VIVE TP-S-955WH Programmable Thermostat Instruction Manual

June 16, 2024
Vive

VIVE TP-S-955WH Programmable Thermostat

Product Information

Specifications

  • Model : TP-S-955WH
  • Wireless Communication Options : FSK or ASK
  • Power Type : Battery Power or Hardwire (Common Wire)
  • Compatible Systems : Gas or Oil Heat, Electric Furnace, Heat Pump (No Aux. or Emergency Heat), Heat Pump (With Aux. or Emergency Heat), Multi-Stage Systems, Heat Only Systems, Cool Only Systems, Millivolt, Dual Fuel
  • Humidity Control : Yes
  • Installation : Requires trained and experienced technician

Product Usage Instructions

Wireless Type Selection:
The thermostat and base module have selectable wireless communication options. Each component has a jumper switch labeled FSK and ASK. The default setting is FSK.

Installation Tips

  1. Wall Locations : Install the thermostat approximately 4 to 5 feet above the floor in an area with average temperature and good air circulation.
  2. Thermostat Subbase Installation : Install the thermostat subbase horizontally or vertically using screws. For horizontal mount, use one screw on the left and one screw on the right. For vertical mount, use one screw on the top and one screw on the bottom.
  3. Electrical Hazard : Before installing the product, disconnect the power to avoid electrical shock or equipment damage.
  4. Mercury Notice : Dispose of any old product containing mercury properly. Contact your local waste management authority for recycling and proper disposal instructions.

Thermostat Quick Reference
Refer to the provided Thermostat Quick Reference guide for quick access to basic thermostat functions and settings.

Private Label Badge
Refer to the Private Label Badge section for information on customizing the thermostat with a private label badge.

Wireless Communication Tips
Learn about tips and best practices for maintaining wireless communication between the thermostat, base module, and other accessories.

Reestablishing Communication
If communication between the thermostat and base module is lost, follow the instructions in this section to reestablish communication.

Wiring
Refer to the provided Wiring guide for detailed instructions on wiring the thermostat and base module.

Technician Setup Menu
Access and navigate the technician setup menu to configure advanced settings and options for the thermostat.

Setting the Humidity
Follow the instructions in this section to set and control the humidity levels using the thermostat.

Programming
Refer to the Programming section for instructions on programming and scheduling temperature settings.

FAQ

  • Q: Can I install the product myself?
    A: No, this product must be installed by a trained and experienced technician.

  • Q: Can I use remote sensors with the thermostat?
    A: If you are using remote sensors, the thermostat must be hardwired.

  • Q: How do I reestablish communication if it is lost?
    A: Follow the instructions in the “Reestablishing Communication” section of the user manual to reestablish communication between the thermostat and base module.

Installation Manual
TP-S-955WH

Thermostat Application Guide

Description|
---|---
Gas or Oil Heat| Yes
Electric Furnace| Yes
Heat Pump (No Aux. or Emergency Heat)| Yes
Heat Pump (With Aux. or Emergency Heat)| Yes
Multi-Stage Systems| Yes
Heat Only Systems| Yes
Cool Only Systems| Yes
Millivolt| No
Humidity| Yes
Dual Fuel| Yes

Power Type

  • Battery Power
  • Hardwire (Common Wire)
  • Hardwire (Common Wire) with Battery Backup

A trained, experienced technician must install this product.
Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions.
If you are using remote sensors the thermostat must be hardwired.

Wireless Type Selection
The thermostat and base module contain selectable wireless communication options. Each component has a jumper switch label FSK and ASK. Default setting : FSK.

  • All components must be set to the same position for wireless communication.
  • Both modes utilize a 916 MHz frequency.
  • FSK : frequency-shift keying, is the recommended mode.
  • ASK : amplitude-shift keying, should be selected when using components that can not communicate with FSK.
    The images below illustrate the location of jumper switches for each item that has one. Note only the thermostat and Base Module are included in this package.

The table below lists the mode options for T955WH wireless thermostat and its accessories.

Component Mode Options
955WH Thermostat FSK or ASK
955WH Thermostat Base Module FSK or ASK
**RISW – Indoor Remote*** FSK or ASK
ROSW Outdoor **Remote*** FSK or ASK
RISW- Indoor Remote ASK
ROSW Outdoor Remote ASK
W150W – Wireless Repeater ASK

Installation Tips

Wall Location
The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation.

Do not install thermostat in these locations

  • Close to hot or cold air ducts
  • That are in direct sunlight
  • With an outside wall behind the thermostat
  • In areas that do not require conditioning
  • Where there are dead spots or drafts (in corners or behind doors)
  • Where there might be concealed chimneys or pipes

Installation Tip
Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building.

