SALUS KL08RF ZigBee Network Wireless Wiring Centre User Manual

June 3, 2024
SALUS

SALUS CONTROL LOGO

SALUS KL08RF ZigBee Network Wireless Wiring Centre

Wiring centre description

SALUS KL08RF ZigBee Network Wireless Wiring
Centre 1

  1. Cartridge fuse 5 x 20 mm 12 A
  2. Power Supply
  3. Thermostat grouping status
  4. Network Status diode
  5. Pair button
  6. Reset button
  7. Delay jumper
  8. INT/EXT antenna jumper
  9. NC/NO actuators jumper
  10. ZigBee network coordinator
  11. Terminals for actuators
  12. Pump control output
  13. Boiler control output
  14. CO terminal
  15. Dew point sensor input (humidistat)
  16. Serial connector for the KL04RF extension
  17. External antenna connector

RX10RF (optional)

Additional, wireless device control module that can be used – for example – when we can’t use cable between the KL08RF wiring centre and the boiler.

Introduction

The KL08RF wireless wiring centre is a part of the iT600RF system. In combination with the wireless thermostats from iT600RF series, KL08RF provides comfortable and reliable heating control. It is equipped with the control outputs for the pump and boiler and has been designed to work with NC or NO actuators. In Offline mode, communication with the wireless thermostats from iT600RF series must be done through the CO10RF co-ordinating unit, which is in the package together with the wiring centre. To work in Online mode (via the SALUS Smart Home app) KL08RF must be connected to the Internet gateway UGE600. In one ZigBee network (Online or Offline) up to 9 KL08RF wiring centres can be connected. KL08RF increases ZigBee network range.

Product Compliance
This product complies with the essential requirements and other relevant provisions of Directives: EMC 2014/30/EU, LVD 2014/35/EU, RED 2014/53/EU and RoHS 2011/65/EU. The full text of the EU Declaration of Conformity is available at the following internet address: www.saluslegal.com.

Safety Information
Use in accordance with the regulations. Indoor use only. Keep your device completely dry. Disconnect your device before cleaning it with a dry cloth. This accessory must be fitted by a competent person, and installation must comply with the guidance, standards and regulations applicable to the city, country or state where the product is installed. Failure to comply with the relevant standards could lead to prosecution.

Technical Information

Power Supply 230 V AC 50 Hz
Max load 3 A
Inputs CO terminal

Dew point sensor (humidistat)

Outputs| Pump control Boiler control

Terminals for actuators

Radio frequency| ZigBee 2,4 GHz
Dimensions [mm]| 355x83x67

  1. Fuse
    Note : Fuse replacement should be done when the wiring centre is disconnected from power supply 230 V AC.
    The mains fuse is located under the housing cover, at the main terminals and protects the wiring centre and devices powered by it. Use cartridge fuse-type 5 x 20 mm – nominal burn rate 12 A. To remove the fuse, lift the socket with a flat screwdriver and pull out the fuse.

  2. Power Supply 230 V AC****

  3. Thermostat grouping status
    This function is only available in Offline mode (together with CO10RF coordinator) – it means MASTER thermostats will affect to SLAVE thermostats within specific group, which is possible only when thermostats are paired with one KL08RF wiring centre (optional + KL04RF) and have been assigned to gr. 1 or gr. 2.
    Note : Within one group there may be only one MASTER thermostat (programmable) and must be SLAVE thermostats (non-programmable).

    How it works:
    If all thermostats of a given group will operate in automatic mode, then each of the thermostats in a given group will work in the same way as the MASTER of this group. For example, if the MASTER thermostat of Group 1 according to it’s programmed schedule maintains a comfort mode – all SLAVE type thermostats from Group 1 will also maintain the comfort mode (the temperature is set individually for every thermostat). Similarly, if the MASTER thermostat is set to Party or Holiday mode – SLAVE thermostats in his group will also work in these modes.

  4. Network Status diode
    LED diode statuses:

SALUS KL08RF ZigBee Network Wireless Wiring Centre
4

  1. Pair button
    Functions of the Pair button:

    • Checking the address of the wiring centre in the Zigbee network. To check the address of the wiring centre in the ZigBee network (when using more than one) press the Pair button. The wiring centre number is indicated by the number of LEDs at the zones:

SALUS KL08RF ZigBee Network Wireless Wiring Centre
5

  * The wiring centre reset (this function is described in detail on the second page of the manual).
  1. Reset button

  2. It is used to refresh the data, after moving jumpers 7,8 or 9. The Reset button does not remove the wiring centre from the ZigBee network.

  3. Delay jumper
    Boiler off delay time.

    • Note : Pump (Pump output) and boiler (Boiler output) always starts 3 minutes after receiving the heating signal from any thermostats paired with wiring centre. Pump stops after 3 minutes, when the last thermostat stops sending demand for heat, while the heat source (Boiler) will turn off after the time set with the jumper.
      Jumper position change must be refreshed in the memory by pressing the Reset button (short press).
  4. INT/EXT antenna jumper
    There is an option to connect the 08RFA external antenna to the wiring centre. If you use an additional antenna, place the jumper in the EXT position.
    Jumper position change must be refreshed in the memory by pressing the Reset button (short press).

