KE2 thermsolutions + Air Defrost Controller User Guide

June 5, 2024
KE2 thermsolutions

KE2 thermsolutions + Air Defrost Controller

KE2-thermsolutions-Air-Defrost-Controller-product

Complete Instructions Locations

Visit: http://ke2therm.com/product/ke2-temp-defrost/and click the Link to Literature buttonKE2-thermsolutions-Air-Defrost-
Controller-2

What’s in the Kit

The following parts are included:

  • A(1) KE2 Temp + Air Defrost controller
  • B(1) temperature sensor – 45″
  • C(1) sensor zip tie
  • D(1) liquid-tight cord grip
  • E(4) self-tapping mounting screws
  • F(2) screws for high voltage shield
  • G(1) programming sticker
  • H(1) high voltage shield

Supplies List

The accessories required for the controller to work are supplied. However, some truck stock items may be needed. See the following list.

  • Conduit to go between the controller & evaporator
  • (2) conduit connectors (straight or elbow as required)
  • (4) high voltage wires (matched to the load of the liquid line solenoid compressor and the controller)
  • wire labeling (numbers, colors, etc.)
  • additional wire ties
  • 18 gauge twisted shielded pair (if extending sensor wires
  • Cat5e or cable rated for RS-485 communication (if adding communication)
  • foam insulation (if running wires outside the space)
  • silicone (for sealing any box penetrations)

Controller Navigation

  • Red blinking – Real Time Clock battery needs to be replaced
  • Yellow light – non-critical alarm (system running)
  • Greenlight- Liquid Line Solenoid (LLS) relay energized
  • Green blinking -waiting on minimum run or off timer to start/stop refrigeration
  • Access Setpoint mode by pressing and holding ENTER Until tS (temperature setpoint) displays on the screen.
  • UseAand to scroll through available setpoints.
  • Press CNTER to view the current setting.
  • USA and to change the setpoint
  • Press ENTER to move between the digits to accelerate the changes.
  • Press and hold wTE to confirm each setpoint change.
  • PressGACK to escape.

Setpoints

KE2-thermsolutions-Air-Defrost-
Controller-3333

Alarms When amber LED is lit:

  • SSA = Shorted Sensor Alarm
  • OSA= Open Sensor Alarm
  • HCA = High Temp Alarm
  • Ltd Low Temp Alarm
    For a complete list of points and descriptions see Q.3.20.

Basic Setpoints 

KE2-thermsolutions-Air-Defrost-
Controller-4

Dimensions – Inches

KE2-thermsolutions-Air-Defrost-
Controller-5

Wiring Diagram

KE2-thermsolutions-Air-Defrost-
Controller-6

Copyright 2022 KE2 Therm Solutions, Inc., Washington, MissOuri 63090
Q.3.65 April 2022 supersedes all prior publications
KE2 Therm Solutions
12 Chamber Drive . Washington, MO 63090
1-888-337-3358. www.ke2therm.com