neptronic St265s S Series Line Voltage Actuators Instruction Manual
- June 3, 2024
- neptronic
Table of Contents
St265s S Series Line Voltage Actuators
Instruction Manual
ST100S ST105S ST120S ST160S ST165S ST180S ST200S ST205S ST220S ST260S ST265S ST280S
Features:
- Mounts easy on round & square shaft (with option –8).
- External clutch for manual adjustments.
- Maintenance free.
- Position indicator.
- Fail safe by Enerdrive System1 (on model 60S, 65S & 80S).
- Auxiliary switches (on model 20S & 80S).
- Reliable control for air damper applications up to 17.5 ft 2[1.6 m2 ] (seal-less damper blades; air friction-dependent).
Technical Data| ST100S| ST105S| ST120S| ST200S|
ST205S| ST220S| ST160S| ST165S| ST180S| ST260S|
ST265S| ST280S
---|---|---|---|---|---|---|---|---|---|---|---|---
Auxiliary switches| No| No| Yes (2)| No| No| Yes (2)| No| No| Yes (2)| No| No|
Yes (2)
Feedback| No| Yes| No| No| Yes| No| No| Yes| No| No| Yes| No
Power supply| 110 to 130 VAC 50/60Hz| 220 to 250 VAC 50/60Hz| 110 to 130 VAC
50/60Hz| 220 to 250 VAC 50/60Hz
Fall safe – Enerdrlve| No| Yes
Power consumption| 8 VA| 20VA Peak, 8VA
Control signal| 3 wire / 2 position, 4 wire / 3 point floating| 2 wire / 2
position, 4 wire / 3 point floating
ingress protection| IP22 equivalent to Nema type 2,
IP54 equivalent to Nema type 3R if water tight inlet
bushings (not supplied NEP617) are installed| IP22 equivalent to Nema type 2
Running time through 90°| 90 – 110 sec (Fail-safe 20-30 sec)
Torque| 70 in.lb. [8 Nm] at rated voltage
Electrical connection| 18 AWG [0.8 mm2] minimum
Inlet bushing| 2 inlet bushing of 13116 in [20.6 mm]
Angle of rotation| 0 to 90 degrees, mechanically adjustable (factory set with
90° stroke)
Direction of rotation| Reversible, Clockwise (CW) or Counterclockwise (CCW)
(factory set with CW direction)
Ambient temperature| -22°F to 122°F [-30°C to 50°C]
Storage temperature| -22°F to 122°F [-30°C to 50°C]
Relative Humidity| 5 to 95 % non condensing.
Weight| 3 lbs. [1.4 kg]
Warning: Do not press the clutch when actuator is powered
Dimensions
| Dimension| Inches| Metric (mm)
---|---|---|---
| A| 1.50| 38.
| B| 4.| 93.
| C| 6.60| 168.
D| model 00S, 05S & 20S| 3.| 77.
| model 60S, 65S & 80S| 4.| 97.
Caution
We strongly recommend that all Neptronic® products be wired to a separate
transformer and that transformer shall service only Neptronic® products. This
precaution will prevent interference with, and/or possible damage to
incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be
observed. Long wiring runs create voltage drop which may affect the actuator
performance.
ST100S/105S/120S/160S/165S/180SST200S/205S/220S/260S/265S/280S
Mechanical Installation
- Manually close the damper blades and positioned the actuator at 0º or 90º.
- Slide the actuator onto the shaft.
- Tighten the nuts on the “U” bolt to the shaft with a 8mm wrench to a torque of 60 in.lb. [6,7 Nm].
- Slide the mounting bracket under the actuator. Ensure free movement of the slot at the base of the actuator. The bracket pin must be placed in the mid distance of the slot.
- Fix the bracket to the ductwork with #8 self-tapping screws.
Wiring Diagrams
Caution: Risk of electric shock. Remove power prior to connect.
PC Board
Stroke Adjustment
To adjust the stroke, move the adjustment screws at the desired position.
Read User Manual Online (PDF format)