  5. NC/NO actuators jumper
    Select the type of the thermoelectric actuator connected to the wiring centre:
    NC – actuator normally closed
    NO – actuator normally opened
    Jumper position change must be refreshed in the memory by pressing the Reset button (short press).

  6. ZigBee network coordinator**
    The ZigBee network coordination unit CO10RF is used for Offline mode and it’s included with the wiring centre. CO10RF enables wireless control of all devices installed in one network. Within one network can be connected max 9 wiring centres. It means that if in the network there are more than one wiring centre, you can use one coordinator and put the remaining ones in a safe place.
    Note** : Do not use CO10RF coordinator with UGE600 simultaneously.

  7. Terminals for actuators
    Wires of the thermoelectric actuators should be plugged into the self-locking connectors in the appropriate zones. You can connect 3 actuators directly to one zone. The current load of one zone is adapted to operate with up to 6 thermoelectric actuators with a power of 2 Watts. If there is a need to connect more than 6 actuators please use an additional relay to relieve the output of the zone.

SALUS KL08RF ZigBee Network Wireless Wiring Centre
10

  1. Pump control output**SALUS KL08RF ZigBee Network Wireless Wiring Centre 11
    Pump output** – this is a volt free output (COM / NO) that controls the circulation pump in the heating / cooling system. The output closes (pump starts) always after 3 minutes after receiving the heating / cooling signal from any of thermostats paired with wiring centre. The output opens (pump stops) after 3 minutes, when the last thermostat stops sending heat / cold demand.

  2. Boiler control outputSALUS KL08RF ZigBee Network Wireless Wiring Centre 12
    Boiler output – this is a volt free output (COM / NO) that controls the boiler in the heating system. The output closes and the boiler turns on but always after 3 minutes after receiving the heating signal from any of thermostats paired with wiring centre. The output opens and the boiler switches off when the last thermostat stops sending heat demand (after the time set on the Delay jumper).

  3. CO terminal (input)

Opened CO input contacts (Changeover) means that whole system works in the heating mode. Short circuit at the input CO will automatically switch the whole system to cooling mode (wiring centre and paired thermostats).

SALUS KL08RF ZigBee Network Wireless Wiring Centre
14

  1. Dew point sensor input (humidistat)

Dew point sensor input is active only in cooling mode (with closed CO contacts). Shorting the contacts at the dew point sensor input (too high humidity) causes switching off all zones in the wiring centre and Pump control outputs.

  1. Serial connector for the KL04RF extension
    It is used for communication between the KL08RF wiring centre and the KL04RF extension module. KL04RF extension module increases functionality and expands support up to 12 zones.

SALUS KL08RF ZigBee Network Wireless Wiring Centre
16

  1. External antenna connector
    The external antenna connector 08RFA is located underneath the wiring centre under zones 7 and 8. After connecting an additional antenna, place the jumper in the EXT position. Jumper position change must be refreshed in the memory by pressing the Reset button (short press).

MOUNTING

SALUS KL08RF ZigBee Network Wireless Wiring Centre
17 SALUS KL08RF ZigBee Network Wireless
Wiring Centre 18

INSTALLATION

  1. Connect the wiring centre to the 230 V AC power supply. The Network Status LED will blink.

SALUS KL08RF ZigBee Network Wireless Wiring Centre
19

  1. SALUS KL08RF ZigBee Network Wireless Wiring Centre 20

  2. Wiring centre will connect to the network automatically. The Network Status LED will turn solid green.

SALUS KL08RF ZigBee Network Wireless Wiring Centre
21

SALUS KL08RF ZigBee Network Wireless Wiring Centre
22

Identification of the wiring centre
To identify the wiring centre in the ZigBee network, follow the steps below: In Online mode (using the SALUS Smart Home app):

SALUS KL08RF ZigBee Network Wireless Wiring Centre
23

SALUS KL08RF ZigBee Network Wireless Wiring Centre 24 Factory reset
To restore the factory settings, press and hold the Pair button for 15 seconds. G1 and G2 diodes will turn red and go out.
Note : If you restore the factory settings of the wiring centre, all paired devices will be removed from the ZigBee network – you will have to synchronize them again.

SALUS KL08RF ZigBee Network Wireless Wiring Centre
25

Head Office :
SALUS Controls plc
SALUS House
Dodworth Business Park South, Whinby Road, Dodworth, Barnsley S75 3SP, UK.

www.salus-controls.com
SALUS Controls is a member of the Computime Group. Maintaining a policy of continuous product development SALUS Controls plc reserve the right to change specification, design and materials of products listed in this brochure without prior notice.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals