Armstrong Rada Sense Mobile App User Guide

June 3, 2024
ARMSTRONG

armstrong-logo

Armstrong Rada Sense Mobile App

IMPORTANT
Installer: This manual is the property of the customer and must be retained with the product for maintenance and operational purposes.

Introduction

The companion mobile app for Rada Sense allows the product to be set up and commis-sioned to the customer’s specific requirements, should they deviate from the factory default settings. The app allows specific settings of the product to be configured as required and also allows the configuration and management of features such as the built-in duty flushing mechanism and thermal disinfection routines.

System Requirements
The mobile app is compatible with both iOS and Android platforms (see End User License agreement for more specific details regarding minimum operating system and hardware requirements).

Installation

Download the Rada Sense mobile app from either the Apple App Store® or Google Play™ or scan the QR code using your mobile device.

Getting Started

Disable Control Panel
Disable the Control Panel with the magnetic key (Control Panel is disabled when the blue light flash-es in the middle oval window under the outlet icon, indicated below). This puts the product into the Programming / Cleaning mode. Ensure Bluetooth connectivity is enabled on your mobile device then launch the Rada Sense app.

Product Discovery
After launching the app, the local area will be scanned for compatible Rada Sense products that are in the Programming / Cleaning mode.Armstrong-Rada-
Sense-Mobile-App-FIG-3

Connecting to Product

Login Screen
  • Enter default PIN of 2502 to connect to the Sense product.
  • Read “Terms & conditions” and “Privacy policies”
  • Tap on “Continue”.Armstrong-Rada-Sense-Mobile-App-FIG-4
  • If the correct PIN is entered, your mobile device will establish a connection to the product.Armstrong-Rada-Sense-Mobile-App-FIG-5

Updating PIN

Armstrong-Rada-Sense-Mobile-App-FIG-6

  1. Enter a new PIN or alternatively, tap “Skip”.
  2. Tap on “Update PIN”.
  3. A screen will appear to advise whether the PIN change has been successful or not.Armstrong-Rada-Sense-Mobile-App-FIG-7

Main Menu

Once connected to the Sense product, you will see the Main Menu as follows:

Outlet 1/2
Depending on the product you are connected to(single or dual outlet), either one or both of the outlet options will appear. Select the relevant outlet to change the individual settings.

Note:

  • On Bath / Shower models:
  • Outlet 1 = Shower
  • Outlet 2 = Bath
  • On Shower / Shower models:
  • Outlet 1 = Fixed Showerhead
  • Outlet 2 = Variable ShowerheadArmstrong-Rada-Sense-Mobile-App-FIG-8

Disinfection Configuration
Set parameters for a thermal disinfection cycle.

Disinfection Cycle
Performs a disinfection cycle and displays the result and log graph of the last cycle.

Duty Flush
Configures the parameters for the automatic duty flush of the product during periods of inactivity.

Engineering
Provides information relating to servicing / diagnostics.

Valve Usage Data
Provides statistics based on the use of the prod-uct.

Valve Information
Displays embedded software configuration data and manufacturing data.

Outlet

Both the Outlet 1 and Outlet 2 (if applicable) sub-menus display the following configurable settings:Armstrong-Rada-Sense-Mobile-App-
FIG-9

Minimum Temperature
Specifies the minimum user adjustable temperature limit.

Maximum Temperature
Specifies the maximum user adjustable temperature limit.

Default Temperature
Specifies the temperature at which the product will turn on by default.

Full Cold Enable
If enabled, the user can select full cold water delivery e.g. for cleaning teeth in a basin applica-tion.

Disinfection Enable
When enabled, allows a disinfection cycle to be performed on the outlet. If disabled, the outlet will be skipped during the disinfection cycle.

Duty Flush Enable
When enabled, allows a duty flush cycle to be per-formed on the outlet. If disabled, the outlet will be skipped during the duty flush cycle.

Flow Time Duration
Configures the length of time the outlet should run for before automatically switching off.

Configure Setpoints

Armstrong-Rada-Sense-Mobile-App-FIG-10

  1. Adjust the outlet settings as required for the outlet and tap “Save” to commit the changes to the product.
  2. A notification as shown in the image (left) indicates that the product is successfully configured with new settings.Armstrong-Rada-Sense-Mobile-App-FIG-11

Disinfection Configuration

The Disinfection Configuration sub-menu displays the configurable options for carrying out a thermal disinfection cycle.

Type

A Standard disinfection will deliver hot water for the duration period specified, which must be above the Minimum Temperature specified. The Energy saving disinfection allows an Upper temperature limit to also be specified as well as the minimum limit. If the water temperature is between the Minimum Temperature and the Upper Temperature, the disinfection time is progressively reduced. The reduction is comput-ed continuously and has the effect of halving the time for each 5°C increase above the Minimum Temperature. Should the temperature rise above the Upper Temperature then no further time reduction accrues.

Minimum Temperature
The minimum temperature required to perform a successful disinfection cycle.

Minimum Time
The minimum duration of the disinfection cycle.

Maximum Warmup Time
The maximum time allowed for the disinfection temperature to be reached. If the temperature is not reached within this period, then the disinfec-tion will be canceled (if unsure, leave as default).

Duration
The maximum duration of the cycle. If cycle is not completed within this period, then the dis-infection will be canceled (if unsure, leave as default ).Armstrong-Rada-Sense-Mobile-App-FIG-12

Warning! Time reduction is not permitted by some National / Lo-cal Regulations. If in doubt, select “Standard” settings.

Flow Options
If checked, the reduced flow rate will minimize the volume of water utilised during the disinfection cycle to save resources.

Important! This option should not be utilised on UK (T3) models.

Master Disinfection Enable
This option needs to be enabled in order to operate a thermal disinfection cycle. Disabling this option provides an extra level of security to prevent accidental triggering of a thermal disinfection cycle.Armstrong-Rada-Sense-
Mobile-App-FIG-13

Configure Setpoints
Adjust the disinfection settings as required for the product and tap “Save” to configure the desired changes to the product. A notification as shown in the image (left) indi-cates that the product is successfully configured with new settings.

Disinfection Cycle

The Disinfection Cycle sub-menu allows the user to commence a manual thermal disinfection cycle on the product to reduce the risk of a build-up of contamination and harmful bacteria within the product and pipework.

Warning!

The Disinfection cycle is not an automated process. It is activated by the supervisor manually and will raise the water temperature to exceed the safe level for bathing and will scald or even kill. It is therefore the responsibility of the supervisor to make sure the process is carried out correctly and safely.

The following safety measures must be observed:
The disinfection process is not to be initiated unless adequate systems are in place to ensure that the area is clear of any persons prior to and during the disinfection process.
Please consult the national or local authority Legionella Legislation or Guidelines as appropriate for your country/area to see how the Thermal Disinfection process can be used to meet the required level of hygiene. The disinfection cycle and its settings are controlled in the “Disinfection Configuration” sub-menu. Disinfection per outlet is enabled or isabled in the “Outlet Configuration”sub-menus.

Thermal Disinfection

IMPORTANT! PLEASE READ CAREFULLY. DO NOT USE THE THERMAL DISINFECTION FEATURE IF THE HOT WATER SUPPLY CAN EXCEED 80°C (176°F)! THE MAXIMUM TEMPERATURE FOR DISINFECTION SETPOINT MUST BE 80°C (176°F) Prior to commencing a thermal disinfection cycle, ensure the product has been configured in line with local bylaws / regional legislation to ensure that the process conforms. The water flow during disinfec-tion will be very hot and may scald on contact. The valve must be supervised throughout the disinfec-tion process and no-one should come within 3m of the outlet. ALL RADA SENSE ALERTS AND ERRORS ARE DISABLED DURING THE PROCESS!Armstrong-Rada-Sense-Mobile-App-FIG-15

  1. Close all outlets in the system.

  2. Tap the “Arm” button which prepares the valve to start disinfection.

  3. The message “Ready to Trigger” will appear once the product has acknowledged the request. Tap “Trigger” to confirm and initiate the disinfection cy-cle within 30 seconds of arming. Failure to trigger will require the Arm process to be repeated.

  4. A 10-second countdown will begin and water flow will commence when this reaches zero.
    Note: The control panel is enabled during disinfection. If any sensor is activated then the disinfection cycle is aborted.
    Warning! For continued protection against legionella, thermal disinfection must be car-ried out on a regular basis. Please consult your national guidelines for details.

