GOODWE DNS Series 36KW Single Phase User Manual
- May 15, 2024
- GOODWE
Table of Contents
- GOODWE DNS Series 36KW Single Phase
- Product Information
- Product Information
- About This Manual
- Safety Precaution
- Product Introduction
- Dimensions
- Check and Storage
- Installation
- Electrical Connection
- Equipment Commissioning
- System Commissioning
- Maintenance
- Troubleshooting
- Technical Parameters
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
GOODWE DNS Series 36KW Single Phase
Product Information
- Specifications
- Product: Grid-Tied PV Inverter
- Model: DNS Series 2.9-6kW
- Version: V1.1-2023-05-30
Product Information
- About This Manual
- This manual provides instructions and guidelines for the usage of the Grid-Tied PV Inverter. It includes important information regarding safety precautions, installation, and electrical connection.
- Safety Precaution
- Before using the Grid-Tied PV Inverter, please read and understand all safety precautions mentioned in the user manual. Failure to follow these precautions may result in electric shock or other hazards.
- Product Introduction
- Application Scenarios
- The Grid-Tied PV Inverter is designed for use in various application scenarios, including residential and commercial solar power systems.
- Supported Grid Types
- The inverter supports different grid types, ensuring compatibility with various utility grid systems.
- Appearance
- The Grid-Tied PV Inverter has a sleek and compact design, allowing for easy installation and integration into existing solar power systems.
- Check and Storage
- Check Before Receiving
- Before receiving the inverter, perform a thorough check to ensure there are no visible damages or defects. If any issues are found, contact the supplier immediately.
- Deliverables
- The package should include the Grid-Tied PV Inverter, installation accessories, and the user manual. Verify that all deliverables are present.
- Storage
- If the inverter is not going to be installed immediately, store it in a cool and dry place, away from direct sunlight and moisture.
- Installation
- Installation Requirements
- Before installation, ensure that all requirements are met, including electrical specifications, mounting location, and safety considerations.
- Inverter Installation
- If required, carefully move the inverter to the desired installation location, ensuring it is handled with care and avoiding any physical damage.
- Installing the Inverter
- Follow the provided installation instructions to securely mount the inverter in the designated location. Ensure proper wiring and connections are made according to electrical regulations.
- Electrical Connection
- Communication Network Introduction
- The inverter supports communication capabilities for monitoring and control purposes. Familiarize yourself with the communication network introduction section for detailed information.
- Connecting the Communication Cable (optional)
- If desired, connect the communication cable to enable remote monitoring and control features. Follow the instructions provided to establish a reliable connection.
- Installing the Communication Module (optional)
- If applicable, install the communication module as per the provided instructions. This module enhances the inverter’s communication capabilities.
- FAQ
- Q: Can I install the inverter outdoors?
- A: The Grid-Tied PV Inverter is designed for both indoor and outdoor installations. However, it is recommended to protect the inverter from extreme weather conditions.
- Q: How often should I perform maintenance on the inverter?
- A: Regular maintenance is essential for optimal performance. Refer to the user manual for specific maintenance intervals and procedures.
- Q: Can I use the inverter with different solar panel types?
- A: The Grid-Tied PV Inverter is compatible with various solar panel types. Ensure that the specifications and electrical characteristics of the panels are within the inverter’s supported range.
About This Manual
- This manual describes the product information, installation, electrical connection, commissioning, troubleshooting, and maintenance.
- Read through this manual before installing and operating the product.
- All the installers and users have to be familiar with the product features, functions, and safety precautions.
- This manual is subject to update without notice. For more product details and latest documents, visit https://en.goodwe.com.
Applicable Model
This manual applies to the listed inverters below (DNS or Inverter for short):
Model | Nominal Output Power | Nominal Output Voltage |
---|---|---|
GW2900D-NS | 2.9kW | 127V |
GW3000D-NS | 3kW | 220/230/240V |
GW3600D-NS | 3.6kW | |
GW4200D-NS | 4.2kW | |
GW5000D-NS | 5kW | |
GW6000D-NS | 6kW | |
GW3000T-DS | 3kW | |
GW3600T-DS | 3.6kW | |
GW4200T-DS | 4.2kW | |
GW5000T-DS | 5kW | |
GW6000T-DS | 6kW | |
GW5KBD-NS | 5kW | |
GW6KBD-NS | 6kW |
Target Audience
This manual applies to trained and knowledgeable technical professionals. The
technical personnel has to be familiar with the product, local standards, and
electric systems.
Symbol Definition
Different levels of warning messages in this manual are defined as follows:
- DANGER
- Indicates a high-level hazard that, if not avoided, will result in death or serious injury.
- WARNING
- Indicates a medium-level hazard that, if not avoided, could result in death or serious injury.
- CAUTION
- Indicates a low-level hazard that, if not avoided, could result in minor or moderate injury.
- NOTICE
- Highlight and supplement the texts. Or some skills and methods to solve product-related problems to save time.
Updates
- The latest document contains all the updates made in earlier issues.
V1.0 2022-12-15
- First Issue
V1.1 2023-05-30
- Update 10 Technical Parameters.
Safety Precaution
Notice
- The inverters are designed and tested strictly complies with related safety rules.
- Read and follow all the safety instructions and cautions before any operations.
- Improper operation might cause personal injury or property damage as the inverters are electrical equipment.
General Safety
Notice
- The information in this user manual is subject to change due to product updates or other reasons. This guide cannot replace the product labels or the safety precautions in the user manual unless otherwise specified. All descriptions here are for guidance only.
- Before installations, read through the quick installation guide. For additional information, please see the user manual.
- All installations should be performed by trained and knowledgeable technicians who are familiar with local standards and safety regulations.
- Use insulating tools and wear personal protective equipment when operating the equipment to ensure personal safety. Wear anti-static gloves, cloths, and wrist strips when touching electronic devices to protect the inverter from damage.
- Strictly follow the installation, operation, and configuration instructions in this manual. The manufacturer shall not be liable for equipment damage or personal injury if you do not follow the instructions. For more warranty details, please visit https://en.goodwe.com/warranty.
DC Side
- DANGER
- Connect the DC cables using the delivered PV connectors. The manufacturer shall not be liable for the equipment damage if other connectors or terminals are used.
- WARNING
- Ensure the component frames and the bracket system are securely grounded.
- Ensure the DC cables are connected tightly, securely, and correctly.
- Measure the DC cable using the multimeter to avoid a reverse polarity connection. Also, the voltage should be under the permissible range.
AC Side
- WARNING
- The voltage and frequency at the connection point meet the inverter grid connection requirements
- Additional protective devices like circuit breakers or fuses are recommended on the AC side. Specification of the protective device should be at least 1.25 times the rated AC output rated current.
- Make sure that all the groundings are tightly connected.
- You are recommended to use copper cables as AC output cables. Contact the manufacturer if you want to use other cables.
Inverter Installation
- DANGER
- Do not apply mechanical load to the terminals, otherwise the terminals can be damaged.
- All labels and warning marks should be visible after the installation. Do not scrawl, damage, or cover any label on the device.
- Inverters shall not be used in multiple inverter combinations for AS/NZS 4777.2:2020.
- Warning labels on the inverter are as follows.
Personal Requirements
NOTICE
- Personnel who install or maintain the equipment must be strictly trained, learn about safety precautions and correct operations.
- Only qualified professionals or trained personnel are allowed to install, operate, maintain, and replace the equipment or parts.
EU Declaration of Conformity
GoodWe Technologies Co., Ltd. hereby declares that the inverter with wireless communication modules sold in the European market meets the requirements of the following directives:
- Radio Equipment Directive 2014/53/EU (RED)
- Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS)
- Waste Electrical and Electronic Equipment 2012/19/EU
- Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No 1907/2006 (REACH)
GoodWe Technologies Co., Ltd. hereby declares that the inverter without wireless communication modules sold in the European market meets the requirements of the following directives:
- Electromagnetic Compatibility Directive 2014/30/EU (EMC)
- Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD)
- Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS)
- Waste Electrical and Electronic Equipment 2012/19/EU
- Registration, Evaluation, Authorization, and Restriction of Chemicals (EC) No 1907/2006 (REACH) You can download the EU Declaration of Conformity at https://en.goodwe.com.
Product Introduction
Application Scenarios
The DNS inverter is a single-phase PV string grid-tied inverter. The inverter
converts the DC power generated by the PV module into AC power and feeds it
into the utility grid. The intended use of the inverter is as follows:
Supported Grid Types
For the grid type with neutral wire, the N-to-ground voltage must be less than
10V.
Appearance Parts
No. | Parts | Description |
---|---|---|
1 | PV Input Terminal | Used to connect the PV module DC input cables. |
2 | DC Switch | Start or stop DC input. |
3 | DC Switch Lock | Only for Australia. Turn the DC switch to OFF and lock it |
to avoid electric shock when you have to work on the inverter.
4| WiFi/4G/LAN/GPRS Communication Module Port or RS485 Communication Cable
Port| • Connect a communication module like WiFi, LAN, GPRS, 4G, etc. The
module type may differ depending on actual needs.
• Connect the RS485 Communication Cable.
• Update the software version of the inverter using
a USB flash driver.
5| DRED/CT/Remote Shutdown Communication Cable Port| Used to connect the DRED
or remote shutdown communication cable.
6| AC Output Terminal| Used to connect the AC output cable, which connects
the inverter and the utility grid.
7| Indicator| Indicates the working state of the inverter.
8| LCD| Used to check the parameters of the inverter.
9| Button| Used to select menus displayed on the screen.
10| PE Terminal| Used to connect the PE cable.
11| Mounting Plate| Used to install the inverter.
12| Heat Sink| Used to cool the inverter.
Dimensions
Indicators
Nameplate
The nameplate is for reference only.
Check and Storage
Check Before Receiving
Check the following items before receiving the product.
- Check the outer packing box for damage, such as holes, cracks, deformation, and other signs of equipment damage. Do not unpack the package and contact the supplier as soon as possible if any damage is found.
- Check the inverter model. If the inverter model is not what you requested, do not unpack the product and contact the supplier.
- Check the deliverables for correct model, complete contents, and intact appearance. Contact the supplier as soon as possible if any damage is found.
Deliverables
- Notice
- Number of expansion bolts, spare screws, and 2PIN terminals are various depending on the different inverters. The actual accessories may differ.
- Communication module types: WiFi, LAN, GPRS, 4G, etc. The actual module delivered depends on the communication method of the selected inverter.
- 2PIN terminal is used to connect CT communication cable.
Storage
If the equipment is not to be installed or used immediately, please ensure
that the storage environment meets the following requirements:
- Do not unpack the outer package or throw the desiccant away.
- Store the equipment in a clean place. Make sure the temperature and humidity are appropriate and no condensation.
- The height and direction of the stacking inverters should follow the instructions on the packing box.
- The inverters must be stacked with caution to prevent them from falling.
- If the inverter has been long-term stored, it should be checked by professionals before being put into use.
Installation
Installation Requirements
Installation Environment Requirements
- Do not install the equipment in a place near flammable, explosive, or corrosive materials.
- Install the equipment on a surface that is solid enough to bear the inverter weight.
- Install the equipment in a well-ventilated place to ensure good dissipation. Also, the installation space should be large enough for operations.
- The equipment with a high ingress protection rating can be installed indoors or outdoors. The temperature and humidity at the installation site should be within the appropriate range.
- Install the equipment in a sheltered place to avoid direct sunlight, rain, and snow. Build a sunshade if it is needed.
- Do not install the equipment in a place that is easy to touch, especially within children’s reach. High temperature exists when the equipment is working. Do not touch the surface to avoid burning.
- Install the equipment at a height that is convenient for operation and maintenance, electrical connections, and checking indicators and labels.
- The altitude to install the inverter shall be lower than the maximum working altitude of 4000m(3000m for Australia).
- The inverter is easy to be corroded when installed in salt areas. Please consult the inverter manufacturer before installing it outdoors in salt areas. A salt area refers to the region within 1000m offshore or affected by the sea breeze. The area prone to the sea breeze varies depending on weather conditions (e.g. typhoons, monsoons) or terrain (such as dams and hills).
- Install the inverter away from a high magnetic field to avoid electromagnetic interference. If there is any radio or wireless communication equipment below 30MHz near the inverter, you have to:
- Install the inverter at least 30m far away from the wireless equipment.
- Add a low-pass EMI filter or a multi-winding ferrite core to the DC input cable or AC output cable of the inverter.
Mounting Support Requirements
- The mounting support shall be nonflammable and fireproof.
- Make sure that the support surface is solid enough to bear the product weight load.
- Do not install the product on the support with poor sound insulation to avoid the noise generated by the working product, which may annoy the residents nearby.
Installation Angle Requirements
- Install the inverter vertically or at a maximum back tilt of 15 degrees.
- Do not install the inverter upside down, forward tilt, back forward tilt, or horizontally.
Installation Tool Requirements
The following tools are recommended when installing the equipment. Use other auxiliary tools on site if necessary.
Inverter Installation Moving the Inverter
CAUTION
Move the inverter to the site before installation. Follow the instructions below to avoid personal injury or equipment damage.
- Consider the weight of the equipment before moving it. Assign enough personnel to move the equipment to avoid personal injury.
- Wear safety gloves to avoid personal injury.
- Keep balance to avoid falling down when moving the equipment.
Installing the Inverter
NOTICE: Avoid the water pipes and cables buried in the wall when drilling holes. Wear goggles and a dust mask to prevent the dust from being inhaled or contacting eyes when drilling holes. The DC switch lock is prepared by the customer.
- Step 1 Put the mounting plate on the wall or the support horizontally and mark positions for drilling holes.
- Step 2 Drill holes to a depth of 80mm using the hammer drill. The diameter of the drill bit should be 10mm.
- Step 3 Secure the mounting plate using the expansion bolts.
- Step 4 (Only for Australia.) Install the DC switch lock.
- Step 5-6 Install the inverter on the mounting plate.
- Step 7 Install the anti-theft lock.
Electrical Connection
Safety Precaution
- DANGER
- Disconnect the DC switch and the AC output switch of the inverter to power off the inverter before any electrical connections. Do not work with power on. Otherwise, an electric shock may occur.
- Perform electrical connections in compliance with local laws and regulations. Including operations, cables, and component specifications.
- If the cable bears too much tension, the connection may be poor. Reserve a certain length of the cable before connecting it to the inverter cable port.
- NOTICE
- Wear personal protective equipment like safety shoes, safety gloves, and insulating gloves during electrical connections.
- All electrical connections should be performed by qualified professionals.
- Cable colors in this document are for reference only. The cable specifications shall meet local laws and regulations.
Connecting the PE Cable
- WARNING
- The PE cable connected to the enclosure of the inverter cannot replace the PE cable connected to the AC output port. Make sure that both of the two PE cables are securely connected.
- Make sure that all the grounding points on the enclosures are equipotential connected when there are multiple inverters.
- To improve the corrosion resistance of the terminal, you are recommended to apply silica gel or paint on the ground terminal after installing the PE cable.
- The PE cable is prepared by the customer. Recommended specifications:
- Type: single-core outdoor copper cable
- Conductor cross-sectional area: ≥4mm2
Connecting the PV Input Cable
DANGER: Confirm the following information before connecting the PV string to the inverter. Otherwise, the inverter may be damaged permanently or even cause fire and cause personal and property losses.
- Make sure that the max short circuit current and the max input voltage per MPPT are within the permissible range.
- Make sure that the positive pole of the PV string connects to the PV+ of the inverter. And the negative pole of the PV string connects to the PV- of the inverter.
WARNING
- Connect the DC cables using the delivered PV connectors. The manufacturer shall not be liable for the damage if other connectors are used.
- The PV strings cannot be grounded. Ensure the minimum isolation resistance of the PV string to the ground meets the minimum isolation resistance requirements before connecting the PV string to the inverter.
- The DC input cable is prepared by the customer. Recommended specifications:
- Type: the outdoor photovoltaic cable that meets the maximum input voltage of the inverter.
- Conductor cross-sectional area: 2.5~4mm2 (Devalan) or 4~6mm2 (MC4).(MC4)
NOTICE: Seal the PV input terminals using waterproof covers when they are not to be used. Otherwise, the ingress protection rating will be influenced.
Connecting the DC Input Cable
- Step 1 Prepare DC cables.
- Step 2 Crimp the crimp contacts.
- Step 3 Disassemble the PV connectors.
- Step 4 Make the DC cable and detect the DC input voltage. Step 5 Plug the PV connectors into the PV terminals.
Devalan PV connector
Connecting the AC Output Cable
- WARNING
- Do not connect loads between the inverter and the AC switch directly connected to the inverter.
- The Residual Current Monitoring Unit (RCMU) is integrated into the inverter.
- The inverter will disconnect the utility grid rapidly once it detects any leak current over the permissible range.
An AC circuit breaker shall be installed on the AC side to make sure that the inverter can safely disconnect the grid when an exception happens. Select the appropriate AC circuit breaker in compliance with local laws and regulations. Recommended AC circuit breakers:
Inverter model | AC circuit breaker |
---|---|
GW2900D-NS | 30A |
GW3000D-NS | 20A |
GW3600D-NS
GW4200D-NS| 25A
GW5000D-NS| 30A
GW6000D-NS| 35A
GW3000T-DS|
20A
GW3600T-DS
GW4200T-DS| 25A
GW5000T-DS| 30A
GW6000T-DS| 35A
GW5KBD-NS| 30A
GW6KBD-NS| 35A
Select and Install RCD depending on local laws and regulations.Type A RCDs (Residual Current Monitoring Device) can be connected to the outside of the inverter for protection when the DC component of the leakage current exceeds the limit value. The following RCDs are for reference:
Model | RCD specifications |
---|---|
GW2900D-NS |
300mA
GW3000D-NS
GW3600D-NS
GW4200D-NS
GW5000D-NS
GW6000D-NS
GW3000T-DS
GW3600T-DS
GW4200T-DS
GW5000T-DS
GW6000T-DS
GW5KBD-NS
GW6KBD-NS
NOTICE
- Install one AC circuit breaker for each inverter. Multiple inverters cannot share one AC circuit breaker.
WARNING
- Pay attention to the silkscreens L, N, PE on the AC terminal. Connect the AC cables to the corresponding terminals. The inverter may be damaged if the cables are connected inappropriately.
- Make sure that the whole cable cores are inserted into the AC terminal holes. No part of the cable core can be exposed.
- Make sure that the cables are connected securely. Otherwise, the terminal may be too hot to damage the inverter when the inverter is working.
- Step 1 Make the AC output cable.
- Step 2 Disassemble the AC connector.
- Step 3 Insert the AC output cable into the AC connector. Step 4 Plut the AC connector into the inverter.
AC-1 Connector
AC-2 Connector
AC-3 Connector
NOTICE
- Make sure that the cable is connected correctly and securely. Clear the debris after completing the connection.
- Seal the AC output terminal to ensure the ingress protection rating.
Communication Communication Network Introduction
- Power Limit Network
- The PV station generates power for self-consumption, but the electric equipment cannot consume all the generated power.
- The inverter can monitor the on-grid electric data in real time and adjust the output power via a smart meter to avoid the residual current feeding back to the utility grid.
Notice
- After completing cable connections, set related parameters via LCD or SolarGo app to enable export power limit control or output power limit control.
Connecting the Communication Cable (optional)
Notice
- Make sure that the communication device is connected to the right terminal. Route the communication cable far away from any interference source or power cable to prevent the signal from being influenced.
- Connect the CT cable using a 2PIN communication terminal.
- Connect the DRED cable, RS485 cable, and remote shutdown cable using a 6PIN communication terminal.
- DRED (Demand response enabling device) is only for Australian and New Zealand installations, in compliance with Australian and New Zealand safety requirements.
- Contact the after-sales service to get the DRED terminal if you need to use the DRED function.
- DRED function is off by default. Start this function via the SolarGo App if it’s needed.
- Remote shutdown is only for Europe installations, in compliance with European safety requirements. A remote shutdown device is not provided by GOODWE.
- The remote shutdown function is off by default. Start this function via the SolarGo App if it’s needed.
DRED/Remote Shutdown Communication Cable
- DRED: Australia
- Remote Shutdown: Europe
CT Communication Cable
RS485 Communication Cable
Installing the Communication Module (optional)
Plug a communication module into the inverter to establish a connection
between the inverter and the smartphone or web pages. The communication module
can be a WiFi module, LAN module, GPRS moduel, or 4G module. Set inverter
parameters, check running information and fault information, and observe
system status in time via the smartphone or web pages.
WiFi kit, LAN kit, 4G kit, GPRS module: optional.
Notice
- Refer to the delivered communication module user manual to get more introduction to the module. For more detailed information, visit https://en.goodwe.com.
Equipment Commissioning
Check Before Power ON
No. | Check Item |
---|---|
1 | The product is firmly installed at a clean place that is well-ventilated |
and easy to operate.
2| The PE, DC input, AC output, and communication cables are connected
correctly and securely.
3| Cable ties are intact, routed properly and evenly.
4| Unused ports and terminals are sealed.
5| The voltage and frequency at the connection point meet the inverter grid
connection requirements.
Power On
- Step 1 Turn on the AC switch between the inverter and the utility grid.
- Step 2 (optional) Turn on the DC switch between the inverter and the PV string. Step 3 Turn on the DC switch of the inverter.
System Commissioning
Indicators and Buttons
Setting Inverter Parameters via LCD
- NOTICE
- Inverter software version shown in this document is V1.00.00.13. The screenshots are for reference only. The actual interface may differ.
- The name, range, and default value of the parameters are subject to change or adjustment. The actual display prevails.
- To prevent the generating capacity from being influenced by wrong parameters, the power parameters should be set by professionals.
LCD Button Description
- This part describes the menu structure, allowing you view inverter information and set parameters more conveniently.
Inverter Parameter Introduction
Parameters | Description |
---|---|
Normal | Home page. Indicates the real-time power of the inverter. Long press |
for 2s to check the current safety code.
E-Today| Check the generated power of the system for that day.
E-Total| Check the total generated power of the system.
Vpv| Check the DC input voltage of the inverter.
Ipv| Check the DC input current of the inverter.
Vac| Check the voltage of the utility grid.
Iac| Check the AC output current of the inverter.
Fac| Check the frequency of the utility grid.
Error History| Check historical error message records of the inverter.
Model| Indicates the specific inverter model. Long press for 2s to set the
safety code. Set the safety country in compliance with the local grid
standards and application scenario of the inverter.