Thermostat Subbase Installation

  1. Horizontal Mount For horizontal mount put one screw on the left and one screw on the right.
  2. Vertical Mount For vertical mount put one screw on the top and one screw on the bottom.

Installation Tip: Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage

Mercury Notice
All of our products are mercury free. However, if the product you are replacing contains mercury, dispose of it properly. Your local waste management authority can give you instructions on recycling and proper disposal.

Base Module Subbase installation

  1. Horizontal Mount
  2. Vertical Mount

Wiring Not
Wire the base module’s subbase the same way you would wire a hardwired thermostat subbase.

Note
To connect the base module to the master thermostat, refer to the directions on page 13 of this manual.

Note
The base module must be hardwired (C and R terminals connected to 24V power.)

Mount Thermostat and Base Module

Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat/base module, then push gently until it snaps in place.
Note : To ensure a solid fit between the thermostat/base module and the subbase

  1. Mount subbase to a flat wall
  2. Use screws provided
  3. Drywall anchors should be flush with the wall
  4. Wires should be pushed into the wall

Battery Installation

Battery installation is optional if there are no remotes connected to the Master Thermostat (C terminal connected). If you connect an outdoor remote and/or indoor remote sensors it is required the thermostat be hardwired.
Important : High quality alkaline batteries are recommended. Rechargeable batteries or low quality batteries do not guarantee a 1-year life span.

Thermostat Quick Reference

Getting to know your thermostat

  1. Indicates the current room temperature

  2. Time and day of the week

  3. Low Battery Indicator : Replace batteries when this indicator is shown.

  4. Program Menu Options : Show different options during programming.

  5. Period Icons – This thermostat can have 2 or 4 programmable time periods per day. Icons are displayed for 4 time periods. Occupied and unoccupied will display in the text field for 2 time periods.

  6. REMOTE indicates a remote has control of the system.

  7. HOLD is displayed when thermostat program is permanently over ridden.

  8. Setpoint : Displays the user selectable setpoint temperature

  9. System Operation Indicators : The COOL, HEAT or FAN icon will display when the COOL, HEAT or FAN is on. NOTE: The compressor delay feature is active if these icons are flashing. The compressor will not turn on until the 5 minute delay has elapsed.

  10. Humidity : Shows the humidity target setpoint settings and keys.

  11. Clean Display : Pressing CLEAN DISPLAY will allow 30 seconds to clean the display. The keys will be inoperable during this time. CLEAN will appear if your contractor has programmed a filter change reminder. Press CLEAN when filter has been replaced to reset the filter change reminder timer.

  12. Next Zone : This button will appear if optional indoor remotes are present. By selecting NEXT ZONE you can cycle through each of the zones set up during the initial installation.

  13. System Information : Shows which zone or zones are controlling your system. Shown only when one or more indoor sensors are connected.

  14. LCD Display

  15. Glow in the dark light button

  16. Fan key

  17. System key

  18. Setpoint keys

  19. Menu key

  20. Scheduled time period Icons

Important
The low battery indicator is displayed when the AA battery power is low. If the user fails to replace the battery within 21 days, the screen will only show the low battery indicator but maintain all functionality. If the user fails to replace the batteries after an additional 21 days (days 22-42 since first “low battery” display) the setpoints will change to 55˚F (Heating) and 85˚F (Cooling). If the user adjusts the setpoint away from either of these, it will hold for 4 hours then return to either 55˚F or 85˚F. After day 63 the batteries must be replaced immediately to avoid freezing or overheating because the thermostat will shut the unit off until the batteries are changed.

Installation Tips
When performing an attic installation, instead of placing the base module in the attic, locate the closet nearest to the air conditioning unit. Then mount the base module high on the wall inside the closet or on the ceiling of the closet. This location will insure the base module is below the 150°F maximum ambient temperature specification.

Do not install the base module in locations

  • That are behind a chimney
  • Where temperature could exceed 150°F
  • Where rain or snow or extreme hot or cold is possible
    Note : This base module is NOT weatherproof.

Base Module – Basement Location

Wireless Range
Range between the thermostat and the base module is up to 100 feet with no obstructions and approximately 50 feet in standard residential construction. To extend the range try replacing the base unit higher if in a basement or further away from large metal objects.

Do not install the base module in locations

  • That are behind a chimney
  • Where temperature could exceed 150°F
  • Where rain or snow or extreme hot or cold is possible

Note: This base module is NOT weatherproof.

Private Label Badge

About The Badge
All of our thermostats use the same universal magnetic badge. Visit the company website to learn more about our free private label program.

Gently slide a screwdriver into the bottom edge of the badge. Gently turn the screwdriver counter clockwise. The badge is held on by a magnet in the well of the battery door. The badge should pry off easily. DO NOT USE FORCE.

Wireless Communication Tips

Follow these steps for a simple wireless communication setup

  1. Locate all components in area near equipment.

  2. Wire base module with 8ft
    pigtail and temporarily mount.
    If you are not able to establish communication, this will allow you to relocate the module to an area with less obstruction, without having to rewire.

  3. Install batteries in all devices you wish to use.
    Thermostat, indoor/outdoor sensors.

  4. A. Press the menu button on thermostat
    B. Press & hold tech set up button
    C. Configure the set up for your application
    D. Establish communication between devices

  5. Install thermostat in final location.
    Note : You must hardwire the thermostat when using remotes.

  6. Turn on fan from thermostat to ensure communication.
    Once communication is established, permanently mount module.

Troubleshooting
If there is no communication between the thermostat and base module devices that are less than 50ft. apart, utilize an 8ft. pigtail to relocate and reduce interference. If there is not communication and devices are over 50ft. apart, add a W150W – Wireless Repeater.

Reestablishing Communication

Establishing communication between master thermostat and the base module
The thermostat and base module come factory linked out of the box. If however, communication is lost, follow this easy- two step process to re- establish the communication link.

  1. Press and hold the base module button for 3 seconds. The Blue LED will flash when ready to receive initial signal from the thermostat. (Base module must be powered by 24V. Blue LED will be continuously on when 24V power is present.)
  2. Hold the light key (shown here) of the thermostat for 10 seconds, the Blue LED on the base module will stop flashing after communication has been established between base module and the thermostat.

Note : The blue LED on the base module will be on when power is present. The blue LED will flash 3 times every time it receives a signal from the thermostat. When a relay is on the corresponding LED relay indicator will be on.
Note : If the base module does not receive a signal from the thermostat for 15 minutes it will turn off all relays until communication is reestablished. The blue LED base module will also turn off to show communication has been lost.
Note : If communication has been lost for 1 hour and if freeze protection is enabled, heat and emergency heat relays will be turned on. The heat and emergency relays will turn on for 10 minutes every hour if there has been a call for heat in the last 24 hours.
Important : DO NOT hold the light button on the thermostat for more than 10 seconds after step 2 above has been completed. Holding the light button down will break the communication link and the base module button will need to be pressed again to reestablish communication.

Wiring

Caution : Electrical Hazar
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.

Wiring

  1. If you are replacing a thermostat, make note of the terminal connections on the thermostat that is being replaced. In some cases the wiring connections will not be color coded. For example, the green wire may not be connected to the G terminal.
  2. Loosen the terminal block screws. Insert wires then retighten the terminal block screws.
  3. Place nonflammable insulation into the wall opening to prevent drafts.

Warning
All components of the control system and the thermostat installation must conform to Class II circuits per the NEC Code.

Installation Tip
Do not overtighten terminal block screws, as this can damage the terminal block. A damaged terminal block can keep the thermostat from fitting on the subbase correctly or cause system operation issues .Max Torque = 6in-lbs.

Wiring Tips

  • C Terminal
    The C (common wire) terminal does not have to be connected when the thermostat is powered by batteries.

  • Wire Specifications
    Use shielded or non-shielded 18-22 gauge thermostat wire.

  • Note
    In many heat pump systems with no emergency heat relay, a jumper can be installed between E and

  • W2 to turn thermostat into a single stage control for Emergency Heat Operation.

Wiring

  1. Power supply

  2. Factory-installed jumper. Remove only when installing on 2-transformer systems

  3. Use either O or B terminals for changeover valve

  4. If DEHUM relay requires a normally-energized input, set dehumidify relay to NC in technician setup.

  5. Power supply

  6. Factory-installed jumper. Remove only when installing on 2-transformer systems

  7. Use either O or B terminals for changeover valve

  8. If DEHUM relay requires a normally-energized input, set dehumidify relay to NC in technician setup.

Terminal Designations on the Base Module
This thermostat is shipped from the factory to operate a conventional heating and cooling system. This thermostat may also be configured for a heat pump system. See the “heat pump” configuration step on page 23 of this manual to configure the thermostat for heat pump applications.

