MITSUBISHI ELECTRIC PUZ-HA42NKA1 42000 BTU H Multi-Position Air Handler Instruction Manual

June 3, 2024
Mitsubishi Electric

PVA-A42AA7 & PUZ-HA42NKA1
42,000 BTU/H MULTI-POSITION AIR HANDLER
42,000 BTU/H HYPER-HEATING UNIVERSAL OUTDOOR
Instruction Manual
MITSUBISHI ELECTRIC PUZ-HA42NKA1 42000 BTU H Multi-Position Air
Handler Indoor Unit: PVA- A42AA7
Outdoor Unit: PUZ-HA42NKA1
Job Name:……….
System Reference:……..

INDOOR UNIT FEATURES

  • Ducted air handler provides a solution to cool and heat large zones
  • Highly efficient totally enclosed ECM motor
  • Selectable external static pressure: 0.30, 0.50 and 0.80 in.WG with 3 fan speeds at each static setting
  • 1 inch R4.2 fiberglass free insulation reduces condensation and boosts efficiency
  • Positive pressure cabinet with air leakage of less than 1.0% at 1.0 in.WG
  • Unique blow through design allows simple coil cleaning when the blower is removed
  • Multi-position installation: horizontal (left or right), vertical (up or down). For downflow configurations, the CMA-1 is recommended for proper management of condensate to prevent water blow-off in certain conditions
  • Optional electric heat kit for additional heat capacity
  • Optional humidifier control and ERV control
  • Multiple control options available:
  • kumo cloud® smart device app for remote access
  • Third-party interface options
  • Wired or wireless controllers

OUTDOOR UNIT FEATURES

  • Variable speed INVERTER-driven compressor
  • Wide heating range: heating performance down to -13°F (average of 80% heating capacity)
  • High speed heating at start up: Hyper-Heating INVERTER® reduces the time for heating at start up by about half compared to standard models
  • Power receiver pre-charged with refrigerant volume for piping length up to 100 ft.
  • High pressure/temperature protection
  • Built-in base pan heater
  • Flash injection circuit provides efficient high heating capacities at low ambient temperatures

SPECIFICATIONS:

PVA-A42AA7 & PUZ-HA42NKA1

Cooling at 95°F1 Maximum Capacity BTU/H 42,000
Rated Capacity BTU/H 42,000
Minimum Capacity BTU/H 17,000
Maximum Power Input W 3,960
Rated Power Input W 3,960
Moisture Removal Pints/h 5.3
Sensible Heat Factor 0.86
Power Factor % 92.0/92.0
Heating at 47°F2 Maximum Capacity BTU/H 54,000
Rated Capacity BTU/H 48,000
Minimum Capacity BTU/H 23,900
Maximum Power Input W 4,570
Rated Power Input W 3,850
Power Factor % 92.0/92.0
Heating at 17°F3 Maximum Capacity BTU/H 48,000
Rated Capacity BTU/H 38,500
Maximum Power Input W 6,635
Rated Power Input W 4,925

Heating at 5°F4

| Maximum Capacity| BTU/H| 48,000
Maximum Power Input| W| 6,865
Heating at -13°F7| Maximum Capacity| BTU/H| 38,400
Efficiency| SEER| 15.4
EER1| 10.6
HSPF [IV]| 10.0
COP at 47°F2| 3.7
COP at 17°F at Maximum Capacity3| 2.1
COP at 5°F at Maximum Capacity4| 1.9
COP at -13°F at Maximum Capacity7| 1.6
ENERGY STAR® Certified| No
Electrical| Voltage, Phase, Frequency| 208/230, 1, 60
Guaranteed Voltage Range| V AC| 198 – 253
Voltage: Indoor – Outdoor, S1-S2| V AC| 208/230
Voltage: Indoor – Outdoor, S2-S3| V DC| 24
Short-circuit Current Rating [SCCR]| kA| 5
Recommended Fuse/Breaker Size (Oudoor)| A| 40
Recommended Wire Size [Indoor – Outdoor]| AWG| 14
Power Supply| Indoor unit is powered by the outdoor unit
Indoor Unit| MCA| A| 5.63
Fan Motor Full Load Amperage| A| 4.50
Fan Motor Output| W| 430
Fan Motor Type| DC Motor
Airflow Rate at Cooling, Dry| CFM| 1040–1262–1485
Airflow Rate at Heating, Dry| CFM| 1040–1262–1485
Sound Pressure Level [Cooling]| dB[A]| 36–40–44
Sound Pressure Level [Heating]| dB[A]| 36–40–44
External Static Pressure| in.WG| 0.30–0.5–0.8
Drain Pipe Size| In. [mm]| 3/4 FPT [19.05]
Coating on Heat Exchanger| —
External Finish Color| Galvanized steel cabinet-Powder coated Slate Gray
Unit Dimensions| W x D x H: In. [mm]| 25 x 21-5/8 x 59-1/2 [635 x 548 x 1511]
Package Dimensions| W x D x H: In. [mm]| 13-7/16 x 34-11/16 x 65 [340 x 880 x 1,650]
Unit Weight| Lbs. [kg]| 172 [78]
Indoor Unit Operating Temperature Range| Cooling Intake Air Temp [Maximum / Minimum]*| °F| 90 DB, 72 WB / 66 DB, 61 WB
Heating Intake Air Temp [Maximum / Minimum]| °F| 77 DB / 59 DB

NOTES:

AHRI Rated Conditions
(Rated data is determined at a fixed compressor speed)| 1 Cooling (Indoor // Outdoor)
2 Heating at 47°F (Indoor // Outdoor)
3 Heating at 17°F (Indoor // Outdoor)| °F
°F
°F| 80 DB, 67 WB // 95 DB, 75 WB
70 DB, 60 WB // 47 DB, 43 WB
70 DB, 60 WB // 17 DB, 15 WB
---|---|---|---
Conditions| 4 Heating at 5°F (Indoor // Outdoor)
5 Heating at -4°F (Indoor // Outdoor)
6 Heating at -5°F (Indoor // Outdoor)
7 Heating at -13°F (Indoor // Outdoor)| °F
°F
°F
°F| 70 DB, 60 WB // 5 DB, 4 WB
70 DB, 60 WB // -4 DB, -5 WB
70 DB, 60 WB // -5 DB, -6 WB
70 DB, 60 WB // -13 DB, -14 WB

*Outdoor Unit Operating Temperature Range (Cooling Air Temp (Maximum / Minimum)):

  • Wind baffles required to operate below 23°F DB in cooling mode.
  • Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re- start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):

  • System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

SPECIFICATIONS: PVA-A42AA7 & PUZ-HA42NKA1

Outdoor Unit MCA A 36.0
MOCP A 44
Fan Motor Output W 74
Airflow Rate CFM 3319/3319
Refrigerant Control LEV
Defrost Method Reverse Cycle
Sound Pressure Level, Cooling1 dB(A) 49
Sound Pressure Level, Heating2 dB(A) 51
Compressor Type Scroll
Compressor Model ANB42FJTMT
Compressor Rated Load Amps A 19
Compressor Locked Rotor Amps A 28.0
Compressor Oil Type // Charge oz. FVC68D // 1.7,57
External Finish Color Ivory Munsell 3Y 7.8/1.1
Base Pan Heater Built-in
Unit Dimensions W x D x H: In. [mm] 41-5/16 x 14-3/16 x 52-11/16 [1050 x 360

x 1338]
Package Dimensions| W x D x H: In. [mm]| 43 x 18 x 57 [1110 x 480 x 1440]
Unit Weight| Lbs. [kg]| 283 [128]
Package Weight| Lbs. [kg]| 307 [139]
Outdoor Unit Operating Temperature Range| Cooling Air Temp [Maximum / Minimum]*| °F| 115 DB / 0 DB
Heating Air Temp [Maximum / Minimum]| °F| 70 DB, 59 WB / -13 DB, -13 WB
Heating Thermal Lock-out / Re-start Temperatures**| °F| -22 / -13
Refrigerant| Type| R410A
Charge| Lbs, oz| 13, 4.0
Chargeless Piping Length| Ft. [m]| 0.0 [30.0]
Additional Refrigerant Charge Per Additional Piping Length| oz./Ft. [g/m]| 0.6 [56]
Piping| Gas Pipe Size O.D. [Flared]| In.[mm]| 5/8 [15.88]
Liquid Pipe Size O.D. [Flared]| In.[mm]| 3/8 [9.52]
Maximum Piping Length| Ft. [m]| 245 [75]
Maximum Height Difference| Ft. [m]| 100 [30]
Maximum Number of Bends| 15

NOTES:

AHRI Rated Conditions
(Rated data is determined at a fixed compressor speed)| 1 Cooling (Indoor // Outdoor)
2 Heating at 47°F (Indoor // Outdoor)
3 Heating at 17°F (Indoor // Outdoor)| °F
°F
°F| 80 DB, 67 WB // 95 DB, 75 WB
70 DB, 60 WB // 47 DB, 43 WB
70 DB, 60 WB // 17 DB, 15 WB
---|---|---|---
Conditions| 4 Heating at 5°F (Indoor // Outdoor)
5 Heating at -4°F (Indoor // Outdoor)
6 Heating at -5°F (Indoor // Outdoor)
7 Heating at -13°F (Indoor // Outdoor)| °F
°F
°F
°F| 70 DB, 60 WB // 5 DB, 4 WB
70 DB, 60 WB // -4 DB, -5 WB
70 DB, 60 WB // -5 DB, -6 WB
70 DB, 60 WB // -13 DB, -14 WB

*Outdoor Unit Operating Temperature Range (Cooling Air Temp (Maximum / Minimum)):

  • Wind baffles required to operate below 23°F DB in cooling mode.
  • Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re- start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):

  • System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

INDOOR UNIT ACCESSORIES:

PVA-A42AA7

control Interface 3-Pin Connector □ PAC-715AD
BACnet® and Modbus® Interface □ PAC-UKPRC001-CN-1
CN24 Relay Kit □ CN24RELAY-KIT-CM3
Connector cable for remote display □ PAC-SA88HA-EP
IT Extender □ PAC-WHS01IE-E
kumo station® for kumo cloud® □ PAC-WHS01HC-E
Lockdown bracket for remote controller □ RCMKP1CB
Remote Operation Adapter‡ □ PAC-SF40RM-E
Thermostat Interface □ PAC-US444CN-1
USNAP Adapter □ PAC-WHS01UP-E
Remote Sensor Flush Mount Temperature Sensor □ PAC-USSEN001-FM-1
Remote Temperature Sensor □ PAC-SE41TS-E
Wireless temperature and humitity sensor for kumo cloud® □ PAC-USWHS003-TH-1
Wired Remote Controller Airzone ZBS Wired Blueface Principal Controller
White □ AZZBSBLUEFACECB
Airzone ZBS Wired Lite Controller White □ AZZBSLITECB
Airzone ZBS Wired Think Controller White □ AZZBSTHINKCB
Airzone ZBS Wireless Lite Controller White □ AZZBSLITERB
Airzone ZBS Wireless Think Controller White □ AZZBSTHINKRB
Deluxe Wired MA Remote Controller† □ PAR-40MAAU
Simple MA Remote Controller† □ PAC-YT53CRAU-J
Touch MA Controller† □ PAR-CT01MAU-SB
Wireless Remote Controller kumo touch™ RedLINK™ Wireless Controller □ MHK2
Wireless MA Controller □ PAR-FA32MA-W
Wireless MA Remote Controller □ PAR-FL32MA-E
Wireless Remote Contoller □ PAR-SL100A-E
Condensate Blue Diamond Sensor Extension Cable — 15 Ft. □ C13-103
Control Wire 20/2PR, 1PR shielded + 1PR plenum wire for Airzone, 100 ft reel

□ CW2042S2-100
20/2PR, shielded + 1PR plenum wire for Airzone, 500 ft reel| □ CW2042S2-500
Disconnect Switch| (30A/600V/UL) [fits 2” X 4” utility box] – Black| □ TAZ- MS303
(30A/600V/UL) [fits 2” X 4” utility box] – White| □ TAZ-MS303W
Downflow Kit| Condensate Management Kit for downflow installation| □ CMA-1
Electric Heat Lockout| Electric Heat Lockout| □ ETC-211000-MIT
Electric Kit Heats| 10kW Electric Heater| □ EH10-MPA-LB
15kW Electric Heater| □ EH15-MPAS-LB
17kW Electric Heater| □ EH17-MPAS-LB
Lineset| 10’ x 3/8” x 10’ x 5/8” Lineset (Twin-Tube Insulation)††| □ MPLS385812T-10
100’ x 3/8” x 100’ x 5/8” Lineset (Twin-Tube Insulation)††| □ MPLS385812T-100
15’ x 3/8” x 15’ x 5/8” Lineset (Twin-Tube Insulation)††| □ MPLS385812T-15
30’ x 3/8” x 30’ x 5/8” Lineset (Twin-Tube Insulation)††| □ MPLS385812T-30
50’ x 3/8” x 50’ x 5/8” Lineset (Twin-Tube Insulation)††| □ MPLS385812T-50
65’ x 3/8” x 65’ x 5/8” Lineset (Twin-Tube Insulation)††| □ MPLS385812T-65
Terminal Block| Separate Terminal Power Block| □ SPTB1

NOTES:
‡ PAC-SF40RM-E (Unable to use with wireless remote controller)

OUTDOOR UNIT ACCESSORIES:

PUZ-HA42NKA1

Air Outlet Guide| Air Outlet Guide (1 Piece)| □ PAC-SH96SG-E (two pieces are required)
---|---|---
Centralized Drain Pan| Central Drain Pan| □ PAC-SH97DP-E
Control/Service Tool| Control/Service Tool| □ PAC-SK52ST
Drain Socket| Drain Socket| □ PAC-SG61DS-E
Hail Guards| Hail Guard| □ HG-A2
M-NET Converter| M-NET Converter| □ PAC-SJ85MA-E
M-NET Converter| □ PAC-SJ95MA-E
Mounting Pad| Condensing Unit Mounting Pad: 24” x 42” x 3”| □ ULTRILITE2
Optional Defrost Heater| Optional Defrost Heater| □ PAC-SJ20BH-E
Stand| 18” Dual Fan Stand| □ QSMS1802M
24” Dual Fan Stand| □ QSMS2402M
Condenser Wall Bracket| □ QSWB2000M-1
Condenser Wall Bracket -Stainless Steel Finish| □ QSWBSS
Outdoor Unit Stand — 12” High| □ QSMS1202M
Wind Baffle| Front Wind Baffle| □ WB-PA3 (two pieces are required)

INDOOR UNIT DIMENSIONS:

PVA-A42AA7

MITSUBISHI ELECTRIC PUZ-HA42NKA1 42000 BTU H Multi-Position Air Handler -
fig1

UTDOOR UNIT DIMENSIONS:

PUZ-HA42NKA1
Unit: mm

MITSUBISHI ELECTRIC PUZ-HA42NKA1 42000 BTU H Multi-Position Air Handler -
fig2

FORM# PVA-A42AA7 & PUZ-HA42NKA1 – 202108
1340 Satellite Boulevard Suwanee, GA 30024
Toll Free:800-433-4822 www.mehvac.com

Specifications are subject to change without notice.
© 2021 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

Documents / Resources

| MITSUBISHI ELECTRIC PUZ-HA42NKA1 42000 BTU H Multi-Position Air Handler [pdf] Instruction Manual
PVA-A42AA7PUZ-HA42NKA1, 42000 BTU H Multi-Position Air Handler, PUZ-HA42NKA1 42000 BTU H Multi-Position Air Handler, Multi-Position Air Handler, Air Handler, Handler
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Mitsubishi Electric User Manuals

Related Manuals