RAB X17 XFU 3-Way Adjustable Dusk to Dawn LED Flood Light Instruction Manual
- June 4, 2024
- RAB
Table of Contents
RAB X17 XFU 3-Way Adjustable Dusk to Dawn LED Flood Light Instruction Manual
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR
FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and
all applicable local codes. Proper grounding is
required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE
APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND
OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining
fixture. No user serviceable parts inside.
WARNING: Do not use an electric generator to test LED fixtures.
WARNING: Min 75°C SUPPLY CONDUCTORS.
KNUCKLE MOUNT
To ensure weatherproof seal, apply weatherproof silicone sealant around the edge of the junction box (not supplied). This is especially important with an uneven wall surface.
- Secure the fixture to a 1/2” NPS hole in the junction box or landscape post as shown in Fig. 1. Seal arm thread using Teflon® tape or silicone sealant.
- Make appropriate wire connections per NEC in an approved enclosure (not included) see Fig. 7.
- The Knuckle Arm allows 180° of vertical aiming adjustment depending on the mounting position as shown in Fig. 2.
TRUNNION MOUNT
To adjust the angle of the Fixture using the Trunnion (Fig. 4):
- Loosen the Pivot Bolts and Angle Locking Screws.
- Make appropriate wire connections per NEC in an approved enclosure (not included) see Fig. 7.
- Adjust fixture to desired angle.
- Tighten Pivot Bolts and Angle Locking Screw.
SLIPFITTER MOUNT
- Place the Slipfitter over the Tenon and secure the Fixture with the Locking Bolts (4) on the side of the Slipfitter as shown in Fig. 3.
- Make appropriate wire connections per NEC in an approved enclosure (not included) see Fig. 7.
- Loosen the Locking Bolts (4) and swivel Fixture to desired angle.
- Tighten the Locking Bolts (4).
FIELD ADJUSTMENT
Follow instructions below to change fixture Power (W) or Color Temperature (CCT) from the factory settings and Photocell On/Off option.
Factory Settings: 4000K and 60W
- Remove Selector Switch Caps by turning counterclockwise using a flat head screwdriver (Fig. 5).
- Locate the Selector Switches on the fixture (Fig. 6).
- Select Power (W) and Color Temperature (CCT) by sliding the respective switch to the desired value.
- Select Photocell On/Off option by sliding respective switch to the desired value.
- Replace Selector Switch Caps and tighten with a flat head screwdriver.
Note : These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V thru 277V, 50 or 60 Hz. For 0-10 Dimming, follow the wiring directions as shown in Fig. 7.
-
Connect the black/brown fixture lead to the LINE supply lead.
-
Connect the white/blue fixture lead to the COMMON supply lead.
-
Connect the green/yellow wire from fixture to supply ground. Do NOT connect the GROUND of the dimming fixture to
the output. -
Connect the purple fixture lead to the DIM V+ lead.
-
Connect the pink/gray fixture lead to the DIM V- lead.
-
Cap the yellow fixture lead, if present. Do NOT connect
CLEANING & MAINTENANCE
CAUTION: Be sure fixture temperature is cool enough to touch.
Do not clean or maintain while fixture is energized.
- Clean glass lens with non-abrasive glass cleaning solution.
- Do not open the fixture to clean the LED. Do not touch the LED.
TROUBLESHOOTING
- Is the fixture grounded properly?
- It is recommended that gloves be worn to avoid injury during installation.
- If any smoke or spark, please turn off the power immediately.
© 2021 RAB LIGHTING Inc.
X17 XFU 60-50-30 IN-1021
P-100056
Easy Answers
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
e-mail
Answered promptly – sales@rablighting.com
Free Lighting Layouts
© 2021 RAB LIGHTING Inc. Answered online or by request
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>