  5. Tapping the “Abort Disinfection” button at any point (either during the countdown or once the dis-infection has commenced) will stop the disinfection cycle immediately after tapping the confirmation pop-up as shown.Armstrong-Rada-Sense-Mobile-App-FIG-17

Disinfection Logs

  • Once the product commences the Thermal Disinfection cycle, a circular bar will gradually fill to indicate progress.
  • Upon completion, the confirmation screen will appear.Armstrong-Rada-Sense-Mobile-App-FIG-18
  • Upon completion, return to the “Disinfection Cycle”sub-menu and tap “Read Log”. If you wish to delete the existing log data, tap “Clear Log”.
  • The summary report will appear indicating either a “Success” or “Fail” of the thermal disinfection cycle against the specified configured temperature limit. A date / time stamp will also be applied to the log. The log can be emailed from your mobile device for record-keeping purposes. In the event of a “Fail”, ensure there is adequate hot water supplied to the valve for the period of time specified in the Disinfection Configuration and sufficient warmup time allowed for the water to get from the source to the product.

Note: The product will only retain one thermal disinfection record which is over-written when a subsequent disinfection cycle is carried out. It is the responsibility of the supervisor to ensure disinfection logs are emailed/retained for proof of compliance.

Duty Flush

The duty flush sub-menu allows the user to configure a periodic flush of the product / pipework in pe-riods of inactivity. This will help to mitigate the build-up of contamination and harmful bacteria within the product and pipework. Unlike a thermal disinfection, the duty flush operates at a safe “blend” temperature rather than an elevated temperature so the risk of scalding is greatly reduced. For this reason, the duty flush can be allowed to operate unsupervised.

Note :: A duty flush routine does not negate the requirement to perform periodic thermal disinfections of the product.

Please consult the national or local authority Legionella Legislation or Guidelines as appropriate for your country/area to see how the Thermal Disinfection process can be used to meet the required level of hygiene.

Temperature
The temperature at which the outlets will flow water during the duty flush cycle. This will only be configurable between the minimum and maxi-mum valve setpoints (see Configure Setpoints on page 10).

Duration
The length of time the outlet should flow water during the duty flush.

Wait Time
The period of inactivity between uses before the duty flush should operate.

Master Duty Flush Enable
Allows the duty flush system to easily be enabled / disabled for all outlets. When disabled, no duty flushing will be performed on any outlet.Armstrong-
Rada-Sense-Mobile-App-FIG-21

Configure Setpoints

Engineering

The Engineering sub-menu provides some additional functions and data related to the product.

Caution!
The valve must be calibrated if either the mixing valve assembly or the DMV control PCB are replaced. The calibration number is required for optimumperfomance and this can be found on the mixing valve body as shown above.
Location
An alias / description of the location of the product can be entered in this field (max 16 characters). This alias will appear in the Bluetooth broadcast of the product during the search for products to make it easier to identify which product you are connecting to.

Commissioning/Service Date
The dates the product was commissioned/serviced will appear in these fields here for record-keeping/ diagnostic purposes.

Valve Usage Data

The Valve Usage Data sub-menu provides detailed information with regards to the usage of the product throughout its life.

Activations

The number of times the product has been operated (turned on) by the user via the control panel.

Total Minutes
The total number of minutes the product has run for (delivered water to outlets).

Time since last Thermal Disinfection
The number of days/hours that have elapsed since the last thermal disinfection cycle was run.

Time since last used
The number of days/hours that have elapsed since the product was last operated by a user.

Valve Information

The Valve Information sub-menu provides detailed diagnostic information of the product, useful for-fault finding and traceability for servicing.

Serial Number
The unique serial number of the DMV.

Configuration
The variant configuration of the product depend-ing on the application of the product e.g. Bath-Shower,Basin, Shower etc.

Firmware Version
The version of the embedded firmware on the DMV PCB.

Date of Manufacture
The date and time stamp that the DMV was manufactured.

Interface Version
The version of the embedded firmware on the control panel (interface).

App Settings

Tapping the icon from the main menu will present the app settings screen as shown.

Temperature Unit
Allows temperature unit to switch between °C and °F.

Update PIN
Allows the connection PIN number to be changed.

Sign Out
The sign out function will return you back to the initial product search screen and return the currently connected product back to normal operational mode.

App Version
The version of the currently installed mobile app appears at the bottom left hand side of the app settings screen.Armstrong-Rada-Sense-Mobile-App-
FIG-26

Error Messages

Symptom: “Error – Failed to connect xxx Please make sure that xxx is in programming mode and in range” Check the following:

  1. Check power to product.
  2. Sense product is in Programming / Cleaning Mode (see page 5 for details) and ensure blue LED is flashing on the control panel.
  3. Ensure mobile device is within 10 metre range in front of the control panel (clear line of sight).
  4. Verify product is not in an error condition (flashing temperature LED combinations on front panel).
  5. Replace control panel.

Symptom: “Turn on Bluetooth”

  • Check the following:
  • Verify Bluetooth connectivity is enabled on your mobile device.
  • Retry. If error persists, follow steps for error condition above “Failed to connect”.Armstrong-Rada-Sense-Mobile-App-FIG-28

Symptom: “Error – Sorry the PIN you entered was incorrect, please try again”
Check the following:

  1. The default PIN number is 2502. If this does not work, check with the building/maintenance supervi-sor to find out whether this has been changed.
  2. Contact Rada Customer Services (see back Page for contact details).

Temperature Range Error Messages
Symptom: “Error – Unable to set the value. The current duty flush temperature value needs to be decreased prior to set the valve max setpoint.”

Check the following:
When attempting to change the valve setpoint range (max), the app reads out the duty flush tem-perature setting. If this notification appears, reduce the duty flush temperature prior to adjusting the valve max setpoint.

Symptom: “Error – Unable to set the value. The current duty flush temperature value needs to be increased prior to set the valve min setpoint.” Check the following:

  1. When attempting to change the valve setpoint range (min), the app reads out the duty flush temperature setting. If this notification appears, increase the duty flush temperature prior to adjusting the valve min setpoint.

Limited Warranty and Remedy

Armstrong International, Inc. (“Armstrong”) warrants to the original user of those products supplied by it and used in the service and in the manner for which they are intended, that such products shall be free from defects in material and workmanship for a period of one (1) year from the date of installation, but not longer than 15 months from the date of shipment from the factory, [unless a Special Warranty Period applies, as listed below]. This warranty does not extend to any product that has been subject to misuse, neglect or alteration after shipment from the Armstrong factory. Except as may be expressly provided in a written agreement between Armstrong and the user, which is signed by both parties, Armstrong DOES NOT MAKE ANY OTHER REPRESENTATIONS OR WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.

The sole and exclusive remedy with respect to the above-limited warranty or with respect to any other claim relating to the products or to defects or any condition or use of the products supplied by Armstrong, however caused, and whether such claim is based upon warranty, contract, negligence, strict liability, or any other basis or theory, is limited to Armstrong’s repair or replacement of the part or product, excluding any labor or any other cost to remove or install said part or product, or at Arm-strong’s option, to repayment of the purchase price. As a condition of enforcing any rights or remedies relating to Armstrong products, notice of any warranty or other claim relating to the products must be given in writing to Armstrong: (i) within 30 days of last day of the applicable warranty period, or (ii) within 30 days of the date of the manifestation of the condition or occurrence giving rise to the claim, whichever is earlier. IN NO EVENT SHALL ARMSTRONG BE LIABLE FOR SPECIAL, DIRECT, IN-DIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, INCLUDING, BUT NOT LIMITED TO, LOSS OF USE OR PROFITS OR INTERRUPTION OF BUSINESS. The Limited Warranty and Remedy terms herein apply notwithstanding any contrary terms in any purchase order or form submitted or issued by any user, purchaser, or third party and all such contrary terms shall be deemed rejected by Armstrong.

Special Warranty Periods are as follows:
SenseTM DMV is covered by a 5-years warrenty against defects in materials or workmanship from the data of purchase/shipment. Armstrong reverses the right to either recplace the complete product, cer-tain components of product and/or replacement internal operating parts. ©2019 Armstrong International, Inc. Designs, materials, weights and performance ratings are approximate and subject to change without notice.

Armstrong International 221 Armstrong Blvd., three Rivers, Michigan, 49093- USA Armstronginternational.com/brain.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals