MITSUBISHI ELECTRIC PUZ-WM Air to Water Heat Pump User Manual
- May 15, 2024
- Mitsubishi Electric
Table of Contents
- PUZ-WM Air to Water Heat Pump
- Safety precautions
- Installation location
- Installing the outdoor unit
- COMP fixed parts removing work (Only PUZ-WM112*AA)
- Drainage piping work
- Water piping work
- Electrical work
- System control
- Specifications
- Serial number
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Air to Water Heat Pump
PUZ-WM • AA series, PUZ-WM • HA series
INSTALLATION MANUAL
PUZ-WM Air to Water Heat Pump
FOR INSTALLER
For safe and correct use, read this manual and the indoor unit installation
manual thoroughly before installing the outdoor unit. English is original.
The other languages versions are translation of the original.
Note: This symbol mark is for EU countries only.
This symbol mark is according to the directive 2012/19/EU Article 14
Information for users and Annex IX.
Your MITSUBISHI ELECTRIC product is designed and manufactured with high
quality materials and components which can be recycled and reused.
This symbol means that electrical and electronic equipment, at their end-of-
life, should be disposed of separately from your household waste.
Please, dispose of this equipment at your local community waste
collection/recycling centre.
In the European Union there are separate collection systems for used
electrical and electronic product.
Please, help us to conserve the environment we live in!
CAUTION:
- Do not vent R32 into the Atmosphere:
Safety precautions
►Before installing the unit, make sure you read all the “Safety precautions”.
►Please report to or take consent by the supply authority before connection to
the system.
►Equipment complying with IEC/EN 61000-3-12 (PUZ-WM60/85/112VAA)
WARNING:
Describes precautions that must be observed to prevent danger of injury or
death to the user.
CAUTION:
Describes precautions that must be observed to prevent damage to the unit.
After installation work has been completed, explain the “Safety Precautions,”
use, and maintenance of the unit to the customer according to the information
in the Operation Manual and perform the test run to ensure normal operation.
Both the Installation Manual and Operation Manual must be given to the user
for keeping. These manuals must be passed on to subsequent users.
: Indicates a part which must be grounded.
WARNING:
Carefully read the labels affixed to the main unit.
MEANINGS OF SYMBOLS DISPLAYED ON THE UNIT
| WARNING
(Risk of fire)| This mark is for R32 refrigerant only. Refrigerant type is
written on nameplate of outdoor unit. In case that refrigerant type is R32,
this unit uses a flammable refrigerant. If refrigerant leaks and comes in
contact with fire or heating part, it will create harmful gas and there is
risk of fire.
---|---|---
| Read the OPERATION MANUAL carefully before operation.
| Service personnel are required to carefully read the OPERATION MANUAL and
INSTALLATION MANUAL before operation.
| Further information is available in the OPERATION MANUAL, INSTALLATION
MANUAL, and the like.
WARNING:
-
The unit must not be installed by the user. Ask a dealer or an authorized technician to install the unit. If the unit is installed incorrectly, water leakage, electric shock, or fire may result.
-
For installation work, follow the instructions in the Installation Manual and use tools and pipe components specifically made for use with R32 refrigerant.
The R32 refrigerant in the HFC system is pressurized 1.6 times the pressure of usual refrigerants. If pipe components not designed for R32 refrigerant are used and the unit is not installed correctly, the pipes may burst and cause damage or injuries. In addition, water leakage, electric shock, or fire may result. -
When installing the unit, use appropriate protective equipment and tools for safety.
Failure to do so could cause injuries. -
The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons, or strong winds. An incorrectly installed unit may fall down and cause damage or injuries.
-
The unit must be securely installed on a structure that can sustain its weight. If the unit is mounted on an unstable structure, it may fall down and cause damage or injuries.
-
If the outdoor unit is installed in a small room, measures must be taken to prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. Consult a dealer regarding the appropriate measures to prevent the allowable concentration from being exceeded. Should the refrigerant leak and cause the concentration limit to be exceeded, hazards due to lack of oxygen in the room may result.
-
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
-
All electric work must be performed by a qualified technician according to local regulations and the instructions given in this manual. The units must be powered by dedicated power lines and the correct voltage and circuit breakers must be used. Power lines with insufficient capacity or incorrect electrical work may result in electric shock or fire.