Terminal| 2 Heat 2 Cool Conventional System| 2 Heat 2 Cool Heat Pump System| 3 Heat 2 Cool Heat Pump System
---|---|---|---
RC| Transformer power (cooling)| Transformer power (cooling)| Transformer power (cooling)
RH| Transformer power (heating)| Transformer power (heating)| Transformer power (heating)
C| Transformer common| Transformer common| Transformer common
B| Energized in heating| Heat pump changeover valve energized in heating| Heat pump changeover valve energized in heating
O| Energized in cooling| Heat pump changeover valve energized in cooling| Heat pump changeover valve energized in cooling
G| Fan relay| Fan relay| Fan relay
W/E| First stage of heat| First stage of emergency heat| First stage of emergency heat
Y| First stage of cool| First stage of heat & cool| First stage of heat & cool
Y2| Second stage of cool| Second stage of cool| Second stage of cool & second stage of heat
W2| Second stage of heat| Auxiliary heat relay, second stage of heat| Auxiliary heat relay, third stage of heat
H| Humidify| Humidify| Humidify
D| Dehumidify| Dehumidify| Dehumidify

D Dehumidify Dehumidify Terminal Designations on the Master Thermostat

**** Terminal| 2 Heat 2 Cool Conventional System| 2 Heat 2 Cool Heat Pump System| 3 Heat 2 Cool Heat Pump System
---|---|---|---
R| 24 VAC transformer power| 24 VAC transformer power| 24 VAC transformer power
C| transformer common| transformer common| transformer common

Powering the Master Thermostat
If you add indoor or outdoor remote sensors to this wireless system you must hardwire the master thermostat.

  1. Power supply
  2. Factory-installed jumper. Remove only when installing on 2-transformer systems
  3. Use either O or B terminals for changeover valve
  4. If DEHUM relay requires a normally-energized input, set dehumidify relay to NC in technician setup.

Technician Setup

This thermostat has a technician setup menu for easy installer configuration. To set up the thermostat for your particular application

  1. Press the MENU button.
  2. Press and hold the technician setup button for 3 seconds. This 3 second delay is designed so that homeowners do not accidentally access the installer settings.
  3.  Configure the installer options as desired using the table below. Use the keys to change settings and the next step or previous step key to move from one step to another. Note: Only press the DONE key when you want to exit the Technician Setup options.
  4.  Press the DONE key to exit.

Tech Setup Steps| LCD Will Show| Adjustment Options| Default
---|---|---|---
Filter Change Reminder| This feature will flash a reminder after the elapsed run time to remind the user to change the filter. A setting of “OFF” will disable this feature.| OFF| You can adjust the filter change reminder from “OFF” to 2000 hours of fan runtime in 50 hour increments.| OFF
Room Temperature Calibration| This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70˚ and you would like it to read 72˚ then select +2.| 0 Calibrate| You can adjust the room temperature display to read up to 4˚above or below the factory calibrated reading.| 0˚F
Minimum Compressor On Time| This feature allows the installer to select the minimum run time for the compressor. For

example, a setting of 4 will force the compressor to run for at least 4 minutes every time the compressor turns on, regardless of the room temperature.

| OFF| You can set the minimum compressor run time to “OFF”, “3”, “4”, or “5” minutes. If 3,4 or 5 is selected, the compressor will run for

at least the selected time before turning off.

| OFF

Keypad Lockout Note : The selected keypad lockout functionality must be activated after exiting tech setup. If you do not perform this procedure, all keys will function freely. To lock the keypad hold down the keys for 3 seconds. You will see a lock in the display. To unlock the display hold down the keys for 3 seconds.

Tech Setup Steps| LCD Will Show| **Adjustment Options ** Default
---|---|---
Compressor Short Cycle Delay| The compressor short cycle delay protects the compressor from “short cycling”. This feature will not allow the compressor to be turned on for 5 minutes after it was last turned off.| ON OF

CO

| Selecting “ON” will not allow the compressor to be turned on for 5 minutes after the last time the compressor was on. Select “OF” to remove this delay.| ON
Cooling Swing| The swing setting often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles.| 0.5  dF CO| The cooling swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the cooling on at approximately 0.5˚ above the setpoint and turn the cooling off at approximately 0.5˚ below the setpoint.| 0.5˚
Heating Swing| The swing setting often called “cycle rate”, “differential”, or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles.| 0.5  dF HE| The heating swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the heating on at approximately 0.5˚ below the setpoint and turn the heating off at 0.5˚ above the setpoint.| 0.4˚
Keypad Lockout| Keypad lockout allows you to configure the thermostat so that some or all of the keys don’t function.| PA| PA= partial keypad lockout, which locks all the keys except the  or keys.

FU= full keypad lockout, which locks out all the keys. See Keypad Lockout Note

| PA

Swing Setting Tip
The second stage will turn on at 2x the swing setting. The second stage will turn off when 1x the swing is reached. For example, if the swing setting is .5 degrees for heating and the thermostat is set at 70˚F, the first stage will turn on at approximately 69.5˚F. The second stage will turn on at 69˚F. The second stage will turn off at 69.5˚F and the first will turn off at 70.5˚F. If the third stage is used, it will turn on at 68.5˚F and turn off at approximately 69˚F.

Tech Setup Steps| LCD Will Show| Adjustment Options| Default
---|---|---|---
Heating Temperature Setpoint Limit| This feature allows you to set a maximum heating setpoint limit. The setpoint temperature cannot be raised above this value.| 90

HE

| Use the  or key to select the maximum heat setpoint.| 90˚F
Cooling Temperature Setpoint Limit| This feature allows you to set a minimum cooling setpoint limit. The setpoint temperature cannot be lowered below this value.| 44

CO

| Use the  key to select the minimum cool setpoint.| 44˚F
˚F or ˚C| This feature allows you to display temperatures in either Fahrenheit or Celsius.| O 74 F|

  • F for Fahrenheit
  • C for Celsius

| ˚F
12 or 24 Hour Clock| You can select either a 12 or 24 hour clock setting.| 12H| Use the key to select 12 or 24 hour clock.| 12
HOUR CLOCK

Morning Recovery

| This feature will start heating early to bring the building temperature to its programmed setpoint by the beginning of the WAKE, OCCUPIED time period.| ON| Use the  key to turn on or off.| ON
Program Options| You can configure this thermostat to have a 7 day program, a 5+1+1 program or as nonprogrammable.| 5d| Use the  key to select 7d for 7 day, 5d for 5+1+1, or 0d for nonprogrammable.| 5d
Time Periods| You can configure this thermostat to have 2 or 4 programmable time periods per day. 4 time periods are Wake, Leave, Return & Sleep. 2C time periods are Occupied & Unoccupied. 4C time periods are Occupied 1, Unoccupied 1, Occupied 2, & Unoccupied 2.| 4| Use the key to select 4, 2c , or 4c time periods per day.| 4
Tech Setup Steps| LCD Will Show| Adjustment Options| Default
---|---|---|---
Pre-Occupancy Fan|

  • The pre-occupancy fan settings will energize the fan before the occupied time to provide ventilation prior to scheduled occupancy.
  • This feature only shows if the technician setup step for time periods is set to 2C or 4C.

| OFF
PRE OCCUPY FAN|

  • You can select the
  • pre-occupancy fan from OFF, 1, 2, or 3 hours.
  • If 1, 2, or 3 is selected, the fan will turn on that many hours prior to the scheduled occupied time period.

| OFF
Display Light|

  • The display light can be configured to stay on all the time or come on when any key is pressed.
  • NOTE : HARDWIRE ONLY
  • Keeping the display light continually “ON” will greatly reduce battery life.

| dL|

  • Use the key to to turn on or off.
  • OFF configures the display light to come on when the light key or any button is pressed.
  • ON configures the display light to stay on.

| OFF
Contractor Call Number|

  • Allows you to put your phone number in the display.
  • You can choose ON or OFF.

| OFF|

  • If selected ON, you will see the input screen after pressing NEXT STEP.
  • Use the key to select the desired number and the key to move from one character to another. See note below for operation.

|

OFF

Beep|

  • When any key is pressed an audible beep will sound.
  • You can choose ON or OFF.

| b|

  • If ON is selected the beep will sound.
  • If OFF is selected there is no sound.

| ON

Contractor Call Number Note
If contractor call number is selected ON, the phone number entered will show in the display if there has been a continuous call for heating or cooling for 24 hours or if the light button is held down for 3 seconds. To remove the phone number from the display, hold the light button down for 3 seconds.

Tech Setup Steps| LCD Will Show| Adjustment Options| Default
---|---|---|---
Stages of Heat| You can configure the thermostat to operate a 3 stage heat pump system.

2H 2C = 2 heat, 2 cool.
3H 2C = 3 heat, 2 cool.

This feature is shown only if the HEAT PUMP technician setup step is ON.

| 2H2C
STAGE| Use the key to change between 2 or 3 stages of heat. 2 heat will use Y1 as first stage and W2 as auxiliary.

3 heat will use Y1 as the first stage, Y2 as the second stage and W2 as the auxiliary.

| 2
STAGES

Note : When the dehumidify terminal is configured as normally-closed, the base module D terminal LED indicator will be lit when the relay is closed. When the thermostat calls for dehumidification, the D terminal LED indicator will turn off.

HUM Terminal

OPTIONS HUM terminal energizes when the ambient humidity is…
1 Below the humidity setpoint and heat or fan is energized.
2 Below the humidity setpoint and heat is energized.
3 Below the humidity setpoint. It will also energize the fan during a call

for humidity.
4| Below the humidity setpoint.

DHM Terminal

OPTIONS DUM terminal energizes when the ambient humidity is…
1 Above the humidity setpoint and cool or fan is energized.
2 Above the humidity setpoint. It will also energize the fan during a call

for dehumidify.
3| Above the humidity setpoint.
4| Above the humidity setpoint and the compressor is not running.

Note
Up to four indoor temperature sensors can be connected to one thermostat. This allows for 5 sensing points (zones). For example: the local (thermostat) plus four indoor sensors enables 5 sensing points.
To connect an indoor sensor to a thermostat, select 1 on the FINDING SENSOR technician setup step. Then hold down the light button on the indoor sensor until it beeps, while in ZONE technician setup step on the indoor sensor. To connect a second indoor sensor change the thermostat to read 2 and change the indoor sensor to zone 2. The zone setting must match between the thermostat and the indoor sensor to connect. When the connection is established the thermostat will show FOUND + NAME of the indoor sensor in the system information area of display.

Balance Point
The system operates differently when a balance point is used. On a dual fuel system, the balance point outdoor temperature setting will be the outdoor temperature at which the thermostat chooses either the heat pump or gas furnace. For example: A balance point setting of 30°F will turn on only the heat pump above 30°F and only the gas furnace below 30°F. Y1 will be stage one above 30°F and W2 will be stage one below 30°F. A heat pump with electric auxiliary will energize the heat pump above and below balance point. The electric auxiliary will only energize below balance point. For Example: A balance point setting of 40°F, will turn on the heat pump above 40°F and turn on the heat pump and electric auxiliary below 40°F.

Reminders
Once a reminder has been turned on and set, the elapsed time can be checked by navigating to its tech setup step. The elapsed time will then appear in the text field. It can also be reset at that time by holding down the set CLEAN button for 3 seconds. Resetting an expired reminder can be done without entering tech setup, by holding down the set CLEAN button for 3 seconds from the home screen.

Setting The Humidity

Setting The Humidity
Follow the steps below to change your target humidity setpoint.

Press the humidity button. Use the button to select the target humidity setpoint. Press DONE when completed.

Note
The target humidity setpoint is not programmable. Unlike temperature, humidity does not change quickly and should not be programmed.
Note
Humidity is only energized during heat. Dehumidify is only energized during cool. Heat and cool each have their own target setpoints.

Ambient Humidity Display
Ambient humidity will flash opposite the day and time, if the optional outdoor temperature sensor is installed the ambient outdoor temperature will also cycle in the display.

Increasing Humidity
The table on the right shows recommended indoor humidity levels in relation to outdoor temperatures during heating (adding humidity).
Consult your professional HVAC technician for recommended settings for your climate.

Programming

Set Time (If using programming)

Follow the steps below to set the day of the week and current time

  1.  Press the MENU button.
  2.  Press Set Time.
  3. Day of the week is flashing. Use the key to select the current day of the week.
  4. Press Next Step.
  5. The current hour is flashing. Use the key to select the current hour. When using 12-hour time, make sure the correct a.m. or p.m. choice is selected.
  6. Press Next Step.
  7. Minutes are now flashing. Use key to  the select current minutes.
  8. Press DONE when completed.

Programming
All our programmable thermostats are shipped with an energy saving default program. You can customize this default program by following the instructions in the set program schedule section starting on page 34.
Your thermostat can be programmed to have each day of the week programmed uniquely (7 days), all the weekdays the same with a separate program for Saturday and a separate program for Sunday (5+1+1), or non-programmable. For the 7-day and 5+1+1 programming modes, there are three time period options.

  1. “4” Residential (WAKE, LEAVE, RETURN, SLEEP)
  2. “2C” Commercial (OCCUPIED, UNOCCUPIED)
  3. “4C” Commercial (OCCUPIED 1, UNOCCUPIED 1, OCCUPIED 2, UNOCCUPIED 2)

This thermostat has a programmable fan feature, which allows you to run the fan continually during any time period.

Custom Program

Day of the Week| Events| Time| Setpoint Temperature (HEAT)| Setpoint Temperature (COOL)
---|---|---|---|---
Weekday| Wake/OCC1| |
Leave/UNOCC1| |
Return/OCC2| |
Sleep/UNOCC2| |
Occupied| |
Unoccupied| |
Saturday| Wake/OCC1| |
Leave/UNOCC1| |
Return/OCC2| |
Sleep/UNOCC2| |
Occupied| |
Unoccupied| |
Sunday| Wake/OCC1| |
LeaveUNOCC1| |
Return/OCC2| |
Sleep/UNOCC2| |
Occupied| |
Unoccupied| |

Set Program Schedule For Two Time Periods
To customize your 5+1+1 Program schedule, follow these steps: Weekday

  1.  Select HEAT or COOL with the SYSTEM key.
    Note : You have to program heat and cool each separately.

  2. Press the MENU button (If menu does not appear first, press RUN SCHED).

  3. Press SET SCHED. Note : Monday-Friday is displayed and the OCCUPIED text is shown. You are now programming the OCCUPIED time period for the weekday setting.

  4. Use the key to make your time selection for the weekday OCCUPIED time period. Note: If you want the fan to run continuously during this time period, select ON with the FAN key.

  5. Then use the key to make your setpoint selection for the weekday OCCUPIED period.

  6.  Press Next Step.

  7.  Repeat steps 4 through 6 for the weekday UNOCCUPIED time period.

Saturday
Repeat steps 4 through 6 for the Saturday OCCUPIED time period and for the Saturday UNOCCUPIED time period.
Sunday
Repeat steps 4 through 6 for the Sunday OCCUPIED time period, and for the Sunday UNOCCUPIED time period.

Default Programming

Factory Default Program

Day of the Week| Events| Time| Setpoint Temperature (HEAT)| Setpoint Temperature (COOL)
---|---|---|---|---
Weekday| Wake/OCC1| 6 AM| 70˚F (21˚C)           75˚F (24˚C)
Leave/UNOCC1| 8 AM| 62˚F (17˚C)           83˚F (28˚C)
Return/OCC2| 6 PM| 70˚F (21˚C)           75˚F (24˚C)
Sleep/UNOCC2| 10 PM| 62˚F (17˚C)           78˚F (26˚C)
Saturday| Wake/OCC1| 6 AM| 70˚F (21˚C)           75˚F (24˚C)
Leave/UNOCC1| 8 AM| 62˚F (17˚C)           83˚F (28˚C)
Return/OCC2| 6 PM| 70˚F (21˚C)           75˚F (24˚C)
Sleep/UNOCC2| 10 PM| 62˚F (17˚C)           78˚F (26˚C)
** Sunday| Wake/OCC1| 6 AM| 70˚F (21˚C)           75˚F (24˚C)
LeaveUNOCC1| 8 AM| 62˚F (17˚C)           83˚F (28˚C)
Return/OCC2| 6 PM| 70˚F (21˚C)           75˚F (24˚C)
Sleep/UNOCC2| 10 PM| 62˚F (17˚C)           78˚F (26˚C)
Day of the Week| Events| Time| Setpoint Temperature (HEAT)| Setpoint Temperature (COOL)
---|---|---|---|---
**
Weekday| OCCUPIED| 8 AM| 70˚F (21˚C)           72˚F (22˚C)
UNOCCUPIED| 6 PM| 64˚F (18˚C)           80˚F (27˚C)
Saturday| OCCUPIED| 8 AM| 70˚F (21˚C)           72˚F (22˚C)
UNOCCUPIED| 6 PM| 64˚F (18˚C)           80˚F (27˚C)
Sunday| OCCUPIED| 8 AM| 70˚F (21˚C)           72˚F (22˚C)
UNOCCUPIED| 6 PM| 64˚F (18˚C)           80˚F (27˚C)

You can use the table on the next page to plan your customized program schedule if using 5+1+1.

To customize your 7 day program schedule, follow these steps
Monday

  1. Select HEAT or COOL with the SYSTEM key.
    Note : You have to program heat and cool each separately.

  2. Press the MENU button (If menu does not appear first press RUN SCHED).

  3. Press SET SCHED. Note: Monday is displayed and the OCCUPIED text is shown. You are now programming the OCCUPIED time period for that day.

  4. Use the key to make your time selection for the OCCUPIED time period. Note : If you want the fan to run continuously during this time period, select ON with the FAN key.

  5. Then use the key to make your setpoint selection  for that day’s OCCUPIED period.

  6. Press NEXT.

  7. Repeat steps 4 through 6 for that day’s UNOCCUPIED time period.

Repeat steps 4 through 6 for the remaining days of the week.
A Note About Programmable Fan
The programmable fan feature will run the fan continuously during any time period it is programmed to be on. This is the best way to keep the air circulated and to eliminate hot and cold spots in your building.

Set Program Schedule For Four Time Periods

(WAKE, LEAVE, RETURN, SLEEP or OCCUPIED 1, UNOCCUPIED1, OCCUPIED 2, UNOCCUPIED 2)
To customize your 5+1+1 Program schedule, follow these steps
Weekday

  1. Select HEAT or COOL with the system key.
    Note : You have to program heat and cool each separately.

  2. Press the MENU button (If menu does not appear first press RUN SCHED).

  3. Press SET SCHEDULE. Note: Monday-Friday is displayed and the WAKE/OCC1 icon is shown. You are now programming the WAKE/OCC1 time period for the weekday setting.

  4. Use the key to make your time

  5. selection for the weekday WAKE/OCC1 time period.
    Note : If you want the fan to run continuously during this time period, select ON with the FAN key.

  6. Then use the key to make your setpoint selection for the weekday WAKE/OCC1

  7. period.

  8. Press Next Step.

  9. Repeat steps 4 through 6 for the weekday LEAVE/UNOCC1 time period, for the weekday RETURN/OCC2 time period, and for the weekday SLEEP/UNOCC2 time period.

Saturday
Repeat steps 4 through 6 for the Saturday WAKE/OCC1 time period, LEAVE/UNOCC1 time period, RETURN/OCC2 time period, and for the Saturday SLEEP/UNOCC2 time period.
Sunday
Repeat steps 4 through 6 for the Sunday WAKE/OCC1 time period, LEAVE/UNOCC1 time period, RETURN/OCC2 time period, and for the Sunday SLEEP/UNOCC2 time period.

To customize your 7 day Program schedule, follow these steps
Monday

  1. Select HEAT or COOL with the SYSTEM key.
    Note : You have to program heat and cool each separately.

  2. Press the MENU button (If menu does not appear first, press RUN SCHED).

  3. Press SET SCHED. Note: Monday is displayed and the WAKE/OCC1 icon is shown. You are now programming the WAKE/OCC1 time period for that day.

  4. Use the key to make your time

  5. selection for that day’s WAKE/OCC1 time period.
    Note : If you want the fan to run continuously during this time period, select ON with the FAN key.

  6. Then use the key to make your setpoint selection for that day’s WAKE/OCC1 period.

  7. Press Next Step.

  8. Repeat steps 4 through 6 for that day’s LEAVE/UNOCC1 time period, for that day’s RETURN/OCC2 time period, and for that day’s SLEEP/UNOCC2 time period.

Repeat steps 4 through 6 for the remaining days of the week.
A Note About Auto Changeover
In Auto you have the ability to switch between Auto Heat or Auto Cool by pressing the system key. This can be done once the current mode has reached its setpoint. For example: if in Auto Heat, the heat setpoint must be satisfied before the thermostat will allow you to switch to Auto Cool. You can switch out of Auto by holding down the SYSTEM key. To get back into Auto, you must toggle the system key to Auto.

Features

Temporary & Permanent Hold Feature

  • Temporary Hold : The thermostat will display HOLD and Run Schedule on the bottom of the screen when you press the key. If you do nothing, the temperature will remain at this setpoint temporarily for 4 hours. The program setpoint will then replace the temporary setpoint.
  • Permanent Hold : With a temporary hold set, If you press the HOLD key at the bottom of your screen, you will see HOLD appear next to the setpoint temperature in the display. The thermostat will now permanently stay at this setpoint and can be adjusted using the keys.
  • To Return To Program : Press the Run Schedule key at the bottom of the screen to exit temporary and permanent holds.

Filter Change Reminder
If your installing contractor has configured the thermostat to re-mind you when the air filter needs changed, you will sea reminder in the display when your air filter needs changed. the reminder will be shown in the display after your system has run long enough to require an air filter change.
Resetting the filter change reminder: When the reminder is displayed, you should change your air filter and reset the reminder by holding down the “Clean” key on the left side of the thermostat for 3 seconds.

Specifications

  • The display range of temperature … 41˚F to 95˚F (5˚C to 35˚C)
  • The control range of temperature…. 44˚F to 90˚F (7˚C to 32˚C)
  • Load Rating……………………………………….. 1 amp per terminal, 1.5 amp
  • maximum all terminals combined
  • Swing (cycle rate or differential) …… Heating is adjustable from 0.2˚ to 2.0˚
  • Cooling is adjustable from 0.2˚ to 2.0˚
  • Power source …………………………………….18 to 30 VAC, NEC Class II, 50/60 Hz for hardwire
  • Battery power from 2 AA Alkaline
  • batteries
  • Operating ambient …………………………. 32˚F to +105˚F (0˚C to +41˚C)
  • Operating humidity ………………………… 90% non-condensing maximum
  • Dimensions of thermostat …………….. 4.7” W x 4.3” H x 1.1” D
  • Frequency ………………………………………… 916 MHz
  • Base module
  • Load rating ……………………………………….. 1 amp per terminal, 1.5 amp
  • maximum all terminals combined
  • Power source ……………………………………. 18 to 30 VAC, NEC class II, 50/60 Hz
  • Operating ambient …………………………. 32°F to +150°F (0° to +65°C)
  • Operating humidity ………………………… 90% non-condensing maximum

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals