PDK Red 1 Expansion Board User Guide
- June 3, 2024
- pdk
Table of Contents
- PDK Red 1 Expansion Board
- Mounting the Power Supplies
- Mounting the Expander Board
- Reader Connection
- Input A/DPS Connection
- Input B/REX Connection
- Locking Relay
- Communication Connections
- Power Connection
- Reference Guide
- OSDP Reference Guide
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
PDK Red 1 Expansion Board
Mounting the Power Supplies
Mount
Line up the power supplies with the top mounting brackets in the enclosure.
Using the supplied screws, fasten the power supplies to the enclosure.
Mounting the Expander Board
Mount
Select your desired mounting location within the enclosure. Line up the
expander board with the desired mounting brackets. Using the supplied screws,
fasten the expander board to the enclosure.
Reader Connection
- A Reader – The reader is mounted at the door with a 22/5 or 22/6 wire running to the door controller. Wire the reader to the controller as shown above. Be sure to check the polarity and voltage prior to powering the controller.
- B OSDP – Place jumper to enable OSDP (see OSDP reference guide at the end of this guide for more info)
- C Piezo – Can be connected to available relay and configured with software.
Input A/DPS Connection
- A DPS (Door Position Sensor) – The DPS is mounted on the door frame with a 22/2 wire running from the DPS to the controller. Wire the DPS to the controller as shown above. For reporting double doors, wire the two-door position in series and connect to the controller.
- B AUX Input – A software rule can be programmed to trigger events or outputs based on input triggers.
Input B/REX Connection
- A Maglock – When installing a Maglock, it is typical to install a REX (request to exit) at the door for free egress. Run an 18/2 wire from the maglock to the controller and REX as shown.
- B REX (Request to Exit) – The REX is mounted at your desired location with an 18/5 wire. Wire the REX to the controller and maglock, as shown above. If reporting is not needed in the system, simply eliminate the green input wire.
- C Jumper Block – Use to designate (+) or (-) board voltage out of NO and NC. If the jumper is off, the relay is a standard dry contact requiring input into C on the relay.
- D AUX Input – A software rule can be programmed to trigger events or outputs based on input triggers.
Locking Relay
- A Diode – The provided diode must be installed when using a strike. Install at the strike with the gray stripe on positive and the black on negative.
- B NC – Used for maglocks (or strikes in fail-safe configuration). Connect the negative (-) of the maglock or strike to NC on the controller.
- C NO – Used for strikes in fail-secure configuration. Connect the negative (-) of the strike to NO on the controller.
- D Jumper Block – Use to designate (+) or (-) board voltage out of NO and NC. If the jumper is off, the relay is a standard dry contact requiring an input into C on the relay.
Communication Connections
- A Ethernet – All Red controllers come with a built-in RJ45 connection for network connectivity. Once connected, the Red controller is Self-Discoverable from pdk.io using IPV6. Alternatively, you may use IPV4 or assign a static IP using pdk.io if desired.
Wireless
(PN: RMW) and PoE (PN: RMPOE) module kits can be purchased for optional
communication methods.
Power Connection
- A Powering Board – Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, G, N]. L to hot, N to neutral, G to ground. Use 14 AWG or larger for all power connections. Secure green wire leads to earth ground.
- Disclaimer -Installers must adhere to all regulations and hold the proper state licenses prior to supplying voltage to the power supply.
- Battery Backup is strongly recommended on all ProdataKey hardware. The recommended backup battery for the Red Max is two 12V 12ah batteries.
Reference Guide
-
Fire Input – To integrate the fire system into a controller, refer to wiring diagrams at www.prodatakey.zendesk.com
-
Programming – After the controller is connected, access the configuration software as instructed in the programming manual available at
www.prodatakey.zendesk.com -
Reader Compatibility – Pdk does not require proprietary readers. Controllers accept a Wiegand input, including biometric readers and keypads. OSDP readers are supported by using the included jumper (see OSDP reference guide). Contact pdk support if assistance is needed.
-
UL 294 Compliance – All equipment must meet appropriate UL certifications. For UL-listed installations, all cable runs must be less than 30 meters (98.5’)
-
Part Number – R1E
OSDP Reference Guide
What is OSDP
Open Supervised Device Protocol (OSDP) is an access control communications
standard developed by the Security Industry Association to improve
interoperability among access control and security products. OSDP brings
heightened security and improved functionality. It is more secure than Wiegand
and supports AES-128 encryption.
OSDP Wire Specification
Four-conductor, twisted-pair cable with an overall shield is recommended to
remain fully TIA-485 compliant at the maximum supported baud rates and cable
distances.
Note
It’s possible to reuse existing Wiegand wiring for OSDP. However, using a
simple stranded cable typical of Wiegand readers generally does not meet the
RS-485 twisted pair recommendations.
OSDP Multi-Drop
Multi-drop gives you the capability to accommodate many readers by running one
length of four-conductor cable, eliminating the need to run wire for each
wire.
- Note – Four (4) is the maximum number of readers each port can support.
- Note – Wiegand readers will not work when OSDP jumpers are installed.
Pdk Technical Support
Phone: 801.317.8802 option #2
Email: support@prodatakey.com
Knowledge Base: prodatakey.zendesk.com.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>