AcuityBrands DMX Interface PWINF DIN D2A 16-Channel Demultiplexer Instruction Manual

October 28, 2023
AcuityBrands

DMX Interface PWINF DIN D2A 16-Channel Demultiplexer

DMX Interface – PWINF DIN D2A 16-Channel Demultiplexer Manual

OVERVIEW

The PWINF DIN D2A DIN demultiplexer converts DMX512 signals into 16 channels of analog control voltage. The demultiplexer can also control Mark7-type fluorescent ballasts, solid state relays or LEDs. The module is RDM discoverable and configurable.

CONNECTIONS

The PWINF DIN D2A features terminal strips that can be removed from the card to facilitate easy wiring installation or replacement. Make the following connections, WITH THE POWER TURNED OFF.

POWER
The module will run on a range from 9 to 30 VDC at a maximum of 6 Watts. Observe the correct polarity when connecting the V+ and V-. A second set of terminals are provided on the connector to daisychain power to other DIN modules. The EARTH GROUND terminal must be connected to the enclosure’s chassis or electrical ground terminal to improve EMC compliance.

DMX512
DMX connections consist of a shield and data pair. Connect the DATA+ and DATA- wires to D1+ and D1- respectively for each of DMX IN and DMX THRU. Observe the same polarity convention throughout the system. Connect the cable shield to the SHLD COM terminal.
DMX THRU may be daisy-chained to the DMX IN of other DIN modules.

ANALOG OUTPUTS
Sixteen analog output terminals are provided in groups of four, each with a common terminal. All common terminals are internally connected, so only one needs to be tied to the device being controlled.
Outputs are rated up to 15 VDC, 10mA per channel, sourcing; or 30mA per channel, sinking. Maximum wire run is 150 meters (500 ft).

STATUS INDICATORS

POWER IN
Blue. Steady glow indicates power supply OK; off indicates no power.

PROCESSOR
Green. Steady glow indicates processor is OK; off when POWER IN is lit indicates processor failure.

DMX INPUT
Amber. Steady glow indicates port latched to active DMX source; off indicates no signal present.

FUNCTION
Amber. Indicates the function associated with the numeric display.

DMX TERMINATE

DMX rules require the last device on a DMX line to be terminated with a 120 resistor between pins 2 and 3 to prevent signal reflection. If there is no connection to the DMX THRU terminals, the DMX Terminate switch should be ON.

If there are other devices connected to the DMX THRU terminal, the DMX Terminate switch should be OFF and termination be applied to the final device in the daisy-chain.

diagram dmx

DMX Interface – PWINF DIN D2A

16-Channel Demultiplexer Manual

CONFIGURATION

To configure, first press the ▲ or ▼ buttons to select the desired function, indicated by the LED next to ADDRESS, MODE, MIN, MAX, or TEST. Once selected, press and hold the ENTER button until a dot appears in the lower
right-hand corner of the display. The card is now in EDIT mode.
When done editing a parameter, press ENTER. The dot will disappear, the new value will be saved and the unit will be ready for operation.

SET DMX ADDRESS

One in ADDRESS edit mode, press ▲ or ▼ to change the start
address to the desired value. Press ENTER to save the address.
Valid addresses range from 1 to 512.

SET OPERATING MODE

Once in MODE edit, choose from the following:
• MODE 1: 0-10VDC Output (MAX will read 158)
• MODE 2: 0-5VDC Output (MAX will read 79)
• MODE 3: 0-15VDC Output (MAX will read 237)
• MODE 4: 0-2.5VDC Output (MAX will read 40)
• MODE 5: Custom D-to-A (set your own voltage)
• MODE 6: EFBC/LED Control – 10% threshold
• MODE 7: Non-Dim (see below)
• MODE 8: EFBC/LED Control – 1% threshold

SET MIN AND MAX VOLTAGE OUTPUT LEVELS

To set a custom output voltage, confirm the DMX start address is set
to 1. Connect a voltmeter between output 1 and COM on the card.
Connect a DMX source to DMX IN. Using your source, vary the DMX
level on channel 1 and confirm that the voltage output is changing.
Set the DMX level to full.
Use the ▲ or ▼ buttons and ENTER to select MAX for editing.
Use ▲ or ▼ while observing the output on the voltmeter. Once the
voltage is at the level you desire, press ENTER to save. Repeat this
process to set a MIN level. Valid MIN levels are between 0 and 254.
Valid MAX levels are between 1 and 255. 255 roughly corresponds
to an output of 16VDC. Customizing these values will place the card
in Mode 5. MIN and MAX should be checked in Modes 6, 7 and 8,
with MAX set as a value of 158 to ensure proper operation of
the solid state relays.