Ver| Check the software version.
Set Language| Set language accordingly. Languages: English, Portuguese,
Spanish.
Set Time| Set time according to the actual time in the country/region where
the inverter is located.
W/L Reset| Power off and restart the WiFi module.
W/L Reload| Restore the factory settings of the WiFi module. Reconfigure the
WiFi module network parameters after restoring the factory settings,
PF Adjust| Set the power factor of the inverter according to actual situation.
Shadow MPPT| Enable the shadow scan function if the PV panels are shadowed.
Power Limit| Soft limit : Set the power feed into the utility grid
according to local requirements and standards.
Hard limit : The inverter and the utility grid will automatically
disconnect when the power feeds into the grid excesses the required limit.
Set Power Limit| Set the power feed back into the utility grid according to
the actual situation.
Set Modbus Addr| Set the actual Modbus address.
LVRT| With LVRT on, the inverter will stay connected with the utility grid
when a short-term utility grid low voltage exception occurs.
HVRT| With HVRT on, the inverter will stay connected with the utility grid
when a short-term utility grid high voltage exception occurs.
Set Start time| Set the time for the inverter to connect with the grid.
Auto-Test
- The auto-test function is disabled by default and is available in Italy only.
- Short press the button until LCDs “Auto Test”, and long press the button to start this function.
- if the auto test is finished, short press the button until LCDs “Auto Test Result”, and long press
- Choose the auto test type between “Remote” and “Local” before starting the test. Under “Remote” mode, the default setting is 1 and cannot be modified. Under “Local” mode, the default setting is 0 and can be set to 0 or 1 by calibrating the software. If it is 1 under “Local” mode, the testing order will be 59.S1, 59.S2, 27.S1, 81>S1, 81<S1. Otherwise, the testing order will be 59.S1, 59.S2, 27.S1, 81>S2, 81<S2.
- Connect AC, then the auto test will start after the inverter relay breaks off successfully: output power is zero and LCD shows the information about testing.
- If sub test finishes and LCDs “Test ***** Ok”, the inverter relay will turn off and reconnect to the grid automatically according to CEI 0-21 requirements. Then the next test starts.
If the test fails, the inverter relay breaks off and enters wait mode. To
retry, the inverter needs to be powered off and be restarted.
Upgrading the Firmware Via USB Flash Disk
- Step 1 Contact the after-sales service to obtain the upgrade package.
- Step 2 Save the upgrade package on the USB flash drive.
- Step 3 Insert the USB flash drive into the USB port, and upgrade the software version of the inverter following the prompts.
Setting Inverter Parameters via the SolarGo App
- SolarGo app is a mobile application that communicates with the inverter via Bluetooth module, wifi module, or GPRS module. Commonly used functions are as follows:
- Check the operating data, software version, alarms, etc.
- Set grid parameters, communication parameters, etc.
- Equipment maintenance.
For more details, refer to the SolarGo APP User Manual. Scan the QR code or visit https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_SolarGo_User %20Manual-EN.pdf to get the user manual.
Monitoring via SEMS Portal
- SEMS Portal is an monitoring platform used to manage organizations/users, add plants, and monitor plant status.
- For more details, refer to the SEMS Portal User Manual. Scan the QR code or visit https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_SEMS%20Portal-User%20Manual-EN.pdf to get the user manual.
Maintenance
Power Off the Inverter
- DANGER
- Power off the inverter before operations and maintenance. Otherwise, the inverter may be damaged or electric shocks may occur.
- Delayed discharge. Wait until the components are discharged after power off.
- Step 1 (optional) Send shutdown command to the inverter.
- Step 2 Turn off the AC switch between the inverter and the utility grid. Step 3 Turn off the DC switch of the inverter.
Removing the Inverter
WARNING: Make sure that the inverter is powered off. Wear proper PPE before any operations.
- Step 1 Disconnect all the cables, including DC cables, AC cables, communication cables, the communication module, and PE cables.
- Step 2 Grab the handles or hoist the inveter to remove the inverter from the mounting plate. Step 3 Remove the mounting plate.
- Step 4 Store the inverter properly. If the inverter needs to be used later, ensure that the storage conditions meet the requirements.
Disposing of the Inverter
- If the inverter cannot work anymore, dispose of it according to the local disposal requirements for electrical equipment waste. The inverter cannot be disposed of together with household waste.
Troubleshooting
- Perform troubleshooting according to the following methods. Contact the after-sales service if these methods do not work.
- Collect the information below before contacting the after-sales service, so that the problems can be solved quickly.
- Inverter information like serial number, software version, installation date, fault time, fault frequency, etc.
- Installation environment, including weather conditions, whether the PV modules are sheltered or shadowed, etc. It is recommended to provide some photos and videos to assist in analyzing the problem.
- Utility grid situation.
Fault | Troubleshooting |
---|
System Failure
|
Isolation Failure
| 1. Check the impedance between the ground and PV (+) & PV (-)
. The impedance value must be greater than 100kΩ. Make sure
the inverter is grounded.
2. Contact local service office for help if the problem still persist.
Inverters for the Australian and New Zealand markets can also be alerted in the following ways in the event of insulation impedance failure:
1. The inverter is equipped with the buzzer: the buzzer sounds continuously for 1 minute in case of failure; If the fault is not resolved, the buzzer sounds every 30 minutes.
2. Add the inverter to the monitoring platform, and set the alarm reminder, the alarm information can be sent to the customer by emails.
Ground I Failure
| 1. The ground current is too high.
2. Unplug the inputs from the PV generator and check the
peripheral AC system.
3. When the problem is solved, reconnect the PV panel and check the Inverter status.
4. Contact local service office for help if the problem still persist.
Vac Failure
| 1. The PV Inverter will automatically restart within 5 minutes if the grid returns to normal.