-
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
-
Use only specified cables for wiring. The wiring connections must be made securely with no tension applied on the terminal connections. Also, never splice the cables for wiring (unless otherwise indicated in this document). Failure to observe these instructions may result in overheating or a fire.
-
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid hazard.
-
The appliance shall be installed in accordance with national wiring regulations.
-
The terminal block cover panel of the outdoor unit must be firmly attached. If the cover panel is mounted incorrectly and dust and moisture enter the unit, electric shock or fire may result.
-
When installing or relocating, or servicing the outdoor unit, use only the specified refrigerant (R32) to charge the refrigerant lines. Do not mix it with any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high pressure in the refrigerant line, and may result in an explosion and other hazards.
The use of any refrigerant other than that speci- fied for the system will cause mechanical failure or system malfunction or unit breakdown. In the worst case, this could lead to a serious impediment to securing product safety. -
Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them. If accessories are incorrectly installed, water leakage, electric shock, or fire may result.
-
Do not alter the unit. Consult a dealer for repairs. If alterations or repairs are not performed correctly, water leakage, electric shock, or fire may result.
-
The user should never attempt to repair the unit or transfer it to another location. If the unit is installed incorrectly, water leakage, electric shock, or fire may result. If the outdoor unit must be repaired or moved, ask a dealer or an authorized technician.
-
After installation has been completed, check for refrigerant leaks. If refrigerant leaks into the room and comes into contact with the flame of a heater or portable cooking range, poisonous gases will be released.
-
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
-
The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater).
-
Do not pierce or burn.
-
Be aware that refrigerants may not contain an odour.
-
Compliance with national gas regulations shall be observed.
-
Keep any required ventilation openings clear of ob- struction.
-
Do not use low temperature solder alloy in case of brazing the refrigerant pipes.
-
When performing brazing work, be sure to ventilate the room sufficiently.
Make sure that there are no hazardous or flammable materials nearby.
When performing the work in a closed room, small room, or similar location, make sure that there are no refrigerant leaks before performing the work. If refrigerant leaks and accumulates, it may ignite or poisonous gases may be released. -
The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
-
Keep gas-burning appliances, electric heaters, and other fire sources (ignition sources) away from the location where installation, repair, and other out- door unit work will be performed. If refrigerant comes into contact with a flame, poisonous gases will be released.
-
Do not smoke during work and transportation.
-
1.1. Before installation
CAUTION:
- Do not use the unit in an unusual environment. If the outdoor unit is installed in areas exposed to steam, volatile oil (including machine oil), or sulfuric gas, areas exposed to high salt content such as the seaside, or areas where the unit will be covered by snow, the performance can be significantly reduced and the internal parts can be damaged.
- Do not install the unit where combustible gases may leak, be produced, flow, or accumulate. If combustible gas accumulates around the unit, fire or explosion may result.
- The outdoor unit produces condensation during the heating operation. Make sure to provide drainage around the outdoor unit if such condensation is likely to cause damage.
- Remove the compressor’s fixing component in accordance with the NOTICE attached to the unit. Running the unit with the fixing component mounted will result in increased noise.
- When installing the unit in a hospital or communications office, be prepared for noise and electronic interference. Inverters, home appliances, highfrequency medical equipment, and radio communications equipment can cause the outdoor unit to malfunction or breakdown. The outdoor unit may also affect medical equipment, disturbing medical care, and communications equipment, harming the screen display quality.
- When the unit is running, vibrations or the noise of refrigerant running may be heard from the extension piping. Try to avoid installing the piping to thin walls, etc. as much as possible and provide sound insulation with the piping cover, etc.
1.2. Before installation (relocation)
CAUTION:
- Be extremely careful when transporting or installing the units. Two or more persons are needed to handle the unit, as it weighs 20 kg or more. Do not grasp the packaging bands. Wear protective gloves to remove the unit from the packaging and to move it, as you can injure your hands on the fins or the edge of other parts.
- Be sure to safely dispose of the packaging materials. Packaging materials, such as nails and other metal or wooden parts may cause stabs or other injuries.
- The base and attachments of the outdoor unit must be periodically checked for looseness, cracks or other damage. If such defects are left uncorrected, the unit may fall down and cause damage or injuries.
