PHILIPS BN126C 4ft Coreline LED Batten Instruction Manual

June 12, 2024
Philips

BN126C 4ft Coreline LED Batten
Instruction ManualPHILIPS BN126C 4ft Coreline LED
Batten CoreLine Batten
BN126C Emergency
PHILIPS BN126C 4ft Coreline LED Batten - icon 1

BN126C 4ft Coreline LED Batten

PHILIPS BN126C 4ft Coreline LED Batten - fig 1

TYPE| Energy effciency class| P(W)| System light output (Lm)| System light output  Emerygency mode (Lm)|
---|---|---|---|---|---
BN126C LED41S/840 PSU ELB3 L1200| D| 36| 4100| 480| 1.45
BN126C LED52S/840 PSU ELB3 L1500| D| 44| 5200| 500| 1.7
BN126C LED80S/840 PSU ELB3 L1500| D| 64| 8000| 500| 1.75
Life time able

L85 SOk hrs| All
L80 75K hrs| 5200-64001m
L70 up to 100K hrs| 2500-41001m

PHILIPS BN126C 4ft Coreline LED Batten - fig 2

PHILIPS BN126C 4ft Coreline LED Batten - fig 3 ** -The luminaire shall be installed by a qualified electrican and wired in ccordance with the latest IEE electrical regulations or the national requirements.
– The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole luminaire shall be replaced.
– Luminaire must not be used or stored in corrosive environment where hazardous materials such as sulphur,chlorine, phthalates,etc,are present.
– Water entering into IP20 luminaire is strictly prohibited. IP20 luminaire is not protected against wet condition, water ingress may cause electrical failure or unsafe conditions.
– Luminaire is rated at IP40 from the front (part 1) and IP20 for a complete housing (part 2).
ATTENTION
OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC SENSITIVE DEVICESPHILIPS
BN126C 4ft Coreline LED Batten - fig 4PHILIPS BN126C 4ft Coreline LED Batten - fig
5PHILIPS BN126C 4ft Coreline LED Batten - fig
6PHILIPS BN126C 4ft Coreline LED Batten - fig
7The batteries have a life time expectancy of 4 years. Do not touch electronic components!Electronic components may be under high voltage.
Light intensity distribution curves
Emergency mode**PHILIPS BN126C 4ft Coreline LED Batten - fig
8Service data for battery change:

Battery Unit

Manufacturer Philips
Unit TrustSight 6,4V 4cell

3000 mAh battery LFP
Technology| LFP
Capacity| 3000 mAh
Power| 4,8 W
Duration| 3 h
Nominal voltage| 6,4 V

Maintenance instructions

To assure the lighting quality of this unique LED lighting concept there are only a few instructions regarding the maintenance of this LED luminaire:
ATTENTION
OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC SENSITIVE DEVICES

  • Do not stare into LED light beam.
  • The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical regulations or the national requirements.
  • Above average concentracion of sulfur effects the useful lifetime of the product.
    E.g: Light color changes from white to blue. Typically in chicken & pig farms.

Functional Notice for Emergency Lighting

Automatic emergency time selection
After installation and power up the driver will detect the battery and start the automatic detection process.

  • During automatic detection, the indicator LED will light up with short green flashes.
  • Between minimum 6 and maximum 30 seconds the TrustSight driver will set the battery type (number of cells) and will set the emergency output power accordingly.

After that, the system is defined and fully operational. The battery type definition has influence on the performance during the self-test and on the battery charge method. When the automatic battery detection process is disrupted, e.g. by switching off the permanent mains, the detection process is stopped and the TrustSight emergency driver will go into emergency mode with the lowest output power. At a next power up, the automatic detection process will start again.
Periodic testing
Periodic tests of emergency lighting luminaires must be performed according to EN50172 clause 7.2.3 and 7.2.4. Switch on in the emergency mode each month by simulation of a failure of the supply to the normal lighting for a period sufficient to ensure that each lamp is illuminated. Twice per year, each luminaire shall be tested for its full rated duration (at least 3hrs).
For more information please consult the TrustSight Gen 3 Design in guide. The latest version is available online.

