invt IVC3 Series Programmable Logic Controller User Manual
- June 3, 2024
- invt
Table of Contents
Series Programmable Logic Controller
User Manual
IVC3 Series Programmable Logic Controller
Item | General-purpose IVC3 |
---|---|
Program capacity | 64 ksteps |
High-speed input | 200 kHz |
High-speed output | 200 kHz |
Power-outage memory | 64 kB |
CAN | The CANopen DS301 protocol (master) supports a maximum of 31 stations, 64 |
TxPDOs, and 64 RxPDOs. The CANopen DS301 protocol (slave) supports 4 TxPDOs
and 4 RxPDOs.
Terminal resistor: Equipped with a built-in DIP switch Station number setting:
Set by using a DIP switch or program
Modbus TCP| Supporting master and slave stations
IP address setting: Set by using a DIP switch or program
Serial communication| Communication mode: R8485
Max. baud rate of PORT1 and PORT2: 115200 Terminal resistor: Equipped with a
built-in DIP switch
USB communication| Standard: USB2.0 Full Speed and MiniB interface Function:
Program upload and download, monitoring, and upgrade of underlying systems
Interpolation| Two-axis linear and arc interpolation (supported by board
software V2.0 or later)
Electronic cam| Supported by board software V2.0 or later
Special extension
module| Max. total number of special extension modules: 8
Customer service center
Shenzhen INVT Electric Co., Ltd.
Product quality feedback sheet
User name| | Telephone|
---|---|---|---
User address| | Postal code|
Product name and model| | Installation date|
Machine No.|
Product appearance or structure|
Product performance|
Product package|
Product material|
Quality in use|
Improvement comments or suggestions|
Address: INVT Guangming Technology Building, Songbai Road, Matian,
Guangming District, Shenzhen, China _ Tel: +86 23535967
Product introduction
1.1 Model description
Figure 1-1 describes the product model.
1.2 Appearance and structure
Figure 1-2 shows the appearance and structure of an IVC3 series main module
(using IVC3-1616MAT as an example).
The bus socket is used to connect extension modules. The mode selection switch
provides three options: ON, TM, and OFF.
1.3 Terminal introduction
The following figures show the terminal arrangement of IVC3-1616MAT.
Input terminals:
Output terminals:
Power supply specifications
Table 2-1 describes the specifications of the built-in power supply of the
main module and those of the power that the main module can supply to
extension modules.
Table 2-1 Power supply specifications
Item| Unit| Min.
value| Typical
value| Max.
value| Remarks
---|---|---|---|---|---
Input voltage range| V AC| 85| 220| 264| Voltage range for proper start and
operation
Input current| A| /| /| 2.| 90 V AC input, full-load output
Rated output current| 5V/GND| mA| /| 1000| /| The capacity is the sum of the
internal consumption of the main module and the load of the extension modules.
The maximum output power is the sum of the full load of all modules, that is,
35 W. The natural cooling mode is adopted for the module.
24V/GND| mA| /| 650| /
24V/COM| mA| /| 600| /
Digital input/output characteristics
3.1 Input characteristics and signal specifications
Table 3-1 describes the input characteristics and signal specifications.
Table 3-1 Input characteristics and signal specifications
Item| High-speed input
terminals XO to X7| Common input terminal
---|---|---
Signal input mode| Source-type or sink-type mode. You can select the mode
through the “S/S” terminal.
Electrical
paramete
rs| Detection
voltage| 24V DC
Input| 1 kf)| 5.7 k0
Input
switched on| The The resistance of the external circuit is lower than 400 0.|
The resistance of the external circuit is lower than 400 0.
Input
switched off| The resistance of the external circuit is higher than 24 ka| The
resistance of the external circuit is higher than 24 kf2.
Filtering
function| Digital
filtering| X0—X7: The filtering time can be set through programming, and the
allowable range is 0 to 60 ms.
Hardware
filtering| Hardware filtering is adopted for ports except the XO to X7, and
the filtering time is about 10 ms.
High-speed function| Ports XO to X7 can implement multiple functions including
high-speed counting, interrupting, and pulse capture.
The maximum touting frequency of XO to X7 is 200 kHz.
The maximum frequency of the high-speed input port is limited. If the input
frequency exceeds the limit, the counting may be incorrect or the system fails
to run properly. You need to select a proper external sensor.
The PLC provides the “S/S” port for selecting the signal input mode. You can
select the source-type or sink-type mode. Connecting “S/S” to “+24V” indicates
that you select the sink-type input mode, and then an NPN-type sensor can be
connected. If “S/S” is not connected to “+24V”, it indicates that the source-
type input mode is selected. See Figure 3-1 and Figure 3-2.
Figure 3-1 Source-type input wiring diagram
Figure 3-2 Sink-type input wiring diagram
3.2 Output characteristics and signal specifications
Table 3-2 describes the output electrical specifications.
Table 3-2 Output electrical specifications
Item | Output specification |
---|---|
Output mode | Transistor output |
The output is connected when the output state is ON, and it is disconnected
when the output state is OFF.
Circuit insulation| Optocoupler insulation
Action indication| The indicator is on when the optocoupler is drived.
Circuit power supply voltage| 5-24 V DC
The polarities are differentiated.
Open-circuit leakage current| Lower than 0.1 mA/30 V DC
Item| Output specification
---|---
Min. load| 5 mA (5-24 V DC)
Max. output
current| Resistive load| Total load of the common terminals:
Common terminal of the 0.3 A/1-point group
Common terminal of the 0.8 N4-point group
Common terminal of the 1.6 N8-point group
Inductive load| 7.2 W/24 V DC
Lamb load’| 0.9 W/24 V DC
Respo nse time| OFF-00N| YO—Y7: 5.1 ps/higher than 10 mA Others: 50.5
ms/higher than 100mA
ON—)OFF
Max output frequency| Y0—Y7: 200 kHz (maximum)
Common output terminal| One common terminal can be shared by a maximum of 8
ports, and all the common terminals are isolated from each other. For details
about common terminals of different models, see the terminal arrangement.
Fuse protection| No
- The transistor output circuit is equipped with a built-in voltage-stabilizing tube to prevent the counter-electromotive force caused when the inductive load is disconnected. If the capacity of the load exceeds the specification requirement, you need to add an external freewheeling diode.
- High-speed transistor output involves distributed capacitance. Therefore, if the machine runs at 200 kHz, you need to ensure that the conducted current is larger than 15 mA to improve the output characteristc curve, and the device connected to it can be connected to a resistor in parallel mode to increase the load current.
3.3 Input/output connection instances
Input connection instance
Figure 3-3 shows the connection of IVC3-1616MAT and IVC-EH-O808ENR, which is
an instance of implementing simple positioning control. The position signals
obtained by the encoder can be detected by the XO and X1 high-speed counting
terminals. The position switch signals that require quick response can be
connected to the high-speed terminals X2 to X7. Other user signals can be
distributed among the input terminals.
Output connection instance
Figure 3-4 shows the connection of IVC3-1616MAT and IVC-EH-O808ENR. The output
groups can be connected to different signal voltage circuits, that is, the
output groups can operate in circuits of different voltage classes. They can
be connected only to DC circuits. Pay attention to the direction of the
current when connecting them.
Communication guide
4.1 Serial communication
The IVC3 series main module provides three asynchronous serial communication
ports, namely PORTO, PORT1, and PORT2. They support the baud rates of 115200,
57600, 38400, 19200, 9600, 4800, 2400, and 1200 bps. PORTO adopts the RS232
level and the Mini DIN8 socket. Figure 4-1 describes the pin definition of
PORTO.
Figure 4-1 Position of the mode selection switch and definition of PORTO pins
As a specialized interface for user programming, PORTO can be forcibly
switched to the programming port protocol through the mode selection switch.
Table 4-1 describes the mapping between PLC running states and PORTO running
protocols.
Table 4-1 Mapping between PLC running states and PORTO running protocols
Mode selection switch setting | State | PORTO running protocol |
---|---|---|
ON | Running | Depend on the user program and its system configuration. It can |
be the programming port, Modbus, free-port, or N:N network protocol.
TM (ON→TM)| Running| Forcibly switched to the programming port protocol.
TM (OFF→TM)| Stopped
OFF| Stopped| If the free-port protocol is used in the system configuration of
the user program, PORTO is automatically switched to the programming port
protocol after the PLC is stopped. Otherwise, the protocol set in the system
is not switched.
4.2 RS485 communication
Both PORT1 and PORT2 are RS485 ports that can be connected to devices with
communication functions, such as inverters or HMIs. These ports can be used to
control multiple devices in networking mode through the Modbus, N:N, or free-
port protocol. They are terminals fastened with screws. You can make the
communication signal cables by yourself. It is recommended that you use
shielded twisted pairs (STPs) to connect the ports.
Table 4-2 RS485 communication characteristics
| Item| Characteristic
---|---|---
RS485
communication| Communication port| 2
Socket mode| PORT1, PORT2
Baud rate| 115200, 57600, 38400, 19200, 9600, 4800, 2400, 1200bps
Signal level| RS485, half duplex, non-isolation
Supported protocol| Modbus master/slave station protocol, free communication
protocol, N:N protocol
Terminal resistor| Equipped with a built-in DIP switch
4.3 CANopen communication
Table 4-3 CAN communication characteristics
Item | Characteristic |
---|---|
Protocol | Standard CANopen protocol DS301v4.02 that can be applied for master |
and slave stations, supporting the NMT service, Error Control protocol, SDO
protocol, SYNC, Emergency, and EDS file configuration
Master station| Supporting 64 TxPDOs, 64 RxPDOs, and a maximum of 31 stations.
The data exchange area (D component) is configurable.
Slave station| Supporting 4 TxPDOs and 4 RxPDOs Data exchange area:
SD500—SD531
Socket mode| Pluggable terminal of 3.81 mm
Terminal resistor| Equipped with a built-in DIP switch
---|---
Station setting| No.| Set through bits 1 to 6 of the DIP switch or through the
program
Baud rate| | Set through bits 7 to 8 of the DIP switch or through the program
Use STPs for CAN communication. If multiple devices are involved in
communication, ensure that the GND terminals of all the devices are connected
and the terminal resistors are set to ON.
4.4 Ethernet communication
Table 4-4 Ethernet communication characteristics
| Item| Characteristic
---|---|---
Ethernet| Protocol| Supporting the Modbus TCP and programming port protocols
IP address setting| The last segment of the IP address can be set through the
DIP switch or an upper computer
Slave station connection| A maximum of 16 slave stations can be connected
simultaneously.
Master station connection| A maximum of 4 master stations can be connected
simultaneously.
Socket mode| RJ45
Function| Program upload/download, monitoring, and user program upgrade
Default IP address| 192.168.1.10
MAC address| Set in factory. See SD565 to SD570.
Installation
IVC3 Series PLCs are applicable to scenarios with installation environments of
standard Il and pollution level of 2.
5.1 Dimensions and specifications
Table 5-1 describes the dimensions and specifications of IVC3 series main
modules.
Table 5-1 Dimensions and specifications
Model | Width | Depth | Height | Net weight |
---|---|---|---|---|
IVC3-1616MAT | 167 mm | 90 mm | 90 mm | 740 g |
IVC3-1616MAR
5.2 Installation modes
Using DIN slots
Generally, the PLCs are installed by using DIN slots with a width of 35 mm, as
shown in Figure 5-1.
The specific installation steps are as follows:
- Fix the DIN slot horizontally on the installation backplate.
- Pull out the DIN slot clamping buckle from the bottom of the module.
- Mount the module onto the DIN slot.
- Press the clamping buckle back to where it was to lock the fix the module.
- Use the stoppers of the DIN slot to fix the two ends of the module, preventing it from sliding.
These steps can also be used to install other PLCs of the IVC3 series by using
DIN slots.
Using screws
For scenarios where large impact may occur, you can install the PLCs by using
screws. Put the fastening screws (M3) through the two screw holes on the
housing of the PLC and fix them on the backplate of the electrical cabinet, as
shown in Figure 5-2.
5.3 Cable connection and specifications
Power cable and grounding cable connection
Figure 5-3 shows the connection of the AC and auxiliary power supplies.
The anti-electromagnetic interference capability of the PLCs can be improved by configuring reliable grounding cables. When installing a PLC, connect the power supply terminal **** to the ground. It is recommended that you use connection wires of AWG12 to AWG16 and try to shorten the wires, and that you configure independent grounding and keep the grounding cables away from those of other devices (especially those generating strong interference), as shown in Figure 5-4.
Cable specifications
For the wiring of the PLC, it is recommended that you use multi-stranded
copper wire and prepare insulated terminals to ensure the wiring quality.
Table 5-2 describes the recommended wire cross-sectional areas and models.
Table 5-2 Recommended cross-sectional areas and models
Cable| Coss-sectional area of wire| Recommended wire model|
Cmpatible wiring terminals and heat-shrinkable tubing
---|---|---|---
AC power, N)
cable (L| 1 .0-2.0mm2| AWG12, 18| H1.5/14 preinsulated tube-like terminal, or
hot tin-coated cable terminal
Grounding cable ****| 2•Omm2| AWG12| H2.0/14 preinsulated tube-like terminal,
or hot tin-coated cable terminal
Input signal
cable (X)| 0.8-1.0mm2| AWG18, 20| UT1-3 or OT1-3 cold-pressed terminal, 03 or
(D4 heat-shrinkable tubing
Output signal cable (Y)| 0.8-1.0mm2| AWG18, 20
Fix the processed cable terminals onto the wiring terminals of the PLC by
using screws. Pay attention to the positions of the screws. The tightening
torque for the screws is 0.5 to 0.8 Nm, which can be used to complete reliable
connection without damaging the screws.
Figure 5-5 shows the recommended cable preparation mode.
Waming
Do not connect transistor output to AC circuits, such as a circuit of 220 V
AC. Strictly follow the electrical parameters to design the output circuits.
Ensure that no overvoltage or overcurrent occurs.
Power-on, operation, and routine maintenance
6.1 Power-on and operation
After the wiring is complete, check all the connections. Ensure that no
foreign matters have dropped inside the housing and heat dissipation is in
good conditions.
-
Power on the PLC.
The POWER indicator of the PLC is on. -
Start the Auto Station software on the PC and download the compiled user program to the PLC.
-
After the program is downloaded and verified, set the mode selection switch to ON.
The RUN indicator is on. If the ERR indicator is on, it indicates that errors occur on the user program or the system. In this case, rectify the errors by referring to the instructions in the /VC Series Small-sized PLC Programming Manual. -
Power on the PLC external system to perform commissioning on the system.
6.2 Routine maintenance
Pay attention to the following aspects when performing routine maintenance and
inspection:
- Ensure that the PLC operates in a clean environment, preventing foreign matters or dust from dropping into the machine.
- Keep the PLC in good ventilation and heat dissipation conditions.
- Ensure that the wiring is properly performed and all the wiring terminals are well fastened.
Notice
-
The warranty covers only the PLC machine.
-
The warranty period is _ 18 months. We provide free-of-charge maintenance and repairs for the product if it is faulty or damaged during proper operation within the warranty period.
-
The warranty period starts from the ex-factory date of the product.
The machine No. is the only basis for determining whether the machine is within the warranty period. A device without the machine No. is deemed out-of- warranty. -
Maintenance and repair fees are charged in the following scenarios even the product is within the warranty period: Faults are caused due to misoperations. Operations are not performed following the instructions provided in the manual.
The machine is damaged due to causes such as fire, flood, or voltage exceptions.
The machine is damaged due to improper use. You use the machine to perform some unsupported functions. -
The service fees are calculated based on the actual fees. If there is a contract, the provisions stated in the contract prevail.
-
Keep this warranty card. Show it to the maintenance unit when you seek maintenance services.
-
Contact the local dealer or directly contact our company if you have any questions.