HYTRONIK HIM32 Dual Sense Daylight Harvest
Technical Specifications
Product type | High bay dual sense sensor (daylight harvest) |
---|---|
Operating voltage | 220-240VAC 50/60Hz |
Rated load | 800VA(Capacitive) 1000W(Resistive) |
Power consumption | < 0.5W |
Detection angle | 360o |
Detection area (Max.)* | Installation Height : 15m Detection Range (Ø) :18m |
Detection range | 10% / 50% / 70% / 100% |
Hold time | 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min |
Stand-by time | 0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞ |
Stand-by dimming level | 10% / 20% / 30% / 50% |
Daylight threshold | 50 ~ 500Lux, Disable |
Warming up time | 30s |
Operating temperature | 35 oC ~ +50oC |
IP rating | IP65 |
Sensor mode | HF, PIR, HF+PIR, HF / PIR |
Installation
Warnings:
- Installation of the sensor involves connecting it to the mains supply. This work must be carried out by a specialist in accordance with electrotechnical regulations.
- Disconnect power supply before installing.
A. Ceiling mount
B. Screw to the Luminaire by conduit
C. Attach to the shade by clamp
Note: We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.
Rotary Switch Settings
A rotary switch is built inside the sensor for scene selection/fast programming. Total of 16 channels are available:
Channel| Detection range| Hold time| Stand-by time|
Stand-by dimming level| Daylight threshold
---|---|---|---|---|---
0| 100%| 5s| 10s| 10%| Disable
1| 100%| 1min| 5min| 10%| 50Lux
2| 100%| 5min| 10min| 10%| 50Lux
3| 100%| 5min| +∞| 10%| 75Lux
4| 100%| 5min| +∞| 10%| 100Lux
5| 100%| 5min| +∞| 30%| 200Lux
6| 100%| 10min| 30min| 10%| 50Lux
7| 100%| 10min| +∞| 10%| 75Lux
8| 100%| 10min| +∞| 10%| 100Lux
9| 100%| 10min| +∞| 30%| 200Lux
A| 100%| 20min| 1h| 10%| 100Lux
B| 100%| 20min| +∞| 30%| 200Lux
C| 100%| 30min| +∞| 10%| 100Lux
D| 100%| 30min| +∞| 30%| 200Lux
E| 100%| 30min| +∞| 50%| 400Lux
F| 100%| 5s| 10s| 10%| 100Lux
Note: settings can also be changed by remote control HRC-11. The last action controls.
Functions
Daylight Harvest (Daylight Regulating)
Daylight sensor measures the available natural light of the surrounding, and
calculates how much electrical light is needed to reach the total lux
expected. The demand is given to the LED driver by 1-10V signal, so as to
deliver the needed amount of electric light.
Note: by pressing the “Sensor off” button on the remote control, the sensor occupancy function is disabled. The target lux level for daylight harvest function can be adjusted by the “Brightness +/-” buttons.
Lux Off Function
The built-in daylight sensor can read ambient natural light and switch off the
fixture automatically whenever artificial light is unnecessary(natural light lux
level exceeds daylight threshold).
Note: if the stand-by time is preset at “+∞”, the fixture never switches
off even when natural light is sufficient.
Load Indication
The light will flash ONCE rapidly after receiving the command from the remote
controller. Note: There is no load indication (the light will not flash) when
button ON/OFF, POWER 100% or POWER 80% is pressed.
Wiring Diagram
Three Options for PIR Lens and Detection Patterns
For single person walking across, the detection range is reduced by 1/3.
Descriptions of the Button Functions (remote control HRC-11)
Permanent ON/OFF [button 1]
Press button 1 , to select permanent ON or permanent OFF mode.
Press button 2 / to resume automatic operation. The mode will change to
AUTO Mode after power failure.
RESET[ button2 ]
Press button 2 , all settings go back to the rotary switch settings.
Shift [ button 3]
Press button 3 , the LED on the top left corner is on for indication. All
values / settings in RED are in valid for 20 seconds.
Auto Mode [ button 4]
Press button 4 to initiate automatic mode. The sensor starts working and
all settings remain as before the light was switched ON/OFF.
Note: the function of Semi-auto is disabled.
Sensor off [ button 5] (Daylight harvest without occupancy)
- Press button 3 , the red LED is on for indication.
- Press button “Sensor off”, the function of movement detection is disabled.
Note: the function of “Twilight” is disabled.
Power output [ button 6]
Press button 6 , the light output shifts between 80% and 100%.
Brightness +/- [ button 7]
Press button 7 to adjust the light brightness to reset the target lux
level.
Scene prog. [ zone 8] (One-key-commissioning)
- Press button “Start” to program.
- Select the buttons in 9 “Detection range”, 10 / 11 “Daylight threshold”, 12 “Hold time”, 13 “Stand-by time”, 14 “Stand-by dimming level” to set all parameters.
- Press button “Memory” to save all the settings programmed in the remote control.
- Press button “Apply” to set the settings to each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +, stand-by dimming level 30%, the steps should be as follows: Press button 8 Start, button 9 100%, Disable, Shift, 13 5min, 3 Shift, 13 + , 30%, 8 Memory. By pointing to the sensor unit(s) and pressing Apply, all settings are passed on the sensor(s).
Detection range [ zone 9]
Press buttons in zone 9 to set detection range at 100% / 75% / 50% / 10%.
Daylight threshold [ zone 10]
Press buttons in zone 10 to set the daylight sensor at 50Lux / 100Lux /
300Lux / 500Lux or Disable as threshold / target Lux level.
Note: 2Lux / 10Lux are disabled.
To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button 3 Shift
at first.
Ambient daylight threshold [ button 11]
- Press button 3 Shift, the red LED is on for indication.
- Press button 11 , the ambient lux level is sampled and set as daylight threshold / target Lux level.
Hold time [ zone 12]
Press buttons in zone 12 to set the hold time at 2s / 30s / 1min / 5min /
10min / 15min / 20min / 30min.
Note:
- To set hold-time at 30s / 5min / 15min / 30min, press button 3 Shift at first.
- 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode.
*To exit from Test mode, press button or any button in zone.
Stand-by time [ zone 13]
Press buttons in zone 13 to set the stand-by period at 0s / 10s / 1min /
5min / 10min / 30min / 1h / +.
Note: “0s” means on/off control; “+” means bi-level control, 100% on when
motion detected, and remains at the stand-by dimming level when no presence is
detected after hold-time.
Stand-by dimming level [ zone 14]
Press buttons in zone 14 to set the stand-by dimming level at 10% / 20% /
30% / 50%.
Daylight harvest auto-configuration function
- Press button “Shift”, the red LED is on for indication.
- Select a time period and the sensor will do light level measurement and determine/save the lowest light level (commission line) with 100% light on, so as to set the target lux level automatically.
Note:
- Make sure the light level measurement covers the night time.
- The fixture will go into sensor mode after the measurement, all sensor settings remain unchanged.
Dual tech [ zone 15 ]
Press buttons in zone 15 to select sensor technology.
HF+PIR: Light is on when both HF and PIR sensors are activated.
HF/PIR: Light is on when HF or PIR sensors are activated.
RF mode [ zone 16 ] All buttons in zone 16 are disabled.
Hytronik Industrial Ltd. | www.hytronik.com
3rd Floor, block C, complex building, 155#, Bai’gang road south,
Bai’gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023
Tel: 86-752-2772020 Fax: 86-752-2777877
Read User Manual Online (PDF format)