GOODWE SECU-A Series Rechargeable Lithium Ion Battery System
Statement
This document contains safety information and instructions on installing, connecting and commissioning. Please finish reading this document before taking any actions on the system.
This manual introduces the installation and commissioning of battery. Please read through the manual and follow the instructions to use battery.
This document is valid for the *** from firmware version **.
This document only contains brief information and may deviate from the real system.
Any Failure to follow this document instruction will make any manufacturer’s warranty, guarantee or liability null and void unless you can prove that the damage was not due to non-compliance.
The battery is used with GoodWe ESA/ES/EM/SBP/BP series products. The battery is designed for indoor use. But in a ESA system, the battery is protected by the ESA enclosure, which could be used outdoors.
The system is not suitable for supplying life-sustaining medical devices. Please ensure that no personal injury would lead due to the power outage of the system.
Alterations to the GoodWe system, e.g., changes or modifications are not allowed unless the written permission of GoodWe is achieved.
The enclosed document is an integral part of this system. Keep the documentation in a convenient, dry place for future reference and observe all instructions contained therein.
The instructions in this document may only be performed by qualified persons who must have the following skills:
- Knowledge of how batteries work and are operated
- Knowledge of how an inverter works and is operated
- Knowledge of, and adherence to the locally applicable connection requirements, standards and directives (the local standard for Australia is AS/NZS 5139:2019)
- Knowledge of, and adherence to this document and the associated system documentation, including all safety instructions
- Training in dealing with the hazards associated with the installation and operation of electrical equipment and batteries
- Training in the installation and commissioning of electrical equipment
The battery must be stored, installed or operated under secured environment, including:
- Ambient temperature shall be -10℃~ 50℃
- Keep it away from corrosive liquids or environment
- Keep it dry, away from any conductive liquid
- No high flammable or explosive materials nearby
Symbols Explanation
| Observe the documents
Observe all documents with the system
---|---
| Grounding
conductor
This symbol indicates the position for connecting a grounding conductor.
| WEEE designation
Do not dispose of the system together with household waste but in accrodance
with the disposal regulations for electronic waste applicable at the
installation site.
| CE mark
The system complies with the requirements of the applicable EU directives
| Please it straight up, without inclination or upside down
| Handle with care
| Keep it dry
| Keep the battery away from open flame or ignition sources.
| Beware of electrical voltage.
| Beware of a danger zone
This symbol indicates that the system must be additionally grounded if
additional grounding or equipotential bonding is required at the installation
site.
| Keep the battery modules away from children.
| Do not short circuit.
| No more than five (5) identical packages being stacked on each other.
Product Overview
[1]: Only for SECU-A5.4L.
Note :
The two COM ports on battery are of the same function.
The two Power Cable Connector + or – on battery are of the same function.
Cable Connection
Power Cable Connection
Note:
-
The battery is designed for GoodWe ESA, ES, EM, SBP, BP series energy storage system.
Before installation, make sure battery is not damaged and battery breaker is switched OFF. And whole energy storage system is isolated from both AC and DC power. -
Before installation and cable connection, make sure battery is not damaged and battery breaker is switched OFF. And whole ESA cabinet is isolated from both AC and DC power.
-
Battery packs shall be connected in parallel.
-
Each battery has two sets of Power Cable Connector – and ﹢, which functions the same. Any of the two sets could be used for power connection.
-
Please make sure the positive and negative pole on both battery and inverter side not reversed, otherwise the inverter or battery could be damaged.
-
The unused battery connectors must be sealed with connector cover.
-
When replacing or expanding the battery system, it is prohibited to connect the battery to the systerm , please contact the after-sales service for processing.
-
Please refer to the inverter user manual for specific connectors on each inverter. We just take SBP and ESA series inverter as example to introduce the connection in this manual.
Power cable connection of battery with ES, EM, SBP and BP inverters
When battery is used with ES, EM, SBP and BP series inverters the power cable needs to be prepared by the user, the recommended conductor cross-sectional area is 25mm2.
Power cable connection of battery with ESA inverter
- Before installation and cable connection, make sure the whole ESA cabinet is isolated from both AC and DC power.
- The cables between the battery and the inverter are connected in the same way. Please refer to the “Cable connection of battery with ES, EM, SBP and BP inverters”.
- Open battery enclosure and install batteries and other component by sequence as below:
Communication Cable Connection
Communication cable connection of battery with ES, EM, SBP and BP inverters
When battery is used with ES, EM, SBP and BP series inverters the network cable needs to be prepared by the user.
PIN | Colour | SECU-A5.4L | SECU A5.4-20 |
---|---|---|---|
1 | Orange and White | N/A | RS485_A |
2 | Orange | N/A | RS485_B |
3 | Green and White | N/A | N/A |
4 | Blue | CAN_H | CAN_H |
5 | Blue and White | CAN_L | CAN_L |
6 | Green | N/A | N/A |
7 | Brown and White | N/A | N/A |
8 | Brown | N/A | N/A |
RJ45 connector
Communication cable connection of battery with ESA inverter
In battery enclosure, battery cable and communication cable is preset inside. Connect directly these cables on battery to the right position:
Note:
- The two COM ports on battery are of the same function.
- Battery packs shall be connected in parallel.
- The cables between the battery and the inverter are connected in the same way. Please refer to the “Cable connection of battery with ES, EM, SBP and BP inverters”.
Battery Commissioning
Calibrating the DIP switch(SECU-A5.4L)
- The DIP switches shall be configured differently between single piece battery and 2 battery paralleling system.
- We just take SBP series inverter system as an example, the calibration method of the DIP switch for ESA series inverter system is the same.
Single Unit Of SECU-A5.4L System
2~6 Units Of SECU-A5.4L System
Powering on the battery system
- Check all cables are connected correctly.
- Turn on the battery break.
- Turn on all battery switches within 30 seconds in the system. If it exceeds 30 seconds, there will be a error alarm.
Battery Switch(SECU-A5.4L)
TURN ON | TURN OFF |
---|---|
Pressing < 1 seconds | Keep Pressing > 5 seconds |
Battery Switch(SECU A5.4-20)
TURN ON | TURN OFF |
---|---|
Pressing < 1 seconds | Turn off the battery breaker |
Note : Please follow the instruction to turn on/off battery in case of any damage on battery modules.
Setting the parameters of battery On PV Master app
To make sure the battery communicates to inverter unit successfully, users have to use PV Master to choose the right battery option on PV Master:
APP Installation And Connection:
Download and install PV Master|
---|---
Select Battery on PV master
Select “SECU-A5.4L” or “SECU A5.4-20”on battery page in PV Master Application
Notes:
- Select wrong battery will lead to BMS communication failure
- Select wrong number of batteries the input and output current will be limited and the parameter indicated by the inverter is inconsistent with the actual value of the battery.
- For the complete commissioning of the whole ESA system, please go to ESA instruction.
Observing the indicator status
LED Indication
Operation Indicator(SECU-A5.4L)
Green, Blink 1s| Standby
Green, Blink 10s| Working
Green, Blink 3s| Alert
Red, Blink 3s| Faulty
Operation Indicator(SECU A5.4-20)
Green light blink 1 time in 1second| Standby
Steady green| Working
Red light blink 1 time in 1second| Alert
Steady red or Red light blink 1 time in 1second| Faulty
Operation Indicator
| SOC < 5%
| 5%≤ SOC ≤25%
| 25%≤ SOC ≤50%
| 50%≤ SOC ≤75%
| 75%≤ SOC ≤95%
| 95%≤ SOC ≤100%
Error Code and Warning Code
SECU-A5.4L
Warning Status
Operation LED | SOC LED | Warning Description |
---|
Green Blink 3 seconds
| | Cell Temperature Difference
| Battery High Temperature
| Discharge Under Low Temperature
| Charge Overcurrent
| Discharge Overcurrent
| Battery Over Voltage
| Battery Under Voltage
| Charge Under Low Temperature
Note : If Battery Under Voltage happens during working status, by pressing battery switch for 5 times in 10 seconds, BMS will compulsively close MOS, so that inverter will detect battery open circuit voltage to charge battery.
Error Status
Operation LED | SOC LED | Error Description | Solution |
---|---|---|---|
Red Blink 3 seconds | Temperature Sensor Failure | Reboot battery or contact |
aftersales
| MOS Fault
| Breaker Open| Turn Off battery and contact aftersales
| DIP Switch Status difference| Keep same of DIP switch status and
reboot battery
| Slave Communication Loss| Reconnect communication cable
| No Series Number| Contact aftersales
| Master Communication Loss| Reconnect communication cable
| Firmware Inconsistency| Contact aftersales
| Multi Master Unit| Turn off and reboot all batteries in 30s
| MOS Over temperature| Turn off battery for 2 hours
SECU A5.4-20
Warning Status
Operation LED | SOC LED | Warning Description |
---|---|---|
Red light blink 1 time in 1 second | The alerting is dealt by the battery |
system itself. For more detailed information, you can check via PV Master App.
Error Status
Operation LED | SOC LED | Error Description | Solution |
---|---|---|---|
Steady red | Overvoltage | Power off for 2 hours. If the problem persists, |
please contact GoodWe.
Red light blink 1
time in 1 second
| | Under voltage| Contact GoodWe for help.
Steady red
| | Cell High Temperature| Power off for 2 hours.If the problem
persists, please contact GoodWe.
| Low Temperature Charging| Power off the equipment and wait until the
temperature recovers. If the problem persists after restarting, please contact
GoodWe.
| Low Temperature
Discharging
| Overcurrent When Charging|
Restart the battery. If the problem persists, please contact GoodWe for help.
| Overcurrent When
Discharging
| Temperature Exception| Power off for 2 hours.If the problem persists, please
contact GoodWe.
| The cell voltage difference is extremely high| Power off for 12 hours.If the
problem persists, please contact GoodWe.
| Harness Abnormal|
Restart the battery. If the problem persists, please contact GoodWe for help.
| MOS Open-Circuit Fault
| MOS Short-Circuit Fault
|
Parallized Connection Fault
| Check the battery model. If the battery model is not correct, please contact
GoodWe.
| BMU Communication Fault|
Restart the battery. If the problem persists, please contact GoodWe for help .
| MCU Internal Communication Fault
Steady red| | Air Switch Short Circuit Fault| Contact GoodWe for help.
---|---|---|---
| Precharge Failure| Restart the battery. If the problem persists, please
contact GoodWe for help.
| MOS Overtemperature Fault|
Power off for 2 hours. If the problem persists, please contact GoodWe.
| Current Sensor Overtemperature Fault
| Microelectronic Fault| Contact GoodWe for help.
Battery Parameters
Physical Parameters
Model| SECU-A5.4L
Battery Type| LiFePO4
System Weight| 49kg
Dimensions(W x D x H )| 400×226.2×484.2mm
Protection| IP20 (indoor)
Installed Capacity| 5.4 kWh
Usable Energy| 4.8 kWh
DOD| 90%
Nominal Voltage| 51.2 V
Operating Voltage Range| 48 ~ 57.6 V
Internal Resistance| ≤ 20 mΩ
Electrical Parameters
Max. Charge current| 50 A
Max. Discharge current| 50 A
Operating Temperature Range| -10 °C ~ 50 °C [1]
Humidity| 15% ~ 85%
System Configuration
Module Connect| 6 Parallels
Capacity Range| 5.4/10.8/16.2/21.6/27/32.4 kWh
Usable Energy Range| 4.8/9.6/14.4/19.2/24/28.8 kWh
Max. Charge Current| 50A (1 Module) / 100A (2~6 Modules)
Max. Discharge Current| 50A (1 Module) / 100A (2~6 Modules)
Monitoring Parameters
| system voltage, current, cell voltage, cell temperature, PCBA temperature
Communication| CAN
Certification| CE, UN38.3
[1] When the temperature is below zero, the battery are not allowed to charge.
When above 40℃, the power output decreased.Technical Data| SECU A5.4-20|
2SECU A5.4-20| 3SECU A5.4-20
---|---|---|---
Usable Energy (kWh)1| 5.4| 10.8| 16.2
Battery Module| SECU A5.4-20
Number of Module| 1| 2| 3
Cell Type| LFP( LiFePO4)
Cell Configuration| 16S1P| 16S2P| 16S3P
Nominal Voltage (V)| 51.2
Operating Voltage Range (V)| 47.5~57.6
Nominal Dis-/Charge Current (A)2| 50| 100
Nominal Power (kW)2| 2.56| 5.12
Short-Circuit Current| 2.323kA@1.0ms
Operating Temperature Range (℃)| Charge: 0 ~ +50 / Discharge: -10 ~ +50
Relative Humidity| 0~95%
Max. Operating Altitude (m)| 2000
Communication| CAN、 RS485
Weight (kg)| 49| 98| 147
Dimensions (W×H×D mm)| 403x227x455 (SECU A5.4-20)
Ingress Protection Rating| IP 20
Storage Temperature (℃)| -20 ~ +40 (≤One Month) / 0 ~ +35 (≤One Year)
Mounting Method| Grounded/ Cabinet
Round-trip Efficiency| 95.0%
Cycle Life3| ≥ 4000 @0.5C/0.5C
Standard and Certification| Safety| IEC62619, IEC63056,CEC
EMC| CE, RCM
Transportation| UN38.3
- Test conditions, 100% DOD, 0.2C charge & discharge at +25±2 °C for battery system at beginning life. System Usable Energy may vary with different Inverter.
- Nominal Dis-/Charge Current and power derating will occur related to Temperature and SOC.
- Based on Cell under 0.5C/0.5C @ 25±2℃ test condition and 80% EOL.
Technical Data | 4*SECU A5.4-20 | 5*SECU A5.4-20 | 6*SECU A5.4-20 |
---|---|---|---|
Usable Energy (kWh)*1 | 21.6 | 27.0 | 32.4 |
Battery Module | SECU A5.4-20 | ||
Number of Module | 4 | 5 | 6 |
Cell Type | LFP( LiFePO4) | ||
Cell Configuration | 16S4P | 16S5P | 16S6P |
Nominal Voltage (V) | 51.2 | ||
Operating Voltage Range (V) | 47.5~57.6 | ||
Nominal Dis-/Charge Current (A)*2 | 50 | 100 | |
Nominal Power (kW)*2 | 2.56 | 5.12 | |
Short-Circuit Current | 2.323kA@1.0ms | ||
Operating Temperature Range (℃) | Charge: 0 ~ +50 / Discharge: -10 ~ +50 | ||
Relative Humidity | 0~95% | ||
Max. Operating Altitude (m) | 2000 | ||
Communication | CAN、 RS485 | ||
Weight (kg) | 196 | 245 | 294 |
Dimensions (W×H×D mm) | 403x227x455 (SECU A5.4-20) | ||
Ingress Protection Rating | IP 20 | ||
Storage Temperature (℃) | -20 ~ +40 (≤One Month) / 0 ~ +35 (≤One Year) | ||
Mounting Method | Grounded/ Cabinet | ||
Round-trip Efficiency | 95.0% | ||
Cycle Life*3 | ≥ 4000 @0.5C/0.5C | ||
Standard and Certification | Safety | IEC62619, IEC63056,CEC | |
EMC | CE, RCM | ||
Transportation | UN38.3 |
- Test conditions, 100% DOD, 0.2C charge & discharge at +25±2 °C for battery system at beginning life. System Usable Energy may vary with different Inverter.
- Nominal Dis-/Charge Current and power derating will occur related to Temperature and SOC.
- Based on Cell under 0.5C/0.5C @ 25±2℃ test condition and 80% EOL.
Safety Instructions
The system has been designed and tested under international safety requirements. However, to prevent personal injury and property damage and ensure long-term operation of the system, do read this section carefully and observe all safety information at all times.
Battery Module Leakage
If the battery modules leak electrolyte, please avoid contact the leaking
liquid or gas. If one is exposed to the leaked substance, do these actions:
Inhalation : Evacuate the contaminated area, and seek for medical help
immediately.
Eye contact : Rinse your eyes with clean water for at least 15
minutes and seek for medical help immediately.
Skin contact : Wash the affected area thoroughly with soap and clean
water, and seek for medical help immediately.
Ingestion : Induce vomiting, and seek for medical help immediately.
Firefighting Measures
- In case of a fire, please make sure that a carbon dioxide extinguisher or Novac1230 or FM-200 is nearby. Water cannot be used to extinguish the fire. (ABC is not effective for this battery firefighting)
- Full protective clothing and self-contained breathing apparatus are required for the firefighters to extinguish the fire.
Warning: Under >150℃ environment, there is possibility that battery could explode
Handling and Storage Guide
- The battery modules and its components shall be protected from damage when it is in transporting and handling
- Please take the weight of the battery module system into account during transportation and battery module shall be lifted carefully
- Do not impact, pull, drag or step on the battery modules, either insert unrelated objects into any part of the battery modules
- The battery module shall be kept away from a fire, water, strong oxidizers or solvents
- The battery modules cannot be stored in high temperature (> 60℃) or stored directly under the sun, or in any high humidity environment.
- Do not use the battery modules if it is defective, or appears cracked, broken.
- Do not attempt to open, disassemble, repair, tamper with, or modify the battery modules without official permission from GoodWe
Warning : battery module damage may lead to electrolyte leakage, please contact technical support immediately
Warning of Electric Shock
It is danger to get electric shock when live components or DC cables are
touched.
Disconnect the battery from voltage source before working on the device. Make
sure of no any manual operation under load. And do not touch non-insulated
parts or cables. And wear suitable protective equipment for all work on the
system.
Warning : If battery is wetted, make sure it is not touched by hand, and contact technical support.
Surge Protection
Over voltages can be further conducted into the building or other connected
devices in the same network via network cables or other cables if there is no
surge protection.
Ensure that the system is integrated into the existing surge protection.
Disclaimer
-
All the information in this document is the property of GoodWe No part of this document could be reproduced in any way for business use. Internal use is allowed.
-
GoodWe makes no representations or warranties express or implied, with respect to this
document or any of the equipment and/or software it may describe, including (with no limitation) any implied warranties of utility, merchantability, or fitness for any particular purpose. All such representations or warranties are expressly disclaimed. Neither GoodWe nor its distributors or dealers shall be liable for any indirect, incidental, or consequential damages under any circumstances. -
The exclusion of implied warranties may not apply in all cases under some statutes, and thus the above exclusion may not apply.
-
Specifications are subject to change without notice. Every effort has been made to make this document complete, accurate and up-to-date. However, GoodWe may need to make some improvements under certain circumstances without advance notice. GoodWe shall not be responsible for any loss caused by this document including, but not limited omissions errors, typographical errors, arithmetical errors or listing errors in this document.