neptronic Rm300 Actuator Instruction Manual
- June 3, 2024
- neptronic
Table of Contents
neptronic Rm300 Actuator Instruction Manual
Feature
- Power supply high voltage 120 or 240 VAC.
- Clutch for manual adjustments.
- Maintenance free.
- Position indicator.
- Control signal fully programmable.
- Fail safe by Enerdrive System1 (on model 360 & 380).
- Auxiliary switches (on model 320 & 380).
Technical Data| TM300 TBMHV4300A| TM320 TBMHV4321A|
TM360 TBMHV4360A| TM380 TBMHV4380A| RM300
RBMHV6300A| RM320 RBMHV6321A| RM360 RBMHV6360A|
RM380 RBMHV6380A
---|---|---|---|---|---|---|---|---
Auxiliary switches| No| Yes(2)| No| Yes(2)| No| Yes(2)| No| Yes(2)
Fail safe – Enerdrive| No| Yes| No| Yes
Power consumption| 10VA| 30VA Peak, 10VA| 14VA| 30VA Peak, 14VA
Torque| 180 in.lb. [20 Nm] at rated voltage| 360 in.lb. [40 Nm] at rated
voltage
Weight| 5 lbs. [2.3 kg]| 8 lbs. [3.5 kg]
Running time through 90º| 60 to 85 sec torque dependant
Feedback| 4 to 20 mA or 2 to 10 VDC adjustable
Power supply| 28 to 32 VDC or 22 to 26 VAC, 110 to 130 VAC, 220 to 250
VAC 50/60Hz
Electrical connection| 18 AWG [0.8 mm2] minimum
Inlet bushing| 2 inlet bushing of 7/8 in [22.2 mm]
Control signal| Analog, Digital or Pulse with modulation (PWM)
programmable (factory set with Analog control signal)
Angle of rotation| 0 to 90 degrees, electronically adjustable (factory
set with 90º stroke)
Direction of rotation| Reversible, Clockwise (CW) or Counterclockwise
(CCW) (factory set with CW direction)
Ambient temperature| 0ºF to +122ºF [-18º C to +50º C]
Storage temperature| -22ºF to +122ºF [-30º C to +50º C]
Relative Humidity| 5 to 95 % non condensing.
Warning: Do not press the clutch when actuator is powered
Dimensions
Dimension | Inches | Metric (mm) |
---|---|---|
A | 5.20 | 132.1 |
B | 1.33 | 33.8 |
C | 9.13 | 231.9 |
D | 3.55 | 90.2 |
Caution
We strongly recommend that all neptronic® products be wired to a separate
transformer and that transformer shall service only neptronic® products. This
precaution will prevent interference with, and/or possible damage to
incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be
observed. Long wiring runs create voltage drop which may affect the actuator
performance.
Mechanical installation
- Manually close the damper blades and positioned the actuator at 0º or 90º.
- Slide the actuator onto the shaft.
- Tighten the nuts on the “U” bolt to the shaft with a 10mm wrench to a torque of 150 in.lb. [17 Nm].
- Slide the mounting bracket under the actuator. Ensure free movement of the slot at the base of the actuator. The bracket pin must be placed in the mid distance of the slot.
- Fix the bracket to the ductwork with #8 self-tapping screws.
Wiring Diagrams
For 2 to 10 VDC output feedback
For any of above wiring configurations, connect one of the supplied 500 ohm
resistors between pins 1 and 5 of TB4.
For 24 VAC or 30 VDC supply
For any of above wiring configuration, do not connect on TB1. Wire 24 VAC or
30 VDC on pin 2 of TB4.
PC Board
Stroke adjustment – No control signal change
-
Apply power and, wait for at least 10 seconds.
-
Press and release the reset button to start the auto-stroke process.
The LED should be illuminated.-
First option:
The actuator will then travel in both directions to find it’s limit and position itself according to the demand.
The LED will extinguish, the process is complete. -
Second option:
When the desired end position is reached, press and release the reset button. The actuator will now return back to its original position. (you can also press and release the reset button when It’s reaches the original position)
The LED will extinguish, the process is complete.
-
Programming – Change of control signal
-
Remove power and put all dip switches “OFF”. (factory preset).
-
Apply power and, within 10 seconds, press and release the reset button. The LED should be blinking.
-
Select the control signal with dip switches:
-
Digital (On/Off or 3 point floating)
move switch No1 “ON” and then “OFF”. -
PWM
move switch No2 “ON” and then “OFF”. -
Analog (factory preset)
move switch No3 “ON” and then “OFF”.
-
-
Stroke adjustment
see the stroke adjustment section above
Note, If PWM mode is selected:
- Time base : When programming is done,
if switch No3 is “on” time base is 0.1 to 5 sec. (resolution 20 msec.)
if switch No3 is “off” time base is 0.1 to 25 sec. (resolution 100 msec.) - For 5 sec. time base, we strongly recommend a switch common connection for better position stability.
- Switch 24 VAC: Triac or dry contact, 40mA maximum switching current.
- Switch common: NPN transistor, SCR, Triac or dry contact 75mA maximum switching current
Feedback selection (CCW direction)
To select CCW direction put switch No1 “ON”.
In Analog or 3 point floating mode you can program the feedback control.
If switch No3 is “OFF”:
The feedback control is automatically reverse to 4 to 20 mA for 90 to 0
degrees.
If switch No3 is “ON”:
The feedback control is to 20 to 4 mA for 90 to 0 degrees
Zero and span calibration
This feature is applicable to analog control signal only.
-
Remove power and put all dip switches “OFF”. (factory preset).
-
Apply power and, within 10 seconds press and hold the reset button until the LED blinks.
The Zero and span calibration process then start. -
Release the reset button. The LED is now constantly illuminated.
-
Apply new minimum voltage.
It can be any value between 0 to 7 VDC, with an external 0 to 10 volt supply (ex: MEP). -
Press and release the reset button to memorize the new minimum voltage. The LED blinks.
-
Apply new maximum voltage.
It can be any value between 3 to 10 VDC, this value should be greater than the new minimum value. -
Press and release the reset button to memorize the new maximum voltage. The LED blinks.
The Zero and span calibration process is complete
Note: To reset zero and span to 2 to 10 VDC (factory value). You just have to re-select the analog control signal mode, see Programming.