DELTA uno Lite Modbus User Guide
- June 3, 2024
- Delta
Table of Contents
DELTA uno Lite Modbus
Revision
Date | Version | Description |
---|---|---|
2022/ 11 / 11 | 0.1 | Initial Version |
Overview
UNOlite is an indoor air quality monitor to measure the space temperature / humidity / CO2 / PM2.5 / PM10 / PM1 / TVOC and expose the measurements directly onto a BACnet MS/TP or Modbus RTU network. Moreover, the measurements are also accessible with UNO apps through BLE or UNO web through Wi-Fi (Wi-Fi model). Please refer to UNOlite official website for more information. This document is primarily concerned how to add UNOlite to Modbus/RTU network.
Hardware Interface
Buttons
Key | Description |
---|---|
Hardware reset | Push this button will trigger a power cycle. |
Factory reset
| After booting, press this button three times within 2 seconds will trigger factory reset. The values below will be restored to default:
s Modbus baudrate
s BACnet saved mac address
s Wi-Fi MQTT broker setting (Wi-Fi model)
NOTE: /t’s recommended to use a paper clip to press the keys.
Terminal block
Terminal | Description |
---|---|
V+ | Power input. For more information, please refer to production |
specification.
V-| Power input. For more information, please refer to production
specification.
A+| RS485(+) data pin. For Modbus/BACnet network.
B-| RS485(-) data pin. For Modbus/BACnet network.
__
GND
| Ground terminal. Each RS485 driver in an installation is recommended to connect to the same ground to get a common reference.
DIP switch
DIPs | Description | ON | OFF |
---|---|---|---|
1 – 6 | Refer to the later sections for the definition of each pin | n |
__
7
| BACnet mode switch. ON : BACnet mode OFF : Modbus mode| | __
n
8| RS485 terminator resistor (120 ohm)| | n
NOTE The dips should be adjusted to proper position in power off state. Adjust the dips, then power on device.
Modbus Mode
UNOlite follows Modbus over serial line specification and will run on
Modbus/RTU mode if the 7th pin is set to OFF state. The definition of the dips
in Modbus mode as listed below:
DIP | Description | ON | OFF |
---|---|---|---|
1 | Modbus slave address (check address table) | n | |
2 | Modbus slave address (check address table) | n | |
3 | Modbus slave address (check address table) | n | |
4 | Modbus slave address (check address table) | n | |
5 | Modbus slave address (check address table) | n |
- NOTE: The definitions of dip are different from Modbus mode. Please make sure which mode is chosen.
- NOTE: Pin6 is not defined in Modbus mode
Serial Configuration
UNOlite can directly connect to a controller with RS485 interface, up to 32 UNOlite devices can be joined to a Modbus serial bus.
NOTE: Suggestion to use 22AWG shielded twisted pair cable to connect devices in sequence
Default Serial Configuration:
- Baud: 9600
- Data-Bit: 8
- Parity: None
- Stop-Bit: 1
Note: perform factory reset to restore default value if the configuration is missing
Modbus Slave Address
The DIP pins 1~5 represent for binary number 0~31, pin 1 is most significant
bit (MSB) and pin 5 is least significant bit (LSB). Notice that Modbus slave
address starts from 208, therefore, UNOlite can be configured address from 208
to 239:
Modbus Slave Address Table
DIP pin| Modbus Slave
Addr
| | DIP pin| Modbus Slave
Addr
---|---|---|---|---
1| 2| 3| 4| 5| 1| 2| 3| 4| 5
↓| ↓| ↓| ↓| ↓| 208 (0xD0)| ↑| ↓| ↓| ↓| ↓| 224 (0xE0)
↓| ↓| ↓| ↓| ↑| 209 (0xD1)| ↑| ↓| ↓| ↓| ↑| 225 (0xE1)
↓| ↓| ↓| ↑| ↓| 210 (0xD2)| ↑| ↓| ↓| ↑| ↓| 226 (0xE2)
↓| ↓| ↓| ↑| ↑| 211 (0xD3)| ↑| ↓| ↓| ↑| ↑| 227 (0xE3)
↓| ↓| ↑| ↓| ↓| 212 (0xD4)| ↑| ↓| ↑| ↓| ↓| 228 (0xE4)
↓| ↓| ↑| ↓| ↑| 213 (0xD5)| ↑| ↓| ↑| ↓| ↑| 229 (0xE5)
↓| ↓| ↑| ↑| ↓| 214 (0xD6)| ↑| ↓| ↑| ↑| ↓| 230 (0xE6)
↓| ↓| ↑| ↑| ↑| 215 (0xD7)| ↑| ↓| ↑| ↑| ↑| 231 (0xE7)
↓| ↑| ↓| ↓| ↓| 216 (0xD8)| ↑| ↑| ↓| ↓| ↓| 232 (0xE8)
↓| ↑| ↓| ↓| ↑| 217 (0xD9)| ↑| ↑| ↓| ↓| ↑| 233 (0xE9)
↓| ↑| ↓| ↑| ↓| 218 (0xDA)| ↑| ↑| ↓| ↑| ↓| 234 (0xEA)
↓| ↑| ↓| ↑| ↑| 219 (0xDB)| ↑| ↑| ↓| ↑| ↑| 235 (0xEB)
↓| ↑| ↑| ↓| ↓| 220 (0xDC)| ↑| ↑| ↑| ↓| ↓| 236 (0xEC)
↓| ↑| ↑| ↓| ↑| 221 (0xDD)| ↑| ↑| ↑| ↓| ↑| 237 (0xED)
↓| ↑| ↑| ↑| ↓| 222 (0xDE)| ↑| ↑| ↑| ↑| ↓| 238 (0xED)
↓| ↑| ↑| ↑| ↑| 223 (0xDF)| ↑| ↑| ↑| ↑| ↑| 239 (0xEF)
Modbus Read Data
UNOlite supports function code both 0x03 and 0x04 to read following registers
- 0x03: read holding registers
-
0x04: read input registers
RequestSlave Address
1 byte
| Function code
1 byte
| Register
2 bytes
| Length [N]
2 bytes
| CRC16
2 bytes
Response
Slave Address
1 byte
| Function code
1 byte
| Count [2*N]
1 byte
| Data
N * 2 bytes
| CRC16
2 bytes
Sensor Measurement
Register| Name| Description
30001
|
0x0000
|
IAQ index
| Give an index according to current PM2.5, PM10, and CO2 concentration. The index also be referenced by IAQ LED:
GREEN: 0~80 YELLOW: 81~100 RED: 101~400 PURPLE: 401~
30002| 0x0001| Concentration of PM2.5| Unit: μg/m3
30003| 0x0002| Concentration of PM10| Unit: μg/m3
30004| 0x0003| Concentration of carbon
dioxide (formula CO2)
| Unit: ppm
30005| 0x0004| Concentration of total volatile
organic compound (TVOC)
| Unit: ppb
30006| 0x0005| Concentration of total volatile
organic compound (TVOC)
| Unit: μg/m3 (factor 1 ppb = 4.5 μg/m3)
30009| 0x0008| Humidity| Unit: 0.01%
30011| 0x000A| Celsius temperature| Real Temp = (Value – 4500) * 0.01
Unit: °C
30018| 0x0011| Fahrenheit temperature| Real Temp = (Value – 4500) * 0.01
Unit: °F
30020 | 0x0013 | Concentration of PM1 | Unit: μg/m3 |
---|
Sensor State
Register| Name| Description
30033
|
0x0020
|
PM2.5 sensor
|
State of sensor hardware module 0x0000: Power off or does not exist 0x0001: Sensor Ready
0x0002: Warming up 0x0003: Busy 0x00FE: CSERROR
0x00FF: FAIL
30034
|
0x0021
|
PM10 sensor
30035
|
0x0022
|
CO2 sensor
30036
|
0x0023
|
TVOC sensor
30037
|
0x0024
|
Humidity sensor
30038
|
0x0025
|
Temperature sensor
30042
|
0x0029
|
PM1 sensor
30044
|
0x002B
|
IAQ LED state
| 0x0000: LED off
0x0001: LED on
Device Information
Register| Name| Description
30145
| 0x0090-
0x009F
| Model and Product Serial Number| An ASCII string consists model name and serial
number, separated by a comma. For example: “UNO-L,2250L01F9999”
30209| 0x00D0| Main firmware version| Number 1 to 65535
0x0000: device is initializing
30257| 0x0100-
0x0102
| BT MAC address| 6 groups of two hexadecimal digits, e.g.
F2:11:8F:36:F6:93
30260| 0x0103-
0x0105
| WIFI MAC address| 6 groups of two hexadecimal digits
Modbus Write Command
UNOlite supports function code 0x06 and 0x10 to write request
0x06: write single register
Request
Address
1 byte
| Function code
1 byte
| Register
2 bytes
| Data
2 bytes
| CRC16
2 bytes
Response
Address
1 byte
| Function code
1 byte
| Register
2 bytes
| Data
2 bytes
| CRC16
2 bytes
0x10: write multiple registers
Request
Address
1 byte
| Fn. Code
1 byte
| Register
2 bytes
| Length[N]
2 bytes
| Count[2*N]
1 byte
| Data
N * 2 bytes
| CRC16
2 bytes
Response
Address
1 byte
| Function code
1 byte
| Register
2 bytes
| Length [N]
2 bytes
| CRC16
2 bytes
Modbus Examples
- Read all sensor status from device 208 (0xD0)
Request| D0 03 00 20 00 0B 17 86
---|---
Response| D0 03 16 00 01 00 01 00 01 00 01 00 01 00 01 00 FE 00 FE 00 FF 00
00 00 01 60 8F
- Read firmware version from device 208 (0xD0)
Request| D0 03 00 D0 00 01 97 B2
---|---
Response| D0 03 02 00 04 45 95 - Set rs485 serial configuration, 115200-8-N-1
Request| D0 10 00 60 00 03 06 00 01 C2 00 84 00 BB 56
---|---
Response| D0 10 00 60 00 03 92 57
Modbus Exception Response
If device receives a request message without a communication error, but cannot handle the query. It will reply with requested function code plus 0x80. Example, function code 0x3 becomes 0x83
Response format
Address 1 byte| Function code 1 byte| Code 1 bytes| CRC16
2 bytes
---|---|---|---
Code list
Code | Name |
---|---|
0x01 | ILLEGAL FUNCTION |
0x02 | ILLEGAL DATA ADDRESS |
0x03 | ILLEGAL DATA VALUE |
0x04 | SERVER DEVICE FAILURE |
0x05 | ACKNOWLEDGE |
0x06 | SERVER DEVICE BUSY |
0x08 | MEMORY PARITY ERROR |
0x0A | GATEWAY PATH UNAVAILABLE |
0x0B | GATEWAY TARGET DEVICE FAILED TO RESPOND |
Note: Please refer to “ModbUs Application_Protocol_V1_1b3” from www.modbus.org
Read User Manual Online (PDF format)