- Do not clean the outdoor unit with water. Electric shock may result.
1.3. Before electric work
CAUTION:
- Be sure to install circuit breakers. If not installed, electric shock may result.
- For the power lines, use standard cables of sufficient capacity. Otherwise, a short circuit, overheating, or fire may result.
- When installing the power lines, do not apply tension to the cables. If the connections are loosened, the cables can snap or break and overheating or fire may result.
- Be sure to ground the unit. Do not connect the ground wire to gas or water pipes, lightning rods, or telephone grounding lines. If the unit is not properly grounded, electric shock may result.
- Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and molded case circuit breaker) with the specified capacity. If the circuit breaker capacity is larger than the specified capacity, breakdown or fire may result.
1.4. Before starting the test run
CAUTION:
- Turn on the main power switch more than 12 hours before starting operation. Starting operation just after turning on the power switch can severely dam- age the internal parts. Keep the main power switch turned on during the operation season.
- Before starting operation, check that all panels, guards and other protective parts are correctly installed. Rotating, hot, or high voltage parts can cause injuries.
- Do not touch any switch with wet hands. Electric shock may result.
- Do not touch the refrigerant pipes with bare hands during operation. The refrigerant pipes are hot or cold depending on the condition of the flowing re- frigerant. If you touch the pipes, burns or frostbite may result.
- After stopping operation, be sure to wait at least five minutes before turning off the main power switch.Otherwise, water leakage or breakdown may result.
1.5. Using R32 refrigerant outdoor units
CAUTION:
- Do not use refrigerant other than R32 refrigerant. If another refrigerant is used, the chlorine will cause the oil to deteriorate.
- Use the following tools specifically designed for use with R32 refrigerant. The following tools are necessary to use R32 refrigerant. Contact your nearest dealer for any questions.
Tools (for R32)
Gauge manifold| Flare tool
Charge hose| Size adjustment gauge
Gas leak detector| Vacuum pump adapter
Torque wrench| Electronic refrigerant charging scale
- Be sure to use the correct tools. If dust, debris, or moisture enters the refrigerant lines, refrigeration oil deterioration may result.
Installation location
2.1. Choosing the outdoor unit installation location
-
R32 is heavier than air—as well as other refrigerants—so tends to accumulate at the base (in the vicinity of the floor). If R32 accumulates around base, it may reach a flammable concentration in case room is small. To avoid ignition, maintaining a safe work environment is required by ensuring appropriate ventilation. If a refrigerant leak is confirmed in a room or an area where there is insufficient ventilation, refrain from using of flames until the work environment can be improved by ensuring appropriate ventilation.
• Avoid locations exposed to direct sunlight or other sources of heat.
• Select a location from which noise emitted by the unit will not inconvenience neighbors.
• Select a location permitting easy wiring and pipe access to the power source and indoor unit.
• Avoid locations where combustible gases may leak, be produced, flow, or accumulate.
• Note that water may drain from the unit during operation.
• Select a level location that can bear the weight and vibration of the unit.
• Avoid locations where the unit can be covered by snow. In areas where heavy snow fall is anticipated, special precautions such as raising the installation location or installing a hood on the air intake must be taken to prevent the snow from blocking the air
intake or blowing directly against it. This can reduce the airflow and a malfunction may result.
• Avoid locations exposed to oil, steam, or sulfuric gas.
• Use the transportation handles of the outdoor unit to transport the unit. If the unit is carried from the bottom, hands or fingers may be pinched. -
Install outdoor units in a place where at least one of the four sides is open, and in a sufficiently large space without depressions. (Fig. 2-1)
CAUTION:
-
Perform grounding.
Do not connect the ground wire to a gas pipe, water pipe arrester or telephone ground wire. Defective grounding could cause an electric shock. -
Do not install the unit in a place where an inflammable gas leaks. If gas leaks and accumulates in the area surrounding the unit, it could cause an explosion.
-
Install a ground leakage breaker depending on the installation place (where it is humid). If a ground leakage breaker is not installed, it could cause an electric shock.
-
Perform the drainage/piping work securely according to the installation manual.
If there is a defect in the drainage/piping work, water could drop from the unit and household goods could be wet and damaged. -
Fasten a flare nut with a torque wrench as specified in this manual.