2. Make sure grid voltage conforms with the specification.
3. Make sure neutral (N) wire and PE cable are connected well.
4. Contact local service office for help if the problem still persist.
Fac Failure
| 1. Not connected to the grid.
2. Check if the power grid is connected to cable.
3. Check the availability of power grid.
Utility Loss
| 1. Not connected to the grid.
2. Check if the power grid is connected to cable.
3. Check the availability of power grid.
PV Over Voltage
| 1. Check if the PV open circuit voltage is higher than or too close to the maximum input voltage.
2. If the problem still persist when PV voltage is less than the
maximum input voltage, contact local service office for help.
Over Temperature
| 1. The internal temperature is higher than normal.
2. Decrease ambient temperature.
3. Move the inverter to a cool place.
4. If the problem still exists, contact local service office for help.
Inverter Failure
| Relay-Check Failure|
1. Turn off DC switch of the inverter.
2. Wait till the LCD light is off.
3. Turn on the DC switch and make sure it is connected.
4. If the problem still exists, contact local service office for help.
---|---|---
DCI Injection High
EEPROM R/W
Failure
SPI Failure
DC BUS High
GFCI Failure
Others
|
No display
| 1. Turn off the DC switch and unplug the DC connector, then
measure the voltage of the PV array.
2. Plug in the DC connector, and turn on the DC switch.
3. If PV array voltage is lower than 250V , please check
configuration of inverter module.
4. If voltage is higher than 250V , please contact local service
office for help.
AFCI-Fault
| 1. Turn off the DC switch of the inverter.
2. Ensure the DC connector is the right model and is properly connected.
3. Turn on the DC switch and make sure it is connected.
4. If the problem still exists, contact local service office for help.
Routine Maintenance
Maintaining Item | Maintaining Method | Maintaining Period |
---|---|---|
System Clean | Check the heat sink, air intake, and air outlet for foreign | |
matter or dust. | Once 6-12 months |
DC Switch
| Turn the DC switch on and off ten consecutive times to make sure that it is working properly.| ****
Once a year
Electrical Connection
| Check whether the cables are securely connected. Check whether the cables are broken or whether there is any exposed copper core.| ****
Once 6-12 months
Sealing
| Check whether all the terminals and ports are properly sealed. Reseal the cable hole if it is not sealed or too big.| ****
Once a year
Technical Parameters
Technical Data| GW2900D- NS| GW3000D- NS|
GW3600D- NS| GW4200D- NS| GW5000D- NS| GW6000D-
NS
---|---|---|---|---|---|---
Input
Max. Input Power (W)18| 4000| 3900| 4680| 5460| 6500| 7200
Max. Input Voltage (V)| 535| 600| 600| 600| 600| 600
MPPT Operating Voltage
Range (V)
|
80 – 435
|
80 – 550
|
80 – 550
|
80 – 550
|
80 – 550
|
80 – 550
MPPT Voltage Range at
Nominal Power (V)
|
N/A
|
150 – 550
|
180 – 550
|
210 – 550
|
240 – 550
|
280 – 550
Start-up Voltage (V)| 80| 80| 80| 80| 80| 80
Nominal Input Voltage (V)|
230
|
360
|
360
|
360
|
360
|
360
Max. Input Current per MPPT (A)|
12.5
|
11
|
11
|
11
|
11
|
11
Max. Short Circuit Current per MPPT (A)|
15.6
|
13.8
|
13.8
|
13.8
|
13.8
|
13.8
Max. Backfeed Current to The Array (A)|
0
|
0
|
0
|
0
|
0
|
0
Number of MPPT| 2| 2| 2| 2| 2| 2
Number of Strings per
MPPT
|
1
|
1
|
1
|
1
|
1
|
1
Output
Nominal Output Power (W)23|
2900
|
3000
|
3680
|
4200
|
5000
|
6000
Nominal Output
Apparent Power (VA)*4
|
2900
|
3000
|
3680
|
4200
|
5000
|
6000
Max. AC Active Power
(W)*7
|
2900
|
3000
|
3680
|
4200
|
5000
|
6000
Max. AC Apparent Power (VA)*7|
2900
|
3000
|
3680
|
4200
|
5000
|
6000
Nominal Power at 40℃
(W)(For Brazil only)
|
2900
|
3000
|
3680
|
4200
|
5000
|
6000
Max Power at 40℃ (Including AC Overload) (W)(For Brazil only)|
2900
|
3000
|
3680
|
4200
|
5000
|
6000
Nominal Output Voltage (V)|
127
|
220/230
|
220/230
|
220/230
|
220/230
|
220/230
Nominal AC Grid
Frequency (Hz)
|
60
|
50/60
|
50/60
|
50/60
|
50/60
|
50/60
Max. Output Current (A)| 22.9| 13.6| 16.0| 19.0| 22.8| 27.3
Nominal Output Current
(A)
|
22.9
|
13.6/13.0
|
16.0/15.6
|
19.0/18.2
|
22.8/21.7
|
27.3/26.1
Power Factor| ~1 (Adjustable from 0.8 leading to 0.8 lagging)
Max. Total Harmonic
Distortion
|
<3%
|
<3%
|
<3%
|
<3%
|
<3%
|
<3%
Maximum Output Overcurrent Protection (A)|
42
|
42
|
42
|
42
|
42
|
50
