Technical Specifications
Product type | Independent PIR DALI sensor (Daylight harvest) |
---|---|
Operating voltage | 220-240VAC 50/60Hz |
Switched power | Maximum 20pcs DALI devices Maximum 40mA |
Power consumption | < 1W |
Detection angle | 360° |
Detection area (Max.)* | Installation Height : 5m |
Detection Range (0) :10m
Detection range| 10% / 50% / 75% / 100%
Hold time| 2s / 30s / 1 min / 5min / 10min / 15min / 20min / 30min
Stand-by time| Os / 10s / Imin / 5min / 10min / 30min / 1h / +co
Stand-by dimming level| 10% / 20% / 30% / 50%
Daylight threshold| 50 — 500Lux , Disable
Warmming-up time| 30s
Operating temperature| I -20°C — +50°C
Installation
Warnings:
-
Installation of the sensor involves connecting it to the mains supply.
This work must be carried out by a specialist in accordance with electrotechnical regulations. -
Disconnect supply before installing.
Note2: The blinds are optional, they may be inserted behind the lens for
focusing the detection range.
Note2: We recommend the mounting distance between sensor to sensor should
be more than 2m to prevent sensors from false-triggering.
- Sensor inset
- Lens pluggable
- Protection cover (covers the high-voltage terminals, and leaves the DALI terminals exposed).
- Ceiling (drill hole O 70mm).
Rotary Switch Settings
A rotary switch is built inside the sensor for scene selection / fast
programming.
Total 16 channels available:
Channel| Detection range| Hold time| Stand-by time|
Stand-by dimming level| Daylight threes hold
---|---|---|---|---|---
0| 100%| 5s| lOs| 10%| Disable
1| 100%| 1min| 5min| 10%| 50Lux
2| 100%| 5min| 10min| 10%| 50Lux
3| 100%| 5min| +.0| 10%| 751 ux
4| 100%| 5min| +00| 10%| 100Lux
5| 100%| 5min| +00| 30%| 2001 ux
6| 100%| 10min| 30min| 10%| 50Lux
7| 100%| 10min| +.0| 10%| 75Lux
8| 100%| 10min| +.0| 10%| 100Lux
9| 100%| 10min| +.0| 30%| 200Lux
A| 100%| 20min| 1h| 10%| 100Lux
B| 100%| 20nnin| +.0| 30%| 200Lux
C| 100%| 30min| +00| 10%| 100Lux
D| 100%| 30min| +00| 30%| 200Lux
E| 100%| 30min| +00| 50%| 400Lux
F| 100%| 5s| lOs| 10%| 100Lux
Note: settings can also be changed by remote control HRC-11. The last action controls.
Functions
Daylight Harvest (Daylight Regulating)
Daylight sensor measures the available surrounding natural light, calculates
how much electrical light is needed to reach the total lux expected. The
demand is given to the LED driver by DALI signal, so as to deliver the needed
amount of electric light.
Lux Off Function
The built-in daylight sensor can read ambient natural light and switch off
the fixture automatically whenever artificial light is not required (natural
light lux level exceeds daylight threshold).
Note: If the stand-by time is preset at “+∞”, the fixture never
switches off even when natural light is sufficient.
Semi-auto Function (Absence Detection)
The motion sensor is employed, but only activated on the manual press of
the push switch, light keeps on in the presence, and dims down in the absence,
and eventually switches off automatically in the long absence.
Manual Override
With the help of push-switch, this sensor maybe over-ridden by the end-
users to switch on/off the lights manually, or adjust the light brightness
during motion hold-time.
This makes the product more user-friendly and offers more options to fit for
extra-ordinary demands.
-
Short push ( <1s): on/off function;
ON → OFF: the light turns off immediately and cannot be lighten for a certain time (equals to hold time preset) even there is movement is detected. After this period, the sensor goes back to auto sensor mode.
OFF → ON: the light turns on 100% and goes to auto sensor mode, even when ambient Lux level exceeds the daylight threshold. -
Long push (>1s): adjust the target lux level by turning the light up or down. Both the adjustment on remote control and push switch can overwrite each other, the last adjustment remains in memory.
Note: end-user can choose either function 4.3 or 4.4 for application. Default function is 4.4.
Synchronization Function
By connecting the “SYNC” terminals in parallel (see wiring diagram), no
matter which sensor detects motion, all HIR24 in the group will turn on the
lights when surrounding natural light is below the daylight threshold. The
sensor module is shared and the detection area could be widely enlarged in
this way.
Wiring Diagram
Note: if neither function 4.3 nor 4.4 is desired, simply leave the “push”
terminal disconnected.
Detection Pattern
Description of the Button Functions (remote control HRC-11)
Permanent ON/OFF [ button 1 ]
Press button ①, to select permanent ON or permanent OFF mode.
- Press button ②/④ to resume automatic operation.
The mode will change to AUTO Mode after power failure.
RESET[ button ② ] Press button ②, all settings go back to the rotary switch settings.
Shift [ button ③] Press button③, the LED on the top left corner is on for
indication.
All values / settings in RED are in valid for 20 seconds.
Auto Mode [ button ④]
Press button ④ to initiate automatic mode.
The sensor starts working and all settings remain as before the light was
switched ON/OFF.
Semi-auto Mode [ button ③ & ④]
- Press button ③ Shift (the red LED is on for indication).
- Press button ④ to initiate semi-auto mode. The fixture is manually on by push-switch and automatically off in semi-auto mode.
Power output [ button ⑤] Press button ⑤, the light output shifts between
80% and 100%.
Note: the function of “Sensor off” and “Twilight” are disabled.
Brightness +/- [ button ⑥]
Press button ⑥ to adjust the light brightness to reset target lux level.
Scene prog. [ zone ➆ ] (One-key-commissioning)
- Press button “Start” to program.
- Select the buttons in ⑧ “Detection range”, ⑨/⑩ “Daylight threshold”, ⑪ “Hold time”, ⑫“Stand-by time”, ⑬“Stand-by dimming level” to set all parameters
- Press button “Memory” to save all the settings programmed in the remote control.
- Press button “Apply” to set the settings to each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +∞, stand-by dimming level 30%, steps should be:
Press button ➆ Start, button ⑧100%, ⑩ Disable, ③ Shift, 5min, ③ Shift, +∞ , ⑬ 30%, ➆ Memory. By pointing to the sensor unit(s) and pressing➆ Apply, all settings are passed on the sensor(s).
Detection range [ zone ⑧]
Press buttons in zone ⑧ to set detection range at 100% / 75% / 50% / 10%.
Daylight threshold [ zone ⑨ ] Press buttons in zone ⑨ to set the daylight
sensor at 50Lux / 100Lux / 300Lux / 500Lux or Disable as threshold / target
Lux level.
Note: 2lux / 10lux are disabled.
To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button ③ Shift at
first.
Ambient daylight threshold [ button ⑩]
- Press button ③ Shift, the red LED is on for indication.
- Press button ⑩, the ambient lux level is sampled and set as daylight threshold / target Lux level.
Hold time [ zone ⑪] Press buttons in zone ⑪ to set the hold time at 2s /
30s / 1min / 5min / 10min / 15min / 20min / 30min.
Note:
- To set hold-time at 30s / 5min / 15min / 30min, press button ③Shift at first.
- 2s is for test purpose only, stand-by period and daylight sensor settings are disabled in this mode.
To exit from Test mode, press button ② or any button in zone⑪ .⑪
Stand-by time [ zone ⑫]
Press buttons in zone ⑫ to set the stand-by period at 0s / 10s / 1min / 5min /
10min / 30min / 1h / +∞.
Note: “0s” means on/off control; “+∞” means bi-level control, 100% on
when motion detected, and remains at the stand-by dimming level when no
presence after hold-time.
Daylight harvest auto-configuration function [ zone ⑬]
-
Press button “Shift”, the red LED is on for indication.
-
Select a time period and the sensor will do light level measurement and determine/save the lowest light level (commission line) with 100%light on, so as to set the target lux level automatically.
Note: -
Make sure the light level measurement covers the night time.
-
The fixture will go into sensor mode after the measurement, all sensor settings remain unchanged.
Stand-by dimming level [ zone ⑭]
Press buttons in zone ⑭ to set the stand-by dimming level at 10% / 20% / 30% / 50%.
Dual tech & RF mode [ zone ⑮]
All buttons in zone ⑮are disabled.
Customer Support
Hytronik Industrial Ltd. | www.hytronik.com
3rd Floor, block C, complex building, 155#, Bai’gang road south,
Bai’gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023
Tel: 86-752-2772020
Fax: 86-752-2777877
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>