CyberPower CPLI72D48V CyberShield Unit User Manual
OVERVIEW
Number | Description |
---|---|
1 | Output (Green) |
2 | On Battery (Yellow) |
3 | Fault (Red) |
4 | Silence Button |
5 | Cold Start Button |
6 | Input Connector |
7 | DC Output Cable |
8 | Battery Cover |
9 | Mounting Hole |
BATTERY REPLACEMENT (FOR TECHNICIAN ONLY)
Follow these instructions carefully during the replacement of the battery.
UNPACKING
Check the CyberShield unit upon receipt. It should contain the following items:
- CPLI72D48V unit
- Lithium battery pack
- User’s manual
- Wall-mounted installation template
BUTTON FUNCTIONS
Button | Functions | Instructions |
---|
__
__
__
Silence
| Temporarily Alarm Off| Press the Silence button for 1 second to turn the
alarm off for 24 hours. A short beep will occur to confirm the alarm is off.
Temporarily Alarm On| Press the Silence button for 1 second again to restore
the
alarm. Two short beeps will occur to confirm the alarm is on.
Shut down| In battery mode, press the Silence button for 10 seconds to
shut down CPLI72D48V.
__
Reset
| In line mode, press the Silence button for 10 seconds to reset
output power and CPLI72D48V.
__
Cold Start
| __
Cold Start
| When utility power is no longer present and a new battery is
installed, press the Cold Start button to start CPLI72D48V.
LED STATUS INDICATION
Indicator | Color | Conditions |
---|---|---|
On | Off | Blinking |
Output | Green | Output is normal |
On Battery | Yellow | Battery mode |
Fault | Red | Replace battery Battery missing |
System error (Every 5 sec.)
AUDIO ALARM
Alarm | Condition |
---|---|
1 long beep | Transfer to battery mode |
1 short beep every 15 minutes | Replace battery/ Battery missing |
4 short beeps every 1 minute | Low battery |
1 short beeps every 5 seconds | System error |
1 short beep | Temporary alarm off |
2 short beep | Temporary alarm on |
COMMUNICATION SIGNALS
The communication signals of this unit are isolated from the internal circuitry via open collector optocoupler transistors. The connection “SIG RTN” (Signal Return) is a return point for all communication signals. In the typical application, the connected equipment digital ground connects to Signal Return, and pull-up resistors turn the open collector signals into logic levels.
Pin Number | Function | Message |
---|---|---|
1 | Power “+” | + Voltage output. |
2 | On Battery | Low when the unit is in utility mode. |
Open when the unit is in battery mode.
3| Battery Missing| Low when the battery is present.
Open when the battery is missing.
4| SIG RTN| Signal return.
5| Power “-”| – Voltage output.
6| Replace Battery| Low when the battery is in a normal state.
Open when the battery needs to be replaced.
7| Low Battery| Low when the battery has sufficient capacity.
Open when the battery’s capacity is low.
8| No Use
SPECIFICATION
Model | CPLI72D48V |
---|
Input
Voltage Range| 48 – 56 Vdc
Output
Output Voltage| 50 – 56 Vdc
Continuous Power Capability (Utility Mode)| 72 W
Max Power Capability (Utility Mode)| 80 W (<5 sec)
Continuous Power Capability (Battery Mode)| 40 W
Max Power Capability (Battery Mode)| 72 W (<5 sec)
Efficiency| >80%
Battery
Battery Type| Lithium Battery Pack (with thermal sensor)
Numbers of Battery| 2,200 mAh/14.4 V x 1
Typical Recharge Time| 5 Hours
Replaceable| Yes (technician only)
Warning Diagnostics
LED Indicators| Output, On Battery, Fault
Audible Alarm| Yes
Management
Auto Charge| Yes
Battery Pre-charge Function| Yes
Communication Interface| On Battery, Replace Battery, Battery Missing,Low
Battery
Physical
Maximum Dimensions (LWD)| 16.5 x 9.6 x 4.7 (cm)
Weight (including battery)| 575 g
Environment
Operating Temperature| 23 ~131°F (-5 ~ 55 °C)
Operating Humidity| 0 ~ 95% noncondensing within enclosure
Max Operating Elevation| 10,000 ft (3,048m)
Max Storage Elevation| 50,000 ft (15,240m)
Storage Temperature| 23 ~ 131°F (-5 ~ 55 °C)