Oomi In-Wall Switch FT139-A Manual
- June 8, 2024
- Oomi
Table of Contents
- Oomi
- In-Wall Switch
- SKU: FT139-A
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 120: Configure the external switch mode for S1.
- Parameter 121: Configure the external switch mode for S2.
- Parameter 122: Set the control destination for external switch
- Parameter 20: Configure the output status after re-power on it.
- Parameter 252: Lock/unlock configuration parameters
- Parameter 255: Reset the In-Wall Switch
- Parameter 4: Overheat protection.
- Parameter 80: To set which notification would be sent to the associated
- Parameter 81: To set which notification would be sent to the associated
- Parameter 82: To set which notification would be sent to the associated
- Parameter 83: Configure the state of LED when it is in 3 modes
- Parameter 84: Set the ON/OFF time of the LED when it is in Night light
- Parameter 86: Set appointment 1
- Parameter 87: Set appointment 2
- Technical Data
- Supported Command Classes
- Controlled Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Oomi
In-Wall Switch
SKU: FT139-A
Quickstart
This is a
secure
On/Off Power Switch
for
U.S. / Canada / Mexico.
To run this device please connect it to your mains power supply.
To add this device to your network execute the following action:
Turn the primary controller of Z-Wave network into inclusion mode, short press
the products Action button that you can find on the product’s housing.
Please refer to the
Manufacturers
Manual for more information.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
Oomi In-Wall Switch is a Z-Wave Smart Switch specifically used to enable Z-Wave command and control (on/off) of any wall switches. In the event of power failure, non-volatile memory retains all programmed information relating to the units operating status.It can connect to 2 external manual switches to control the load ON/OFF independently. Its surface has a pin socket, which can be used for connecting to the touch panel, so you can also use the touch panel to control the Dual Nano Switch.The In-Wall Switch is also a security Z-Wave device and supports Over The Air (OTA) feature for the products firmware upgrade.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave
controller. This
procedure should only be used when the primary controller is inoperable.
Press and hold the Action button that you can find on the product’s housing for 20 seconds and then release. This procedure should only be used when the primary controller is inoperable.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-
specific
installation guidelines/norms may do works with mains power. Prior to the
assembly of
the product, the voltage network has to be switched off and ensured against
re-switching.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Inclusion
Turn the primary controller of Z-Wave network into inclusion mode, short press the products Action button that you can find on the product’s housing.
Exclusion
Turn the primary controller of Z-Wave network into exclusion mode, short press the products Action button that you can find on the product’s housing.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1| 5| Z-Wave Plus Lifeline.When the load state of Nano Switch (turn on/off the
load) is changed, the Hail CC and Basic Report (configured by parameter 80)
can be sent to the associated nodes in this group.
---|---|---
2| 5| Forward the Basic Set, Switch All, Scene Activation Set to associated
nodes in Group 2 when the Dual Nano Switch receives the Basic Set, Switch All,
Scene Activation Set commands from main controller. (E.g. Send/forward Basic
Set to control the other nodes in association Group 2)
3| 5| Send Basic Set (configured by parameter 0x51 ) to the associated nodes
in Group 3 when the external switch S1 is operated.Note: The Switch Mode of
external switch S1 should be identified successfully, which means that the
value of Configuration parameter 0x78 should be non-zero, then the Basic Set
can be sent to the associated nodes in Group 3 via triggering the S1 switch.
4| 5| Send Basic Set (configured by parameter 0x52) to the associated nodes in
Group 4 when the external switch S2 is operated.Note: The Switch Mode of
external switch S2 should be identified successfully, which means that the
value of Configuration parameter 0x79 should be non-zero, then the Basic Set
can be sent to the associated nodes in Group 3 via triggering the S2 switch.
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 120: Configure the external switch mode for S1.
Configure the external switch mode for S1.
Size: 1 Byte, Default Value: 0
SettingDescription
2 | 3 way switch mode |
---|---|
0 | Enter automatic identification mode |
1 | 2-state switch mode |
3 | Momentary push button mode |
Parameter 121: Configure the external switch mode for S2.
Configure the external switch mode for S2.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Enter automatic identification mode |
---|---|
1 | 2-state switch mode |
2 | 3 way switch mode |
3 | Momentary push button mode |
Parameter 122: Set the control destination for external switch
Set the control destination for external switch
Size: 1 Byte, Default Value: 3
SettingDescription
1 | control the output loads of itself. |
---|---|
2 | control the other nodes |
3 | control the output loads of itself and other nodes. |
Parameter 20: Configure the output status after re-power on it.
Configure the output status after re-power on it.
Size: 1 Byte, Default Value: 0
SettingDescription
1 | Always on |
---|---|
0 | Last status |
2 | Always off |
Parameter 252: Lock/unlock configuration parameters
Lock/unlock configuration parameters.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Unlock |
---|---|
1 | Lock |
Parameter 255: Reset the In-Wall Switch
Reset the In-Wall Switch to factory default.
Size: 4 Byte, Default Value: 0
SettingDescription
1431655765| Reset to factory default setting and removed from the z-wave
network
---|---
0| Reset all configuration parameters to factory default setting
Parameter 4: Overheat protection.
Output Load will be turned off automatically after 30 seconds and if the
temperature of product inside exceeds 100 .
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Disable |
---|---|
1 | Enable |
Parameter 80: To set which notification would be sent to the associated
devices (Group 1)
To set which notification would be sent to the associated devices (Group 1)
when the state of Nano Dimmers load is changed.
Size: 1 Byte, Default Value: 3
SettingDescription
0 | Send Nothing |
---|---|
1 | Send Hail CC |
2 | Send Basic Report CC |
3 | Send Hail CC when using the manual switch to change the load state. |
Parameter 81: To set which notification would be sent to the associated
nodes in association group 3
To set which notification would be sent to the associated nodes in
association Group 3 when using the external switch 1 to switch the loads.
Size: 1 Byte, Default Value: 1
SettingDescription
0 | Send Nothing |
---|---|
1 | Send Basic Set CC |
Parameter 82: To set which notification would be sent to the associated
nodes in association group 4
To set which notification would be sent to the associated nodes in
association Group 4 when using the external switch 2 to switch the loads.
Size: 1 Byte, Default Value: 1
SettingDescription
1 | Send Basic Set CC |
---|---|
0 | Send Nothing |
Parameter 83: Configure the state of LED when it is in 3 modes
Configure the state of LED when it is in 3 modes (Energy mode, Momentary
indicate mode, Night light mode)
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Energy mode. The LED will follow the status (on/off). |
---|---|
1 | Momentary indicate mode. When the state of Switchs load changed, the LED |
will follow the status (on/off) of its load, but the LED will turn off after 5
seconds if there is no any switch action.
2| Night light mode. The LED will remain ON state.
Parameter 84: Set the ON/OFF time of the LED when it is in Night light
mode.
Set the ON/OFF time of the LED when it is in Night light mode.
Size: 4 Byte, Default Value: 301991936
SettingDescription
0 – 60 | The minute time of OFF |
---|---|
256 – 316 | The hour time of OFF |
65536 – 65596 | The minute time of ON |
16777216 – 16777276 | The hour time of ON |
Parameter 86: Set appointment 1
Set the ON time of output load.
Size: 4 Byte, Default Value: 8327680
SettingDescription
0 – 60 | The minute value of ON time |
---|---|
65536 – 65543 | The day value (Mon to Sun) |
16777216 | Enable the setting. |
256 – 316 | The hour value of ON time |
16777215 | Disable the setting. |
Parameter 87: Set appointment 2
Set the OFF time of output load.
Size: 4 Byte, Default Value: 8327680
SettingDescription
256 – 316 | The hour value of ON time |
---|---|
65536 – 65543 | The day value (Mon to Sun) |
16777215 | Disable the setting. |
0 – 60 | The minute value of ON time |
16777216 | Enable the setting. |
Technical Data
Hardware Platform | ZM5101 |
---|---|
Device Type | On/Off Power Switch |
Network Operation | Always On Slave |
Firmware Version | HW: 139 FW: 1.01:01.00 |
Z-Wave Version | 6.51.09 |
Certification ID | ZC10-18015945 |
Z-Wave Product Id | 0x016A.0x0103.0x008B |
Firmware Updatable | Updatable by Consumer by RF |
Electric Load Type | Dimmable LEDELV (Electronic)FluorescentIncandescentLEDMLV |
(Magnetic)
Supported Notification Types| Heat Alarm
Switch Type| Toggle
Z-Wave Scene Type| Scene
Frequency| XXfrequency
Maximum transmission power| XXantenna
Supported Command Classes
- Association Grp Info
- Association V2
- Basic
- Clock
- Configuration
- Device Reset Locally
- Firmware Update Md V3
- Manufacturer Specific V2
- Notification V4
- Powerlevel
- Scene Activation
- Scene Actuator Conf
- Security
- Switch All
- Switch Binary
- Version V2
- Zwaveplus Info V2
Controlled Command Classes
- Basic
- Hail
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>