NON-DIM CONTROL

Mode 7 provides non-dim control of solid state relays or LEDs. At a
DMX level of 0%, each channel outputs +10VDC. The output voltage
drops to zero when DMX passes 50%. All blocking diodes must be
shunted (bypassed) in this mode.

EFBC / LED CONTROL

Mode 6 and 8 allow unified control of up to eight circuits of LED
fixtures or Mark 7-type electronic fluorescent ballasts, with a
maximum of 20 fixtures/ballasts on each circuit. Two channels are
used for each circuit. Channels are paired: 1 with 9, 2 with 10, and
so on.
The lower channel provides 0-10VDC dimming control, while the
higher acts as a non-dim, when connected to a solid state relay
controlling the circuit’s AC supply. In mode 6, the non-dim triggers
when DMX passes through 10%. In mode 8, the non-dim threshold
is 1%. All blocking diodes must be shunted (bypassed) in this mode.

TEST MODE

Once in TEST mode, using the ▲ or ▼ buttons will toggle each
output on and off. The output number is shown on the right hand
display. DMX input is ignored while in TEST mode.

CCL PIN (PANIC INPUT)

Shorting the CCL pin to COM will drive all outputs to full.
The CCL input overrides the DMX input level.

SELF-TEST

Press the ▲ button while turning power on to enter self-test mode.
All LEDs will flash sequentially. The display will cycle 0 through 9,
then show the serial number and firmware version. Cycle power to
end self-test.

DIODE SHUNTS

The behavior of the diode shunts is dependent on the module’s
revision level .The revision number is shown on the product label,
next to the part number.
The diodes prevent the control signal from back-feeding into the
output and damaging the module. The diodes must removed from
the circuit to allow sinking control. The 16 DIP switches are wired
as shunts, allowing the diodes to be engaged or disengaged outputby-
output.
REV 4 and below: The blocking diodes are engaged by default. With
the shunt switches in the “off” position, the diodes will prevent current
backflow. This is the correct arrangement for driving analog dimmers.
With the shunts in the “on” position, the diodes are bypassed. This
is the correct arrangement for sinking control of EFBCs and LED
dimmers.
REV 5 and above: The blocking diodes are bypassed by default.
With the DIP switches in the “off” position, current will backflow
through the card. This is the correct arrangement to allow sinking
control of EFBCs and LED dimmers. With the DIP switches in the
“on” position, the diodes will block backflow current. This is the
correct arrangement for driving analog dimmers.

© 2021 Acuity Brands, Inc. • One Lithonia Way, Conyers GA 30012
Pathway Connectivity | #103 – 1439 17th Ave SE Calgary, AB Canada T2G 1J9
Phone: + 1 866 617 3074 www.pathwayconnect.com

DMX Interface – PWINF DIN D2A

16-Channel Demultiplexer

E1.20 RDM RESPONDER FEATURES

The PWINF DIN D2A is fully compliant with ANSI E1.20 Remote
Device Management as a responder device. An RDM Controller can
discover and set the card’s DMX start address, firmware version
and operating mode.
With Pathscape software, the user can upgrade the firmware in the
field. Download Pathscape from the Pathway website.

ELECTRICAL INFORMATION

• 1500V opto-isolation between DMX input and analog outputs
• 250V fault protection on DMX input port
• Input operating voltage: 9-30VDC
• 6W power consumption

Exceeding this rating may result in personal injury or
damage to this and other connected devices.

PHYISCAL

• 0.7 lbs (0.316 kg)
• 6.25”W x 4”H x 1.85”D (159mm x 103mm x 47mm)
• Operating conditions: 14°F-113°F (-10°C-45°C), 5-95%
relative humidity, non-condensing

COMPLIANCE

• ANSI E1.11 DMX512-A R2013
• ANSI E1.20 RDM – Remote Device Management
• ANSI E1.3 – 2001 (R2021), Lighting Control Systems –
0-10V Analog Control (with diode shunts on)
• ANSI C82.11 Fluorescent Ballast Control (diode shunts off)
• Suitable for many LED drivers using pink and purple wires
• RoHS 2011/65/EU + 2015/863
• CE
• Class 2 Low Voltage

© 2021 Acuity Brands, Inc. · One Lithonia Way, Conyers GA 30012 Pathway Connectivity | #103 – 1439 17th Ave SE Calgary, AB Canada T2G 1J9
Phone: + 1 866 617 3074 www.pathwayconnect.com
08/27/21