pt control is selected .
- Only shown if input is pressure for EEPR or EHGBP
- Only shown if in SH, SHt, or SUB control and tt selected.
- P ress & hold ENTER for 3 seconds to activate.
- Press BACK button to return to normal operation.
- Press ENTER to enter manual valve control, & to adjust, and press BACK to exit.
Alarm List
Refrigerant List
Refrigerant | Abbreviation |
---|---|
R-22 | R22 |
R-134a | 134 |
R-404A | 404 |
R-407A | 40A |
R-407C | 40C |
R-410A | 410 |
R-717 | 717 |
R-422A | 42A |
R-422D | 42d |
R-507 | 507 |
Refrigerant | Abbreviation |
--- | --- |
R-448A | 448 |
R-449A | 449 |
R-450A | 450 |
R-438A | 438 |
R-408A | 408 |
R-409A | 409 |
R-407F | 407 |
R-744 | 744 |
R-513A | 513 |
R-458A | 458 |
© Copyright 2021 KE2 Therm Solutions, Inc., Washington, Missouri 63090 Q.3.66
June 2021 supersedes all prior publications.
KE2 Therm Solutions
12 Chamber Drive . Washington, MO 63090 1.888.337.3358 .
www.ke2therm.com