LED indicator (color / flashing) Error condition Cause Solution
Green / no flashing System OK battery fully charged
Off Mains oft EM mode, Rest mode, test in progress
Green/slow (0.25s on 125s oft) System OK battery is charging
Green/ fast (0.2k on, 025s off) System OK recently tested (< 5 days,

Australia mode only)
Red/no flashing| Battery voltage too high or too low| No battery connected| Connect battery
| Wrong or bad battery connected| Replace battery
Red / fast (0.25s on, 0.25sofft| Output voltage too low or too high| Wrong LED load connected| Connect right load and perform functional test
No load connected or output shorted| Wrong connection| Connect right load and perform functional test
Red /slow (0.25s on, 1.25s oft)| Failed test due to battery| Battery end of life Charger failure| Replace battery and perform duration test Replace driver
Red-green / fast
Fast flashing: (on-time = 0.254 off-time = 0.25s) Slow flashing. (on-time = 0.25; off-time = 1.25s)| | DALI device identification|
Green/short on-time = 50ms, off-time = 0.95s)| | Battery detection|

PHILIPS BN126C 4ft Coreline LED Batten - fig 9 Signify Holding.
All rights reserved. This document contains information relating to the product portfolio of Signify which information may be subject to change. No representation or warranty as to the accuracy or completeness of the information included herein is given and any liability for any action in reliance thereon is disclaimed. The information presented in this document is not intended as any commercial offer and does not form part of any quotation or contract.Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V.. All other trademarks are owned by Signify Holding or their respective owners.
Signify Holding.
The Netherlands
Emergency Luminaires
In case a self-contained emergency driver has been added, this is how to set the timers (IEC62034 (§6.3.21):
DALI version : Check IEC 62386 part 202.
PRO version: The first test is randomized. Then a fixed schedule is maintained, there is no need to set the timers or take special precautions when powering
BASIC version : No timers available, only manual testing through the test button. PHILIPS BN126C 4ft Coreline LED Batten - fig
10To get an overview of all spare parts for a luminaire, please refer to detailed instructions in the service manual available via the Signify Service tag apps (Android and i0S). https://play.google.com/store/apps/details?id=com.philips.servicetag

Disconnect before servicing
Luminaire has basic insulation between Low Voltage supply and control conductors.
The light source and/or control gear and/or the external flexible cable contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
Storage, installation, use, operation and maintenance of the products needs to be performed exactly according the instructions in this manual and/or other instructions as may be provided by us to guarantee safe use of the product over its entire lifetime. Failure to adhere to these instructions will invalidate your entitlement to warranty. Bolts with indication of torque strength on the drawing need to be tightened using a calibrated torque wrench. Pre-assembled bolts need to be retightened again to the required torque specification to assure maximum strength over lifetime.
This product contains a light source of energy efficiency class: see tableor label.
– For Zhaga-D4i/SR-Certified based luminaires only Zhaga-D4i/SR-Certified components/sensors are to be used
(see also: https://www.zhagastandard.org/products / https://www.lighting.philips.co.uk/oem-emea/products/driving-connected- lighting). The functional compatibility of two SR-certified and/or Zhaga-D4i controllers/sensors to be used in combination, as well as the override possibility of any line-switch function used in an SR-based/Zhaga-D4i luminaire, is to be released by the master controller/sensor supplier. If using a NEMA 7-pin socket on an SR-based luminaire, a full system verification is required. Not following this advice can/will cause risk of damage and non- compliance for which Signify cannot take any responsibility.

2022 Signify Holding
All rights reserved. Reproduction in whole or in part is prohibited without the prior written consent of the copyright owner. The information presented in this document does not form part of any quotation or contract, is believed to be accurate and reliable and may be changed without notice. No liability will be accepted by the publisher for any consequence of its use. Publication thereof does not convey nor imply any license under patent- or other industrial or intellectual property rights.
Signify Holding The Netherlands

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals