FRESH-AIRE UV UV 247 24 Volt Germicidal UV Light Instruction Manual

June 3, 2024
FRESH-AIRE UV

FRESH-AIRE UV UV 247 24 Volt Germicidal UV Light Instruction Manual
FRESH-AIRE UV UV 247 24 Volt Germicidal UV Light

UV247 is installed inside the air handling system to reduce biological contamination for reduced system maintenance and improved indoor air quality.

IMPORTANT!

  • Only qualified technicians should install this product
  • Install in accordance with relevant building codes
  • Read instructions carefully including safety warnings

Parts Included

Parts Included
Parts Included

  • A UV Lamp
  • B Power Supply
  • C UV Warning Sticker
  • D Magnetic Bracket
  • E Self-Tapping Screws
  • F Sight Glass
  • G Tap-in Connector
  • H Plastic Nuts

Installation Notes

Before installing UV247 it is necessary to determine the optimal mounting location inside the air system. First, look for the area with the heaviest mold growth. Also consider a location that will allow the germicidal UV light to shine on the greatest surface area. For enhanced antimicrobial effect 2 or more lamps can be installed in different parts of the air system.

Some typical mounting locations:
UV247 Mounting Options
Installation Notes

  • A Supply-side duct
  • B At the blower
  • C Across top of coils
  • D Coil face
  • E Coil “A” plate
  • F Return-side duct

WARNING
PROTECT EYES FROM UV LIGHT
TURN OFF UNIT OR DISCONNECT BEFORE SERVICING

Important: some materials inside the air system (including filter media, flex duct, wiring etc.) may not be UV light resistant.
Use the optional UV shield (part #TUV-SHIELD-LPC) or cover the materials with reflective tape.

Air Handler Interior Surface Installation

  1. Determine the optimal position for placement of the UV lamp.

  2. Use a utility knife to cut a slit in the insulation on the interior surface.
    Air Handler Interior Surface Installation

  3. Place the Magnetic Bracket directly on the metal surface or remove the magnet and hardmount the bracket using the Self-Tapping Screws provided. Use foil tape to close the cut in the insulation.

  4. Use plastic Quick-Nuts to attach the UV lamp to the Magnetic Bracket as shown.
    Air Handler Interior Surface Installation

Coil “A” plate Installation

  1. Snap the Magnetic Bracket apart by bending.
    Coil “A” plate Installation

  2. Drill a 1” hole in the “A”-plate then attach the smaller piece of the bracket using the Self-Tapping Screws.

  3. Insert the UV lamp into the hole then use the Plastic Nuts to attach the UV lamp to the Magnetic Bracket as shown.
    Coil “A” plate Installation

Power Supply Installation

IMPORTANT! Check which power supply is included with your UV247 before connecting to power. Turn off main power source before installation.

  1. Find a suitable location for the Power Supply inside the control panel of the air handler. Install using the Self Tapping Screws.
  2. Use the wiring diagrams below to connect to power.
    Power Supply Installation

IMPORTANT
Turn off main power source before installation.

IMPORTANT! Must be wired to constant power – do not connect to blower relay.
Power Supply Installation

IMPORTANT!
Systems with high 24 VAC loads may require the installation of a separate 24 VAC transformer to power the UV light.
Always use a separate 24 VAC transformer with “communicating” air systems.
Draws 16 VA, may need to do load calculation: Volts under load X Amps under load.

UV Lamp Connection

  1. When all the other components are properly installed connect the UV Lamp cable to the Power supply cable.
  2. Make sure the clips are aligned and then push the connectors firmly together.
    A tight connection ensures a proper seal.
    UV Lamp Connection

Sight Glass Installation

  1. Find a suitable location on the outside of the duct-work near the UV Lamp installation and apply the warning/lamp replacement sticker.
  2. Drill a ½” hole through the orange circle on the sticker. Press the UV safety viewport into hole.
  3. Turn on the power and use the sight glass to confirm that the UV Lamp is operating.
    Sight Glass Installation

Lamp Replacement

The germicidal UV lamp in UV247 needs to be replaced periodically. Note: UV lamps will continue to emit visible light but lose germicidal effectiveness over time.

UV Lamp
(Part # UV24L, UV24L-OS)
UV Lamp

CAUTION!
UV lamps contain small amounts of mercury – dispose of lamps in accordance with local environmental regulations. For more information visit www.lamprecycle.org
Note: Use of replacement UV lamps other than Part # UV24L, UV24L-OS voids warranty.