When fastened too tight, a flare nut may be broken after a long period and cause a leakage of refrigerant.
2.2. Outline dimensions (Outdoor unit) (Fig. 2-2) 2.3. Ventilation and service space
2.3.1. Windy location installation
When installing the outdoor unit on a rooftop or other location unprotected
from the wind, situate the air outlet of the unit so that it is not directly
exposed to strong winds. Strong wind entering the air outlet may impede the
normal airflow and a malfunction may result.
The following shows three examples of precautions against strong winds.
-
Face the air outlet towards the nearest available wall about 35 cm away from the wall. (Fig. 2-3)
-
Install an optional air guide if the unit is installed in a location where strong winds from a typhoon, etc. may directly enter the air outlet. (Fig. 2-4)
A Air outlet guide -
Position the unit so that the air outlet blows perpendicularly to the seasonal wind direction, if possible. (Fig. 2-5)
B Wind direction
2.3.2. When installing a single outdoor unit (Refer to the last page)
Minimum dimensions are as follows, except for Max., meaning Maximum
dimensions, indicated.
Refer to the figures for each case.
-
Obstacles at rear only (Fig. 2-6)
-
Obstacles at rear and above only (Fig. 2-7)
• Do not install the optional air outlet guides for upward airflow. -
Obstacles at rear and sides only (Fig. 2-8)
-
Obstacles at front only (Fig. 2-9)
-
Obstacles at front and rear only (Fig. 2-10)
-
Obstacles at rear, sides, and above only (Fig. 2-11)
• Do not install the optional air outlet guides for upward airflow.
2.3.3. When installing multiple outdoor units (Refer to the last page)
Leave 50 mm space or more between the units.
Refer to the figures for each case.
-
Obstacles at rear only (Fig. 2-12)
-
Obstacles at rear and above only (Fig. 2-13)
• No more than 3 units must be installed side by side. In addition, leave space as shown.
• Do not install the optional air outlet guides for upward airflow. -
Obstacles at front only (Fig. 2-14)
-
Obstacles at front and rear only (Fig. 2-15)
-
Single parallel unit arrangement (Fig. 2-16)
- When using an optional air outlet guide installed for upward airflow, the clearance is 500 mm or more. 6. Multiple parallel unit arrangement (Fig. 2-17)
- When using an optional air outlet guide installed for upward airflow, the clearance is 1000 mm or more.
7. Stacked unit arrangement (Fig. 2-18)
• The units can be stacked up to two units high.
• No more than 2 stacked units must be installed side by side. In addition, leave space as shown.
2.4. Minimum installation area
If you unavoidably install a unit in a space where all four sides are blocked
or there are depressions, confirm that one of these situations (A, B or C) is
satisfied.
Note: These countermeasures are for keeping safety not for specification
guarantee.
A) Secure sufficient installation space (minimum installation area Amin).
Install in a space with an installation area of Amin or more, corresponding to
refrigerant quantity M (factory-charged refrigerant + locally added
refrigerant).
M [kg] | Amin [m²] |
---|---|
1.0 | 12 |
1.5 | 17 |
2.0 | 23 |
2.5 | 28 |
3.0 | 34 |
3.5 | 39 |
4.0 | 45 |
4.5 | 50 |
5.0 | 56 |
5.5 | 62 |
6.0 | 67 |
6.5 | 73 |
7.0 | 78 |
7.5 | 84 |
B) Install in a space with a depression height of 0.125 [m].
C) Create an appropriate ventilation
open area.
Make sure that the width of the open area is 0.9 [m] or more and the height of
the open area is 0.15 [m] or more.
However, the height from the bottom of the installation space to the bottom
edge of the open area should be 0.125 [m] or less.
Open area should be 75% or more opening.
Installing the outdoor unit
- Be sure to install the unit in a sturdy, level surface to prevent rattling noises during operation. (Fig. 3-1)
Foundation bolt| M10 (3/8″) ---|--- Thickness of concrete| 120 mm Length of bolt| 70 mm Weight-bearing capacity| 320 kg - Make sure that the length of the foundation bolt is within 30 mm of the bottom surface of the base.
- Secure the base of the unit firmly with four-M10 foundation bolts in sturdy loca- tions.
Installing the outdoor unit
- Do not block the vent. If the vent is blocked, operation will be hindered and breakdown may result.
- In addition to the unit base, use the installation holes on the back of the unit to attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 × 15 mm or less) and install on site.
WARNING:
- The unit must be securely installed on a structure that can sustain its weight. If the unit is mounted on an unstable structure, it may fall down and cause damage or injuries.
- The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons, or strong winds. An incorrectly installed unit may fall down and cause damage or injuries.
CAUTION:
- Install be unit on a rigid structure to prevent excessive operation sound or vibration.
COMP fixed parts removing work (Only PUZ-WM112*AA)
-
Before starting the unit operation, be sure to uncover the COMP CASE TOP and COMP CASE FRONT, and remove the COMP fixed parts. (Fig. 4-1)
-
After removing the COMP fixed parts, be sure to tighten nuts, and make COMP CASE TOP and COMP CASE FRONT back to the original state. (Fig. 4-2)
Note:
- This work is applicable to the following models.
PUZ-WM112VAA| PUZ-WM112YAA
---|---
PUZ-WM112VAA-BS| PUZ-WM112YAA-BS
CAUTION:
- If the COMP fixed parts are not removed, the operation noise may increase.
WARNING:
- Before the COMP fixed parts are removed, be sure to be breaker off. If not, the COMP case touches electrical parts and they may break down.
Drainage piping work
Outdoor unit drainage pipe connection
When drain piping is necessary, use the drain socket or the drain pan
(option).
| WM50| WM60| WM85| WM112
---|---|---|---|---
Drain socket| PAC-SG61DS-E
Drain pan| PAC-SG64DP-E| 1 PAC-SJ83DP-E
Water piping work
6.1. Water piping connection (Fig. 6-1)
- Connect the water pipes to the outlet and inlet pipes. (Parallel male screw for 1-inch water pipe (ISO 228/1-G1B))
- Inlet and outlet pipes position is shown on the Fig. 6-1.
- Install the hydraulic filter at the water intake.
- Maximum allowable torque at the water piping connection is 50 N•m.
- Check if water leaks after installation.
- Inlet water gauge pressure must be between 0-0.3 MPa.
- Use the inlet water with a temperature lower than 55 ˚C.
Note:
-
The water velocity in pipes should be kept within certain limits of ma – terial to avoid erosion, corrosion and excessive noise generation.
Be aware, and take care of, that local velocities in small pipes, bends and similar obstructions can exceed the values above. e.g.) Copper : 1.5 m/s -
When connecting metal pipes made of different materials, be sure to insu – late the joint to prevent electrolytic etching.
-
Set up a field system so that the inlet water temperature and water flow rate can be within the allowable range specified in our technical data, etc.
If the unit is used out of the allowable range, the parts of unit might be dam- aged.
6.2. Water quality condition
- The water in a system should be clean and with a pH value of 6.5-8.0.
- The followings are the maximum values;
Calcium : 100 mg/L
Chlorine : 100 mg/L
Iron/manganese : 0.5 mg/L
[Fig. 6-1] A Water outlet
B Water inlet
6.3. Minimum water quantity
Refer to the indoor unit installation manual. Note: Make sure to perform
the frozen prevention measure for water pipe system. (Water piping insulation,
back-up pump system, using of a certain % ethylene glycol instead of normal
water) Insulate the water piping properly. The performance can be poor if the
insulation is insufficient.
WARNING:
As the outlet water temperature can reach 60 ºC at maximum, do not touch the
water piping directly with a bare hand.
Note:
Parts which require regular inspection
Parts | Check every | Possible failures |
---|
Pressure relief valve (3bar)
Temperature and pressure relief valve| 1 year
(turning the knob manually)| PRV would be fixed and expansion vessel would
burst
6.4. Available range (Water flow rate, return water temp.) Note:
Be sure to avoid the unavailable range during defrosting.
Otherwise, the outdoor unit is insufficiently defrosted and/or the heat
exchanger of the indoor unit may freeze.
Electrical work
7.1. Outdoor unit (Fig. 7-1, Fig. 7-2)
- Remove the service panel.
- Wire the cables referring to the Fig. 7-1 and the Fig. 7-2.
F. Terminal block
G. Indoor/Outdoor connection terminal block (S1, S2, S3)
H. Service panel
J. Earth terminal
K. Wire the cables so that they do not contact the center of the service
panel.
Note:
If the protective sheet for the electrical box is removed during servicing, be
sure to reinstall it.
CAUTION:
Be sure to install N-Line. Without N-Line, it could cause damage to unit.
7.2. Field electrical wiring
Outdoor unit model | WM5OV | WM6OV | WM85V | WM112V | WM85, 112Y |
---|---|---|---|---|---|
Outdoor unit power supply | ∼/N (single), | ||||
50 Hz, 230 V | ∼/N (single), | ||||
50 Hz, 230 V | ∼/N (single), | ||||
50 Hz, 230 V | ∼/N (single), | ||||
50 Hz, 230 V | 3N∼ (3 ph 4-wires), |
50 Hz, 400 V
Outdoor unit input capacity Main switch (Breaker) 1| 16 A| 16 A| 25 A| 32 A|
16 A
Wiring WireNo. x size(mm2)| Outdoor unit power supply| 3 x Min. 1.5| 3 x Min.
2.5| 3 x Min. 2.5| 3 x Min. 4| 5 x Min. 1.5
Indoor unit-Outdoor unit 2| 3 x 1.5 (Polar)| 3 x 1.5 (Polar)| 3 x 1.5
(Polar)| 3 x 1.5 (Polar)| 3 x 1.5 (Polar)
Indoor unit-Outdoor unit earth 2| 1 x Min. 1.5| 1 x Min. 1.5| 1 x Min. 1.5| 1
x Min. 1.5| 1 x Min. 1.5
Remote controller-Indoor unit 3| 2 x 0.3 (Non-polar)| 2 x 0.3 (Non-polar)| 2
x 0.3 (Non-polar)| 2 x 0.3 (Non-polar)| 2 x 0.3 (Non-polar)
Circuit rating| Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase) 4| 230 VAC| 230 VAC| 230 VAC| 230
VAC| 230 VAC
Indoor unit-Outdoor unit S1-S2 4| 230 VAC| 230 VAC| 230 VAC| 230 VAC| 230 VAC
Indoor unit-Outdoor unit S2-S3 4| 24 VDC| 24 VDC| 24 VDC| 24 VDC| 24 VDC
Remote controller-Indoor unit 4| 12 VDC| 12 VDC| 12 VDC| 12 VDC| 12 VDC
1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
Make sure that the current leakage breaker is one compatible with higher
harmonics.
Always use a current leakage breaker that is compatible with higher harmonics
as this unit is equipped with an inverter.
The use of an inadequate breaker can cause the incorrect operation of
inverter.
2. Max. 45 m
If 2.5 mm 2 used, Max. 50 m
If 2.5 mm 2 used and S3 separated, Max. 80 m
3. The 10 m wire is attached in the remote controller accessory.
4. The figures are NOT always against the ground.
S3 terminal has 24 VDC against S2 terminal. However between S3 and S1, these
terminals are NOT electrically insulated by the transformer or other device.
Notes:
-
Wiring size must comply with the applicable local and national codes.
-
Power supply cables and the cables between Interface unit/Flow temp. controller and outdoor unit shall not be lighter than polychloroprene sheathed flexible cables. (Design 60245 IEC 57)
-
Be sure to connect the cables between Interface unit/Flow temp. controller and outdoor unit directly to the units (no intermediate connections are al- lowed).
Intermediate connections may result in communication errors. If water enters at the intermediate connection point, it may cause insufficient insulation to ground or a poor electrical contact.
(If an intermediate connection is necessary, be sure to take measures to prevent water from entering the cables.) -
Install an earth longer than other cables.
-
Do not construct a system with a power supply that is turned ON and OFF frequently.
-
Use self-extinguishing distribution cables for power supply wiring.
-
Properly route wiring so as not to contact the sheet metal edge or a screw tip.
WARNING:
- In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
Never splice the power cable or the indoor-outdoor connection cable, otherwise it may result in a smoke, a fire or communication failure.
System control
Set the refrigerant address using the DIP switch of the outdoor
unit. Note:
a) Up to 6 units can be connected.
b) Select one single model for all units.
c) For Dip switch setting for indoor unit, refer to the indoor unit’s
installation manual.
Specifications
Outdoor model| PUZ-WM5OVHA| PUZ-WM6OVAA| I PUZ-WM85VAA| I PUZ-WM112VAA| PUZ-
WM85YAA| I PUZ-WM112YAA
---|---|---|---|---|---|---
Power supply| V / Phase / Hz| 230 / Single / 50| 400 / Three / 50
Dimensions (W x H x D)| mm| 950 x 943 x 330| 1050 x 1020 x 480
Sound Power Level *1 (Heating)| dB(A)| 61| 58| 60| 58| 60
*1 Measured under rated operation frequency.
Serial number
■ The serial number is indicated on the SPEC NAME PLATE. EC DECLARATION OF CONFORMITY
MITSUBISHI ELECTRIC AIR CONDITIONING SYSTEMS EUROPE LTD.
NETTLEHILL ROAD, HOUSTOUN INDUSTRIAL ESTATE, LIVINGSTON, EH54 5EQ, SCOTLAND,
UNITED KINGDOM
hereby declares under its sole responsibility that the air conditioners and
heat pumps described below for use in residential, commercial and light-
industrial environments:
MITSUBISHI ELECTRIC, PUZ-WM50VHA, PUZ-WM50VHA-BS,
PUZ-WM60VAA, PUZ-WM60VAA-BS, PUZ-WM85VAA, PUZ-WM85VAA-BS, PUZ-
WM112VAA, PUZ-WM112VAA-BS,
PUZ-WM85YAA, PUZ-WM85YAA-BS, PUZ-WM112YAA, PUZ-WM112YAA-BS
* : , , 1, 2, 3, · · · , 9
Note: Its serial number is on the nameplate of the product.
Directives
2014/35/EU: Low Voltage
2006/42/EC: Machinery
2014/30/EU: Electromagnetic Compatibility
2009/125/EC: Energy-related Products Directive and Regulation (EU) No.
813/2013
2011/65/EU, (EU) 2015/863 and (EU) 2017/2012: RoHS Directive
2014/68/EU: Pressure Equipment
Issued: UNITED KINGDOM
1 January 2020
Atsushi Edayoshi
Manager, Quality Assurance Department
English is original. The other languages versions are translation of the
original.
CAUTION
- Refrigerant leakage may cause suffocation. Provide ventilation in accordance with EN378-1.
- Be sure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or frostbite.
- Never put batteries in your mouth for any reason to avoid accidental ingestion.
- Battery ingestion may cause choking and/or poisoning.
- Install the unit on a rigid structure to prevent excessive operation sound or vibration.
- The A-weighted sound pressure level is below 70dB.
- This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
This product is designed and
intended for use in the residential, commercial and light-industrial
environment.
Importer:
Mitsubishi Electric Europe B.V.
Capronilaan 46, 1119 NS, Schiphol Rijk, The Netherlands
French Branch
25, Boulevard des Bouvets, 92741 Nanterre Cedex, France
German Branch
Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany
Belgian Branch
Autobaan 2, 8210 Loppem, Belgium
Irish Branch
Westgate Business Park, Ballymount, Dublin 24, Ireland
Italian Branch
Centro Direzionale Colleoni, Palazzo Sirio-Ingresso 1 Viale Colleoni 7, 20864
Agrate Brianza (MB), Italy
Norwegian Branch
Gneisveien 2D, 1914 Ytre Enebakk, Norway
Portuguese Branch
Avda. do Forte, 10, 2799-514, Carnaxide, Lisbon, Portugal
Spanish Branch
Carretera de Rubi 76-80 – Apdo. 420 08173 Sant Cugat del Valles (Barcelona),
Spain
Scandinavian Branch
Hammarbacken 14, P.O. Box 750 SE-19127, Sollentuna, Sweden
UK Branch
Travellers Lane, Hatfield, Herts., AL10 8XB, England, U.K.
Polish Branch
Krakowska 50, PL-32-083 Balice, Poland
Please be sure to put the contact address/telephone number on this manual
before handing it to the customer.
MITSUBISHI ELECTRIC CORPORATION
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310,
JAPAN
BH79D849H02
Printed in UNITED KINGDOM
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>