---|---|---|---|---|---|---
Efficiency
Max. Efficiency| 96.0%| 97.8%| 97.8%| 97.8%| 97.8%| 97.8%
European Efficiency| 95.6%| 97.5%| 97.5%| 97.5%| 97.5%| 97.5%
Protection
PV Insulation Resistance Detection|
Integrated
Residual Current
Monitoring
|
Integrated
PV Reverse Polarity Protection|
Integrated
Anti-islanding Protection| Integrated
AC Overcurrent
Protection
|
Integrated
AC Short Circuit
Protection
|
Integrated
AC Overvoltage
Protection
|
Integrated
DC Switch| Optional
DC Surge Protection| Type III(Type II Optional)|
Type III
|
Type III
|
Type III
|
Type III
|
Type III
AC Surge Protection| Type III
Emergency Power Off| Optional
Remote Shutdown| Optional
General Data
Operating Temperature
Range (℃)
|
-25 – +60
Relative Humidity| 0 – 100%
Max. Operating Altitude
(m)*5
|
4000
Cooling Method| Natural Convection
User Interface| LED,LCD, WLAN+APP
Communication| WiFi,RS485 or 4G or 2G or LAN (Optional)
Weight (kg)| 13.0| 13.0| 13.0| 13.0| 13.0| 13.5
Dimension (W×H×D mm)| 354 × 433 × 147
Noise Emission (dB)| < 25| < 25| < 25| < 25| < 25| < 50
Topology| Non-isolated
Self-consumption at Night (W)|
<1
Ingress Protection Rating|
IP65
Anti-corrosion Class | C4 |
---|---|
DC Connector | MC4 |
AC Connector | Plug and play connector |
Environmental Category | 4K4H |
Pollution Degree | III |
Overvoltage Category | DC II / AC III |
Protective Class | I |
The Decisive Voltage Class (DVC) |
PV: C AC: C Com: A
Active Anti-islanding Method|
AFDPF + AQDPF *6
Country of Manufacture (For Australia only)|
China
Technical Data| GW3000T- DS| GW3600T- DS|
GW4200T- DS| GW5000T- DS| GW6000T- DS
---|---|---|---|---|---
Input
Max. Input Power (W)18| 3900| 4680| 5460| 6500| 7200
Max. Input Voltage (V)| 600| 600| 600| 600| 600
MPPT Operating Voltage Range
(V)
|
80 – 550
|
80 – 550
|
80 – 550
|
80 – 550
|
80 – 550
MPPT Voltage Range at Nominal
Power (V)
|
130 – 550
|
150 – 550
|
170 – 550
|
200 – 550
|
240 – 550
Start-up Voltage (V)| 80| 80| 80| 80| 80
Nominal Input Voltage (V)| 360| 360| 360| 360| 360
Max. Input Current per MPPT (A)| 13| 13| 13| 13| 13
Max. Short Circuit Current per MPPT (A)|
16.3
|
16.3
|
16.3
|
16.3
|
16.3
Max. Backfeed Current to The Array (A)|
0
|
0
|
0
|
0
|
0
Number of MPP Trackers| 2| 2| 2| 2| 2
Number of Strings per MPPT| 1| 1| 1| 1| 1
Output
Nominal Output Power (W)23| 3000| 3680| 4200| 5000| 6000
Nominal Output Apparent Power (VA)*4|
3000
|
3680
|
4200
|
5000
|
6000
Max. AC Active Power (W)7| 3000| 3680| 4200| 5000| 6000
Max. AC Apparent Power (VA)7| 3000| 3680| 4200| 5000| 6000
Nominal Power at 40℃ (W)(For
Brazil only)
|
3000
|
3680
|
4200
|
5000
|
6000
Max Power at 40℃ (including AC
overload)(W)(For Brazil only)
|
3000
|
3680
|
4200
|
5000
|
6000
---|---|---|---|---|---
Nominal Output Voltage (V)| 220/230| 220/230| 220/230| 220/230| 220/230
Nominal AC Grid Frequency (Hz)| 50/60| 50/60| 50/60| 50/60| 50/60
Max. Output Current (A)| 13.6| 16.0| 19.0| 22.8| 27.3
Max. Output Fault Current (Peak and Duration) (A)|
35
|
35
|
35
|
35
|
35
Inrush Current (Peak and
Duration) (A)
|
60
|
60
|
60
|
60
|
80
Nominal Output Current (A)| 13.6/13.0| 16.0/15.6| 19.0/18.2| 22.8/21.7|
27.3/26.1
Power Factor| ~1 (Adjustable from 0.8 leading to 0.8 lagging)
Max. Total Harmonic Distortion| <3%| <3%| <3%| <3%| <3%
Maximum Output Overcurrent Protection (A)|
42
|
42
|
42
|
42
|
50
Efficiency
Max. Efficiency| 97.8%| 97.8%| 97.8%| 97.8%| 97.8%
European Efficiency| 97.5%| 97.5%| 97.5%| 97.5%| 97.5%
Protection
PV String Current Monitoring| Integrated
PV Insulation Resistance Detection|
Integrated
Residual Current Monitoring| Integrated
PV Reverse Polarity Protection| Integrated
Anti-islanding Protection| Integrated
AC Overcurrent Protection| Integrated
AC Short Circuit Protection| Integrated
AC Overvoltage Protection| Integrated
DC Switch| Optional
DC Surge Protection| Type III(Type II Optional)
AC Surge Protection| Type III
AFCI| Optional
Emergency Power Off| Optional
Remote Shutdown| Optional
General Data
Operating Temperature Range
(℃)
|
-25 – +60
Relative Humidity| 0 – 100%
Max. Operating Altitude (m)5| 4000
Cooling Method| Natural Convection
User Interface| LED, LCD, WLAN+APP
---|---
Communication| WiFi, RS485 or 4G or 2G or LAN (Optional)
Weight (kg)| 13| 13| 13| 13| 13.5
Dimension (W×H×D mm)| 354 × 433 × 147
Noise Emission (dB)| < 25| < 25| < 25| < 25| < 50
Topology| Non-isolated
Self-consumption at Night (W)| <1
