HYTRONIK QCB01/BLESID Mesh System User Guide

June 3, 2024
HYTRONIK

HYTRONIK QCB01/BLESID Mesh System

*QCB01/BLE is supplied with white color housing by default. Black color housing can be supplied upon request.

Key Features

  • Non-dimmable control applications
  • Intelligent control with Bluetooth 5.0 SIG mesh module built in
  • 2 types of built-in Bluetooth 5.0 control module to select from
  • Detailed Bluetooth system features can be viewed on page 03-09
  • Luminaire outlet: Wieland 4-pole terminal base (L’, N, E, Em)
  • Black housing and white housing available to choose from
  • Tamper-proof structure design
  • Expandable: easy extension to another QCB01/BLE wirelessly
  • Rating of system: Default rating is 400VA capacitive & 800W resistive
  • Max 10A can be supplied as a special version upon request
  • Flame-retardant material for safety protection

Your Benefits

  • Five types of installation methods meets different project needs
  • Reduce labour hours and labour cost significantly
  • Simple and intuitive wiring connections
  • Improved safety level during wiring operations
  • Clear and clean wiring makes it easy for future maintenance
  • Can be supplied with pre-wired cables

Mechanical Structure & Dimensions

HYTRONIK-QCB01-BLESID-Mesh-System-fig-3

Warning:

  • Installation of this device involves connecting it to the mains supply. This work must be carried out by a specialist in accordance with electrcial technical regulations.
  • Disconnect supply before installing.

Input & Output Terminal Function

HYTRONIK-QCB01-BLESID-Mesh-System-fig-4HYTRONIK-QCB01-BLESID-Mesh-System-fig-5In the middle of the QCB01/BLE there is a pre-installed Bluetooth 5.0 SIG mesh controller module. We offer 2 types of different controller modules for users to choose from (HBTD8200S/F or HBTD8200S/F/CA). For each controller module, all the 8 luminaire outlets as one channel (1 x 8). Default rating for this controller module is 400VA capacitive & 800W resistive. If higher loading capability is required, we can supply a special version with max 10A capability upon request.

Technical Specifications

Mains voltage 220~240VAC 50/60Hz
Rated load Rating of system 10A. Rating of each output 10A
Terminal capacity 0.75 – 4.0mm2 (max. 2 x 2.5mm2)
Storage temperature -20°C ~ +60°C
Max. relative humidity 20 ~ 90%
Compliance CE, UKCA
Insulation Class II

Minimum Installation

Note: The minimum height for total height of unit is 140mm (including connectors and cables).

Wiring Diagram

(QCB01/BLE-S or QCB01/BLE-SCA)

Wiring & Emergency Test
Local lighting switch and local emergency test switch

Emergency test using power interruption Note:

  1. A local lighting switch may still be used when there is a central emergency test switch or when a circuit breaker is used to interrupt the power.
  2. Do not wire across phases.

Emergency test using central switchHYTRONIK-QCB01-BLESID-Mesh-System-
fig-10 Note:

  1. A local lighting switch may still be used when there is a central emergency test switch.
  2. Do not wire across phases.

Ceiling Rose/ Conduit Box Connection

Ceiling rose QCCR01 can be used when there is a need to take power from a conduit box. The installation-friendly design comes with a very spacious termination space for really easy wirings.HYTRONIK-QCB01-BLESID-Mesh-System-
fig-11