Ingress Protection Rating| IP65
Anti-corrosion Class| C4
DC Connector| MC4
AC Connector| Plug and play connector
Environmental Category| 4K4H
Pollution Degree| III
Overvoltage Category| DC II / AC III
Protective Class| I
The Decisive Voltage Class (DVC)| PV: C AC: C Com: A
Active Anti-islanding Method| AFDPF + AQDPF 6
Country of Manufacture (For Australia only)|
China
Technical Data | GW5KBD- NS | GW6KBD- NS |
---|
Input
Max. Input Power (W)18| 6500| 7200
Max. Input Voltage (V)| 600| 600
MPPT Operating Voltage Range (V)| 80 – 550| 80 – 550
MPPT Voltage Range at Nominal Power (V)| 200 – 550| 240 – 550
Start-up Voltage (V)| 80| 80
Nominal Input Voltage (V)| 360| 360
Max. Input Current per MPPT (A)| 13| 13
Max. Short Circuit Current per MPPT (A)| 16.3| 16.3
Max. Backfeed Current to The Array (A)| 0| 0
Number of MPP Trackers| 2| 2
Number of Strings per MPPT| 1| 1
Output
Nominal Output Power (W)23| 5000| 6000
Nominal Output Apparent Power (VA)4| 5000| 6000
---|---|---
Max. AC Active Power (W)7| 5000| 6000
Max. AC Apparent Power (VA)*7| 5000| 6000
Nominal Power at 40℃ (W)(For Brazil only)| 5000| 6000
Max Power at 40℃ (including AC overload)(W)(For
Brazil only)
|
5000
|
6000
Nominal Output Voltage (V)| 220| 220
Nominal AC Grid Frequency (Hz)| 60| 60
Max. Output Current (A)| 22.8| 27.3
Max. Output Fault Current (Peak and Duration) (A)| 35| 35
Inrush Current (Peak and Duration) (A)| 60| 80
Nominal Output Current (A)| 22.7| 27.3
Power Factor| ~1 (Adjustable from 0.8 leading to 0.8 lagging)
Max. Total Harmonic Distortion| <3%| <3%
Maximum Output Overcurrent Protection (A)| 42| 50
Efficiency
Max. Efficiency| 97.8%| 97.8%
European Efficiency| 97.5%| 97.5%
Protection
PV String Current Monitoring| Integrated
PV Insulation Resistance Detection| Integrated
Residual Current Monitoring| Integrated
PV Reverse Polarity Protection| Integrated
Anti-islanding Protection| Integrated
AC Overcurrent Protection| Integrated
AC Short Circuit Protection| Integrated
AC Overvoltage Protection| Integrated
DC Switch| Optional
DC Surge Protection| Type III
AC Surge Protection| Type III
AFCI| Optional
Remote Shutdown| Optional
General Data
Operating Temperature Range (℃)| -25 – +60
Relative Humidity| 0 – 100%
Max. Operating Altitude (m)5| 4000
Cooling Method| Natural Convection
---|---
User Interface| LED, LCD, WLAN+APP
Communication| WiFi, RS485 or 4G or 2G or LAN (Optional)
Weight (kg)| 13.0| 13.5
Dimension (W×H×D mm)| 354 × 433 × 147
Noise Emission (dB)| < 25| < 50
Topology| Non-isolated
Self-consumption at Night (W)| <1
Ingress Protection Rating| IP65
Anti-corrosion Class| C4
DC Connector| MC4
AC Connector| Plug and play connector
Environmental Category| 4K4H
Pollution Degree| III
Overvoltage Category| DC II / AC III
Protective Class| I
The Decisive Voltage Class (DVC)| PV: C AC: C Com: A
Active Anti-islanding Method| AFDPF + AQDPF 6
Country of Manufacture (For Australia only)| China
- For Australia or New Zealand Max. Input Power (W) GW3000D-NS or GW3000T-DS is 4000, GW3600D-NS or GW3600T-DS is 4800, GW4200D-NS or GW4200T-DS is 5600, GW5000D-NS or GW5000T-DS is 6667
- For CEI 0-21 Nominal Output Power GW3000T-DS or GW3000D-NS is 2700, GW3600T-DS or GW3600D-NS is 3350, GW4200T-DS or GW4200D-NS is 3800, GW5000T-DS or GW5000D-NS is 4540, GW6000T-DS or GW6000D-NS is 5450
- For Australia or New Zealand Nominal Output Power (W) GW5000D-NS is 4999
- For Australia or New Zealand Nominal Output Apparent Power (VA) GW5000D-NS is 4999
- For Australia Max. Operating Altitude (m) is 3000
- AFDPF: Active Frequency Drift with Positive Feedback, AQDPF: Active Q Drift with Positive Feedback
- For Chile Max. AC Active Power (W) & Max.Output Apparent Power(VA) : GW3000T-DS is 3000, GW3600T-DS is 3600, GW4200T-DS is 4200, GW5000T-DS is 5000, GW6000T-DS is 6000
- For Brazil Max. Input Power (W), GW2900D-NS is 5220, GW3000D-NS is 5400, GW3600D-NS is 6624, GW4200D-NS is 7560, GW5000D-NS is 9000, GW6000D-NS is 10800, GW3000T-DS is 5400, GW3600T-DS is 6624, GW4200T-DS is 7560, GW5000T-DS is 9000, GW6000T-DS is 10800, GW5KBD-NS is 9000, GW6KBD-NS is 10800
GoodWe Technologies Co., Ltd.
- No. 90 Zijin Rd., New District, Suzhou, 215011, China
- www.goodwe.com.
- service@goodwe.com.
Grid-Tied PV Inverter
- DNS Series
- 2.9-6kW
- V1.1-2023-05-30
- V1.1-2023-05-30 Copyright Statement.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>