INVT Electric IPE300 Series Engineering VFD User Manual
- June 13, 2024
- INVT Electric
Table of Contents
INVT Electric IPE300 Series Engineering VFD
Product Information
The IPE300 series engineering VFD (Booksize) is a variable-frequency drive
that is designed to meet diversified customer demands. It offers abundant
expansion cards including PLC programmable card, communication card, and I/O
expansion card, allowing for various functions as needed. Each VFD can
accommodate up to two expansion cards. The VFD supports Modbus, CANopen,
PROFIBUS-DP, PROFINET, Ethernet/IP, and other international mainstream
communication methods, ensuring seamless connectivity with the host controller
and DCS control system.
The VFD utilizes a high power density design and some models come with a
built-in DC reactor and braking unit to save installation space. It is
designed with overall EMC (Electromagnetic Compatibility) considerations to
meet low noise and low electromagnetic interference requirements, enabling it
to operate reliably in challenging grid, temperature, humidity, and dust
conditions.
Product Usage Instructions
This manual provides comprehensive instructions on how to install, wire, set parameters for, diagnose and troubleshoot faults for, and maintain the IPE300 series engineering VFD (Booksize). It also includes relevant precautions that should be followed. Before installing the VFD, it is important to carefully read through this manual to ensure proper installation and optimal performance with all the powerful functions.
If the end user is a military unit or the product is used for weapon
manufacturing, it is necessary to comply with relevant export control
regulations in the Foreign Trade Law of the People’s Republic of China and
complete any necessary formalities.
Please note that the manual is subject to change without prior notice.
Manuals Included
- Name: IPE300 series engineering VFD
- Name (booksize): IPE300 series engineering VFD (booksize)
- Order No.: 66001-00812
- Order No. (booksize): 66001-01052
For detailed information on safety precautions, please refer to the manual’s content section.
IPE300 series engineering VFD (Booksize)
No.
Change description
1 First release.
Deleted the content related to the expansion 2
card EC-PC502-00.
Version V1.0 V1.1
Change history Release date November 2022
July 2023
IPE300 series engineering VFD (Booksize)
Preface
Preface
Thanks for choosing IPE300 series variable-frequency drive (VFD) of booksize.
If not otherwise specified in this manual, the VFD always indicates IPE300 series VFD in booksize design, which is a single-drive system oriented to engineering applications. The VFDs feature high reliability, usability, maintainability, environment adaptability, and wide power range, provide enriched functions, and support flexible configuration. The VFD can be widely used in equipment driving with demanding reliability and performance requirements in the metallurgy, petroleum, chemical, building material, HVAC water supply, municipal engineering, paper making, electric power, power source industries.
In order to meet diversified customer demands, the VFD provides abundant expansion cards including PLC programmable card, communication card, and I/O expansion card to achieve various functions as needed. Each VFD can be installed with two expansion cards at most.
The VFD supports Modbus, CANopen, PROFIBUS-DP, PROFINET, Ethernet/IP and other international mainstream communication methods, connecting seamless with the host controller and DCS control system.
The VFD uses high power density design. Some models carry built-in DC reactor and braking unit to save installation space. Through overall EMC design, it can satisfy the low noise and low electromagnetic interference requirements to cope with challenging grid, temperature, humidity and dust conditions, thus greatly improving product reliability.
This manual instructs you how to install, wire, set parameters for, diagnose and remove faults for, and maintain the VFD, and also lists related precautions. Before installing the VFD, read through this manual carefully to ensure the proper installation and running with the excellent performance and powerful functions into full play.
If the end user is a military unit or the product is used for weapon manufacturing, please comply with relevant export control regulations in the Foreign Trade Law of the People’s Republic of China, and complete necessary formalities.
The manual is subject to change without prior notice.
Manuals for IPE300 series engineering VFD include:
Name IPE300 series engineering VFD IPE300 series engineering VFD (booksize)
Order No. 66001-00812 66001-01052
IPE300 series engineering VFD (Booksize)
Safety precautions
1 Safety precautions
1.1 What this chapter contains
Read this manual carefully and follow all safety precautions before moving,
installing, operating and servicing the product. Otherwise, equipment damage
or physical injury or death may be caused.
We shall not be liable or responsible for any equipment damage or physical
injury or death caused due to your or your customers’ failure to follow the
safety precautions.
1.2 Safety definition
Danger: Severe personal injury or even death can result if related
requirements are not followed.
Warning: Personal injury or equipment damage can result if related
requirements are not followed.
Note: Actions taken to ensure proper running.
Trained and qualified professionals: People operating the equipment must have
received professional electrical and safety training and obtained the
certificates, and must be familiar with all steps and requirements of
equipment installing, commissioning, running and maintaining and capable to
prevent any emergencies.
1.3 Warning symbols
Warnings caution you about conditions that can result in severe injury or
death and/or equipment damage and advice on how to prevent dangers. The
following table lists the warning symbols in this manual.
Symbol Danger Warning Forbid
Name
Description
Severe personal injury or even death can Danger
result if related requirements are not followed.
Personal injury or equipment damage can Warning
result if related requirements are not followed.
Electrostati The PCBA may be damaged if related
c discharge requirements are not followed.
Abbreviation
Hot Note
Hot sides Do not touch. The VFD base may become hot.
Electric shock
Read manual
Note
As high voltage still presents in the bus capacitor after power off, wait for at least five minutes (or 15 min / 25 min, depending on the warning symbols on the machine) after power off to prevent electric shock. Read the operation manual before operating the equipment. Actions taken to ensure proper running.
Note
-1-
IPE300 series engineering VFD (Booksize)
Safety precautions
1.4 Safety guidelines
Only trained and qualified professionals are allowed to carry out related
operations. Do not perform wiring, inspection or component replacement when power supply
is applied. Ensure all the input power supplies have been disconnected before
wiring or inspection, and wait for at least the time designated on the VFD or until
the DC bus voltage is less than 36V. The minimum waiting time is listed in the
following.
VFD model
Minimum waiting time
380V 00110132
5 minutes
380V 01600355
15 minutes
380V 0400 and higher
25 minutes
Do not refit the VFD unless authorized; otherwise fire, electric shock or other
injury may result.
The base may become hot when the machine is running. Do not touch.
Otherwise, you may get burnt.
The electrical parts and components inside the VFD are electrostatic sensitive.
Take measurements to prevent electrostatic discharge when performing related
operations.
1.4.1 Delivery and installation Do not install the VFD on inflammables. In
addition, prevent the VFD from contacting or adhering to inflammables. Connect
the optional braking parts (such as braking resistors, braking units or
feedback units) according to the wiring diagrams. Do not run the VFD if it is
damaged or incomplete. Do not contact the VFD with damp objects or body parts.
Otherwise, electric shock may result.
Note:
1. Select appropriate tools for VFD delivery and installation to ensure the
safe and proper running and avoid physical injury or death. To ensure personal
safety, take mechanical protective measures like wearing safety shoes and
working uniforms.
2. Protect the VFD against physical shock or vibration during the delivery
and installation.
3. Do not carry the VFD only by its front cover as the cover may fall off.
4. The installation site must be away from children and other public places.
5. Use the VFD in proper environments. (For details, see “Installation
environment”.) 6. Prevent the screws, cables and other conductive parts from
falling into the VFD.
-2-
IPE300 series engineering VFD (Booksize)
Safety precautions
7. As leakage current of the VFD during running may exceed 3.5mA, ground
properly and ensure the grounding resistance is less than 10. The conductivity
of PE grounding conductor is the same as that of the phase conductor (The
cross-sectional area of the PE grounding conductor for 30kW and higher models
can be reduced).
8. R, S and T are the power input terminals, and U, V and W are the output
motor terminals. Connect the input power cables and motor cables properly;
otherwise, damage to the VFD may occur.
1.4.2 Commissioning and running
Cut off all power supplies connected to the VFD before terminal wiring, and
wait for at least the time designated on the VFD after disconnecting the power
supplies.
High voltage presents inside the VFD during running. Do not carry out any
operation on the VFD during running except for keypad setup. The VFD may start
up by itself when power-off restart is enabled (P01.21=1). Do not get close to
the VFD and motor.
The VFD cannot be used as an “Emergency-stop device”. The VFD cannot act as an
emergency brake for the motor; it is a must to install a
mechanical braking device. During driving a permanent magnet SM, besides
above-mentioned items, the
following work must be done before installation and maintenance: a) All input
power supplies have been disconnected, including the main power and
control power. b) The permanent-magnet SM has been stopped, and the voltage on
output end of
the VFD is lower than 36V. c) After the permanent-magnet SM has stopped, wait
for at least the time
designated on the VFD, and ensure the voltage between + and – is lower than
36V. d) During operation, it is a must to ensure the permanent-magnet SM
cannot run again by the action of external load; it is recommended to install
an effective external braking device or cut off the direct electrical
connection between the permanent-magnet SM and the VFD.
Note: 1. Do not switch on or switch off the input power supplies of the VFD
frequently. 2. If the VFD has been stored for a long time without being used,
check the capacitors, perform
capacitor reforming (see “Maintenance”), and carry out pilot run for the VFD
before the use. 3. Close the VFD front cover before running; otherwise,
electric shock may occur.
-3-
IPE300 series engineering VFD (Booksize)
Safety precautions
1.4.3 Maintenance and component replacement
Only trained and qualified professionals are allowed to perform maintenance,
inspection, and component replacement for the VFD.
Cut off all power supplies connected to the VFD before terminal wiring, and
wait for at least the time designated on the VFD after disconnecting the power
supplies.
During maintenance and component replacement, take measures to prevent screws,
cables and other conductive matters from falling into the internal of the VFD.
Note:
1. Use proper torque to tighten screws.
2. During maintenance and component replacement, keep the VFD and its parts and components away from combustible materials and ensure they have no combustible materials adhered.
3. Do not carry out insulation voltage-endurance test on the VFD, or measure the control circuits of the VFD with a megohmmeter.
4. During maintenance and component replacement, take proper anti-static
measures on the VFD and its internal parts.
1.4.4 Disposal
The VFD contains heavy metals. Dispose of a scrap VFD as industrial waste.
Dispose of a scrap product separately at an appropriate collection point but
not
place it in the normal waste stream.
-4-
IPE300 series engineering VFD (Booksize)
Quick startup
2 Quick startup
2.1 What this chapter contains
This chapter introduces the basic installation and commissioning rules that
you need to follow to realize quick installation and commissioning.
2.2 Unpacking inspection
Check the following after receiving the product.
1. Whether the packing box is damaged or dampened. If any problems are found,
contact the local INVT dealer or office.
2. Whether the model identifier on the exterior surface of the packing box is
consistent with the purchased model. If any problems are found, contact the
local INVT dealer or office.
3. Whether the interior surface of the packing box is abnormal, for example,
in wet condition, or whether the enclosure of the VFD is damaged or cracked.
If any problems are found, contact the local INVT dealer or office.
4. Whether the VFD nameplate is consistent with the model identifier on the
exterior surface of the packing box. If any problems are found, contact the
local INVT dealer or office.
5. Whether the accessories (including the manual, keypad, and expansion card)
inside the packing box are complete.If any problems are found, contact the
local INVT dealer or office.
2.3 Checking before use
Check the following before using the VFD.
1. Mechanical type of the load to be driven by the VFD to verify whether the
VFD will be overloaded during work. Whether the power class of the VFD needs
to be increased.
2. Whether the actual running current of the motor is less than the rated
current of the VFD. 3. Whether the control accuracy required by the load is
the same as that is provided by the VFD. 4. Whether the grid voltage is
consistent with the rated voltage of the VFD. 5. Check whether expansion cards
are needed for selected functions.
2.4 Environment checking
Check the following before installing the VFD:
1. Whether the actual ambient temperature exceeds 40°C. When the temperature
exceeds 40°C, derate 1% for every increase of 1°C. Do not use the VFD when the
ambient temperature exceeds 50°C.
Note: When the VFD is built in a cabinet, the ambient temperature is the
temperature of air in the cabinet.
-5-
IPE300 series engineering VFD (Booksize)
Quick startup
2. Whether the actual ambient temperature is lower than -10°C. If the
temperature is lower than -10°C, use heating devices.
Note: When the VFD is built in a cabinet, the ambient temperature is the
temperature of air in the cabinet. 3. Whether the altitude of the application
site exceeds 1000m. When the installation site altitude
exceeds 1000 m, derate 1% for every increase of 100m. 4. Whether the actual
environment humidity exceeds 90% or condensation occurs. If yes, take
additional protective measures. 5. Whether there is direct sunlight or
biological invasion in the environment where the VFD is to
be used. If yes, take additional protective measures. 6. Whether there is dust
or inflammable and explosive gas in the environment where the VFD is
to be used. If yes, take additional protective measures.
2.5 Checking after installation
Check the following after the VFD installation is complete.
1. Whether the input power cables and motor cables meet the current-carrying
capacity requirements of the actual load.
2. Whether correct accessories are selected for the VFD, the accessories are
correctly and properly installed, and the installation cables meet the
capacity carrying requirements of all components (including the reactor, input
filter, output reactor, output filter, DC reactor, braking unit and braking
resistor).
3. Whether the VFD is installed on non-flammable materials and the heat-
radiating accessories (such as the reactor and braking resistor) are away from
flammable materials.
4. Whether all control cables and power cables are run separately and Whether
the routing complies with EMC requirement.
5. Whether all grounding systems are properly grounded according to the
requirements of the VFD.
6. Whether all the installation clearances of the VFD meet the requirements
in the manual. 7. Whether the installation mode conforms to the instructions
in the operation manual. It is
recommended that the VFD be installed uprightly. 8. Whether the external
connection terminals of the VFD are tightly fastened and the torque is
appropriate. 9. Whether there are screws, cables, or other conductive items
left in the VFD. If yes, get them
out.
-6-
IPE300 series engineering VFD (Booksize)
Quick startup
2.6 Basic commissioning
Complete the basic commissioning as follows before the actual use of the VFD:
1. According to the actual motor parameters, select the motor type, set motor
parameters, and select the VFD control mode.
2. Check whether autotuning is required. If possible, de-couple the VFD from
the motor load to start dynamic parameter autotuning. If the VFD cannot be de-
coupled from the load, perform static autotuning.
3. Adjust the ACC/DEC time according to the actual work condition of the
load. 4. Perform device commissioning by means of jogging and check whether
the motor rotational
direction is correct. If not, change the rotation direction by swapping any
two phase wires of the motor. 5. Set all control parameters and then perform
actual run.
-7-
IPE300 series engineering VFD (Booksize)
Product overview
3 Product overview
3.1 What this chapter contains
This chapter mainly introduces the operation principles, product features,
layouts, nameplates and model designation rules.
3.2 Basic principles
The VFD is used to control asynchronous AC induction motor and permanent- magnet synchronous motor. The following figure shows the main circuit diagram of the VFD unit.
The rectifier converts 3PH AC voltage into DC voltage, and the capacitor bank of intermediate circuit stabilizes the DC voltage. The inverter converts DC voltage into AC voltage that can be used by an AC motor. When the circuit voltage exceeds the maximum limit value, external braking resistor will be connected to intermediate DC circuit to consume the feedback energy.
PB
R
U
S
V
T
W
PE
PE
–
Figure 3-1 380V (0018 and lower) main circuit diagram
PB
R
U
S
V
T
W
PE
PE
–
Figure 3-2 380V (00220045) main circuit diagram
R
U
S
V
T
W
PE
PE
–
Figure 3-3 380V (0055 and higher) main circuit diagram
-8-
IPE300 series engineering VFD (Booksize)
Product overview
The VFD cabinet is a product that integrates circuit breakers, contactors, input reactors, output reactors, and other peripheral accessories into a cabinet on the basis of the VFD unit. The following figure shows the main circuit diagram.
1
8
R S T
2 9
4 3
DC+ 5
6 7
U V W
DC-
PE 10
Figure 3-4 Cabinet main circuit diagram
No.
Name
Description
To switch the circuit on and off, and automatically cut off the circuit
1
Breaker
to protect the power supply and VFD in case of abnormality.
2
AC input reactor To suppress AC voltage and current harmonics.
3
Rectifier
To convert AC current to DC current.
4
Buffer component To prevent excessive impulse current at power-up.
Capacitor To stabilize the DC voltage, and filter out the AC part from the DC
5
component voltage.
6
Inverter
To convert DC current to AC current.
7
AC output reactor To suppress peak voltage to protect the motor and VFD.
8
Contactor To switch the circuit on and off, optional.
9
Input filter To suppress harmonics to reduce interference to the grid, optional.
To transfer excess energy to the braking resistor at dynamic
10
Braking unit
braking, optional.
Note: Only one of the input filter and the braking unit can be selected. If
you need both, please contact INVT.
3.3 Product specifications
Description
Specifications
Input voltage (V) AC 3PH 380V(-15%) 440V(+10%); Rated voltage: 380V
Power input Input current (A) See section “Product ratings”.
Input frequency (Hz) 50Hz or 60Hz; Allowed range: 4763Hz
Output voltage (V) 0Input voltage (V)
Power
Output current (A) See section “Product ratings”.
output
Output power (kW) See section “Product ratings”.
Output frequency (Hz) 0400Hz
-9-
IPE300 series engineering VFD (Booksize)
Product overview
Description
Specifications
Control mode
Space voltage vector control, and sensorless vector control (SVC)
Motor type
Asynchronous motor (AM) and permanent magnetic synchronous motor (SM)
Speed ratio
Asynchronous motor (AM): 1:200 (SVC), synchronous motor (SM): 1:20 (SVC)
Technical control
performance
Speed control accuracy
Speed fluctuation Torque response
± 0.2% (SVC)
± 0.3% (SVC) < 20ms (SVC)
Torque control accuracy
10% (SVC)
Starting torque
For AMs: 0.25Hz/150% (SVC) For SMs: 2.5Hz/150% (SVC)
150% for 1 minute (for the G type) Overload capacity
110% for 1 minute (for the P type)
Settings can be implemented through digital, analog, pulse
Frequency setting method
frequency, multi-step speed running, simple PLC, PID, Modbus communication, Profibus communication and so on. Settings can be combined and the setting channels can be
switched.
Running control performance
Automatic voltage regulation
Fault protection
The output voltage can be kept constant although the grid voltage changes. More than 30 protection functions, such as protection against overcurrent, overvoltage, undervoltage,
overtemperature, phase loss, and overload
Used to implement impact-free smooth startup for rotating
motors Speed tracking restart
Note: The function is available only for the 0011 and
higher VFD models.
Terminal analog input No more than 20mV
resolution
Peripheral interface
Terminal digital input No more than 2ms
resolution
Analog input
Two inputs; AI1: 010V/020mA; AI2: -1010V
Analog output Two outputs. AO0, AO1: 010V/020mA
Four regular inputs; max. frequency: 1kHz; internal
Digital input
impedance: 3.3k
Two high-speed inputs. Max. frequency: 50kHz
-10-
IPE300 series engineering VFD (Booksize)
Product overview
Other
Description
Specifications
One high-speed pulse output; max. frequency: 50kHz
Digital output One Y terminal open collector output, sharing the terminal
with S4. The function can be selected through a jumper.
Two programmable relay outputs
Relay output
RO1A: NO; RO1B: NC; RO1C: common RO2A: NO; RO2B: NC; RO2C: common
Contact capacity: 3A/AC250V, 1A/DC30V
Three extended interfaces: SLOT1 and SLOT2
Extended interfaces Supporting PG cards, programmable expansion cards,
communication cards, I/O cards and so on
Supports wall-mounting, floor-mounting and Mounting method
flange-mounting.
Temperature of -10°C 50°C. Derating is required when the ambient
running environment temperature exceeds 40°C.
IP rating
IP20
Pollution level Level 2
Cooling method Forced air cooling
The braking unit has been built in the 380V 0045 and lower
Braking unit
VFD models. It is optional for the 380V 00550132 (inclusive) models
and can be built in the VFD.
All series of 380V meet the IEC61800-3 C3 requirements.
EMC filter
Optional external filters can be used to meet the
IEC61800-3 C2 requirements.
3.4 Product nameplate
Model:IPE300-0015-4-B-S
I P20
Power(Output):15kW
Input:AC 3PH 380V(-15%)~440V(+10%) 40A 47Hz-63Hz
Output:AC 3PH 0V-Uinput 32A 0Hz-400Hz
S/N:
Made in China
Shenzhen INVT Electric Co.,Ltd
Figure 3-5 Product nameplate
Note: The preceding are standard product nameplate examples. The marking such as “CE” or “IP20” on the nameplate is marked according to actual certification conditions.
-11-
IPE300 series engineering VFD (Booksize)
3.5 Model designation code
Product overview
A model designation code contains product information. You can find the model designation code on the VFD nameplate.
IPE300-16-0015-4-B-L3-S
Figure 3-6 Model description
Field Symbol
Name
Remarks
Product series
abbreviation
Product series IPE300: IPE300 series engineering VFD
abbreviation
Product
category
Rated power
Product category Power range
Empty: VFD unit 16: VFD cabinet 0015: 15kW
Voltage class
4: AC 3PH 380V(-15%) 440V(+10%) Voltage class
Rated voltage: 380V
B: Built-in braking unit
Note: The braking unit has been built in the 0045 and
Braking unit
Braking unit configuration
lower VFD models as a standard configuration. Therefore, this field is omitted. The built-in braking unit is optional for 00550132
models. “-B” is added for the models with built-in
braking unit.
Reactor
Reactor Default: No output reactor
configuration L3: Built-in output reactor
Product version
Empty: Standard version Product version
S: Booksize
Note:
1. The 0045 and lower models carry built-in braking units, the 00550132 (inclusive) models can be configured with optional built-in braking units, and the 0160 and higher models can be configured with external braking units.
2. The 00220110 (inclusive) models carry built-in DC reactors, and the 0200 and higher models supports built-in output reactors.
-12-
IPE300 series engineering VFD (Booksize)
Product overview
3.6 Product ratings
3.6.1 Ratings of VFD unit
Table 3-1 Ratings of VFD unit
VFD model
Heavy overload
Light-load application
Full load
application
Blowing
power
Weight
Output Input Output Output Input Output
rate
dissipation power current current power current current
(m3/h)
(kg)
(W)
(kW) (A) (A) (kW) (A) (A)
IPE300-0011-4-B-S 11
30
23 7.5 25 18.5
338
56.29 3
IPE300-0015-4-B-S 15 40 32 11 32 25 IPE300-0018-4-B-S 18.5 45 38 15 40 32
511 149.14 6
525
IPE300-0022-4-B-S 22 51 45 18.5 45 38 IPE300-0030-4-B-S 30 64 60 22 51 45
589 170.36 8.5
745
IPE300-0037-4-B-S 37 80 75 30 64 60 IPE300-0045-4-B-S 45 98 92 37 80 75
959 340.79 16
1126
IPE300-0055-4-S 55 128 115 45 98 92
1189
IPE300-0075-4-S 75 139 150 55 128 115 1473 752.32 25
IPE300-0090-4-S 90 168 170 75 139 150 1879
IPE300-0110-4-S 110 201 215 90 168 180 IPE300-0132-4-S 132 265 260 110 201 215
2016 2587
849.5 41
IPE300-0160-4-S 160 310 305 132 265 260 IPE300-0185-4-S 185 345 340 160 310 305
2780 3004
1443 78
IPE300-0200-4-S 200 385 380 185 345 340 3177
IPE300-0220-4-S 220 430 425 200 385 380 3609 1798 122
IPE300-0250-4-S 250 460 480 220 430 425 3927
IPE300-0280-4-S 280 500 530 250 460 480 5598
IPE300-0315-4-S 315 580 600 280 500 530 6121
124
IPE300-0355-4-S 355 625 650 315 580 600 IPE300-0400-4-S 400 715 720 355 625 650
6608 6976
2697
IPE300-0450-4-S 450 840 820 400 715 720 7658
175
IPE300-0500-4-S 500 890 860 450 840 820 8000
Note:
1. The VFD input current is measured in cases where the input voltage is 380V. 2. The rated output current is the output current when the output voltage is 380V.
3. Within the allowable input voltage range, the output current/power cannot exceed the rated output current/power.
-13-
IPE300 series engineering VFD (Booksize) 3.6.2 Ratings of VFD cabinet
Table 3-2 Ratings of VFD cabinet
Product overview
VFD model
Heavy overload
Light-load application
Full load
application
Blowing
power
Weight
Output Input Output Output Input Output
rate
dissipation power current current power current current
(m3/h)
(kg)
(W)
(kW) (A) (A) (kW) (A) (A)
IPE300-16-0110-4-S 110 201 215 90 168 180 IPE300-16-0132-4-S 132 265 260 110 201 215
2185 2756
849.5 314
IPE300-16-0160-4-S 160 280 305 132 230 260 IPE300-16-0185-4-S 185 320 340 160 280 305
2949 3196
1443 366
IPE300-16-0200-4-S 200 350 380 185 320 340 3455
IPE300-16-0220-4-S 220 385 425 200 350 380 3894 1798 418
IPE300-16-0250-4-S 250 435 480 220 385 425 4258
IPE300-16-0280-4-S 280 480 530 250 435 480 6687
IPE300-16-0315-4-S 315 550 600 280 480 530 6945
443
IPE300-16-0355-4-S 355 605 650 315 550 600 IPE300-16-0400-4-S 400 680 720 355 605 650
7789 8243
2697
IPE300-16-0450-4-S 450 770 820 400 680 720 9099
511
IPE300-16-0500-4-S 500 850 860 450 770 820 9496
-14-
IPE300 series engineering VFD (Booksize)
Product overview
3.7 Structure
3.7.1 Structure of VFD unit The VFD structure is shown in the following figure
(taking the 380V 0030 VFD model as an example).
1
5
6
2
7
8
4
9
10
3
11
13
12
Figure 3-7 VFD unit structure
No.
Name
Description
1
Upper cover
Protects internal components and parts.
2
Keypad
For details, see section “Keypad instruction”.
3
Lower cover
Protects internal components and parts.
4
Expansion card
Optional. For details, see “Expansion card”.
5
Baffle of control board Protects the control board and install expansion cards.
6
Cooling fan
For details, see section “Expansion card”.
7
Keypad interface
Connects the keypad.
8
Nameplate
For details, see section “Product overview”.
9
Control circuit terminals For details, see section “Installation guidelines”.
Optional. Cover plate can upgrade protection level, however,
Cover plate of heat emission
10
as it will also increase internal temperature, derated use is
hole
required.
11
Main circuit terminals For details, see section “Installation guidelines”.
12
POWER indicator
Power supply indicator
13
Product label
For details, see section “Model designation code”
-15-
IPE300 series engineering VFD (Booksize) 3.7.2 Layout of VFD cabinet The following figure shows the layout of the 110185kW cabinet.
Product overview
Front door
Cab ine t VFD unit
Breaker Input terminal
Output reactor Output terminal Isolation transformer
The following figure shows the layout of the 200500kW cabinet.
Front door Isolation transformer
Breaker Input terminal Input reactor
Cabinet VFD unit
Output terminal Output reactor
Note: The product configuration varies with the power cabinet. For details, see section 3.7.3. -16-
IPE300 series engineering VFD (Booksize)
Product overview
3.7.3 Cabinet configuration table
Code
Name
16S6
16S7
16S8
16S9
16S10
01100132 01600185 02000250 02800355 04000500
Main circuit configuration
–
Breaker
E250
AC fast fuse
E255
Main contactor
E150
Braking unit
E203
Input reactor
E204
DC reactor
E205
Output reactor
–
Variable-frequency unit
Control circuit
–
Safety relay
–
Cabinet lights
E108
Cabinet heater
– Emergency stop, class 0
E110 Emergency stop, class 1
– Local/Remote switching
E112 Motor fan output (46A)
E113 Motor fan output (610A)
E114
Motor fan output
(1016A)
IP rating
–
IP20
C121
IP21
Installation
C201
100mm base
C202
200mm base
C211
Lifting ring
Note: means standard configuration; means optional configuration.
-17-
IPE300 series engineering VFD (Booksize)
Installation guidelines
4 Installation guidelines
4.1 What this chapter contains
This chapter describes the mechanical installation and electrical installation
of the VFD.
Only trained and qualified professionals are allowed to carry out the
operations mentioned in this chapter. Please carry out operations according to
instructions presented in “Safety precautions”. Ignoring these safety
precautions may lead to physical injury or death, or device damage.
Ensure the VFD power has been disconnected before installation. If the VFD has
been powered on, disconnect the VFD power and wait for at least the time
specified on the VFD, and ensure the POWER indicator is off. You are
recommended to use a multimeter to check and ensure the VFD DC bus voltage is
below 36V.
The VFD installation must be designed and done according to applicable local
laws and regulations. INVT does not assume any liability whatsoever for any
VFD installation which breaches local laws or regulations. If recommendations
given by INVT are not followed, the VFD may experience problems that the
warranty does not cover.
4.2 Installation environment
The installation environment is essential for the VFD to operate with best performance in the long run. Install the VFD in an environment that meets the following requirements.
Environment
Condition
Installation site Indoor
-10+50°C When the ambient temperature exceeds 40°C, derate 1% for every increase
of 1°C.
Do not use the VFD when the ambient temperature exceeds 50°C.
In order to improve reliability, do not use the VFD in the places where the
Ambient
temperature changes rapidly.
temperature When the VFD is used in a closed space, such as control cabinet, use a
cooling fan or air conditioner for cooling, preventing the internal temperature
from exceeding the temperature required.
When the temperature is too low, if you want to use the VFD that has been
idled for a long time, install an external heating device before the use to
eliminate the freeze inside the VFD. Otherwise, the VFD may be damaged.
-18-
IPE300 series engineering VFD (Booksize)
Installation guidelines
Environment
Condition
Relative humidity (RH)
RH: less than 90% Condensation is not allowed. The max. RH cannot exceed 60% in the environment where there are
corrosive gases.
Storage -3060.0°C
temperature
Install the VFD in a place: Away from electromagnetic radiation sources Away from oil mist, corrosive gases, and combustible gases Without the chance for foreign objects such as metal powder, dust, oil and
Running
water to fall into the VFD (do not install the VFD onto combustible objects
environment
such as wood)
Without radioactive substances and combustible objects
Without hazard gases and liquids
With low salt content
Without direct sunlight
Altitude
Lower than 1000 meters When the altitude exceeds 1000m, derate by 1% for every additional 100m. When the installation site altitude exceeds 3000m, consult the local INVT
dealer or office. Vibration Max. vibration acceleration: 5.8m/s2 (0.6g)
Installation Install the VFD vertically to ensure good heat dissipation
performance.
direction
Note:
1. The VFD must be installed in a clean and well-ventilated environment based on the housing IP rating.
2. The cooling air must be clean enough and free from corrosive gases and
conductive dust.
4.3 VFD unit installation
4.3.1 Installation direction
The VFD unit can be installed on the wall or in a cabinet.
The VFD must be installed vertically. Check the installation position according to following requirements. For details about the outline dimensions, see Appendix C Dimension drawings.
-19-
IPE300 series engineering VFD (Booksize)
OK
NG
Installation guidelines
NG
A. Vertical installation
B. Horizontal installation
C. Transverse installation
4.3.2 Installation method
Figure 4-1 Installation direction
There are three kinds of installation modes based on different VFD dimensions. Wall-mounting: applicable to 380V 0185 and lower models. Flange-mounting: applicable to 380V 0185 and lower models. Floor-mounting: applicable to 380V 02000500 models.
Wall-mounting
Flange-mounting
Figure 4-2 Installation method
1. Mark the installation hole positions. For details about the installation hole positions, see Appendix C Dimension drawings.
2. Mount the screws or bolts onto the designated positions.
3. Lean the VFD against the wall.
4. Tighten the screws.
Note:
1. The flange mounting plate must be used for flange mounting.
2. The 380V 02000500 models with optional output AC reactors also supports floor mounting.
-20-
IPE300 series engineering VFD (Booksize) 4.3.3 Installing one unit
A
Installation guidelines
Hot air C
AB
B
Cold air C
Figure 4-3 Installing one VFD Note: For clearances A, B, and C, each must be 100mm at least. 4.3.4 Multiple-VFD installation
A
Hot air C
AB
D
B
Cold air C
Figure 4-4 Parallel installation Note: 1. When you install VFDs in different
sizes, align the top of each VFD before installation for the
convenience of future maintenance. 2. For clearances A, B, C, and D, each must
be 100mm at least.
-21-
IPE300 series engineering VFD (Booksize) 4.3.5 Vertical installation
Installation guidelines
Hot air
Cold air
Windshield
Hot air
Cold air
Windshield
Figure 4-5 Vertical installation Note: During vertical installation, you must
install windshield, otherwise, the VFD will experience mutual interference,
and the heat dissipation effect will be degraded.
-22-
IPE300 series engineering VFD (Booksize) 4.3.6 Tilted installation
Installation guidelines
Hot air
Cold air
Hot air
Cold air
Hot air
Cold air
Figure 4-6 Tilted installation Note: During tilted installation, it is a must
to ensure the air inlet duct and air outlet duct are separated from each other
to avoid mutual interference.
4.4 VFD cabinet installation
4.4.1 Transportation The VFD cabinet is shipped in a wooden box with pallets,
which are heavy as a whole and must be carried with a lifting tool, such as a
forklift and crane; operators must be professionally trained; the inverter
unit must be transported in strict accordance with the allowed ways marked on
the box, and not allowed to be transported upside down or on the sides.
-23-
IPE300 series engineering VFD (Booksize)
×
Installation guidelines
×
Figure 4-7 Transportation requirements
When transported with a forklift, the VFD must be fixed to the pallets and
transported together, which means you are not allowed to remove the pallets to
transport the VFD. If the forklift’s fork tines are too short, it may cause
the unit/cabinet to tip over, resulting in serious injury, property damage or
even death.
When transported with a crane, the VFD must be fixed to the pallets and lifted
together.
Figure 4-8 Transportation means -24-
IPE300 series engineering VFD (Booksize)
Installation guidelines
4.4.2 Unpacking
The cabinet is delivered in the wooden box padded with EPE.
To remove the packing, do as follows:
Step 1 Place the well-packed unit in an empty and flat place.
Step 2 Use tools such as a pry bar or large one-piece screwdriver to remove the wooden box cover and the steel tongue nails of the surrounding boards.
Step 3 Remove the surrounding boards and EPE filling materials from the wooden box.
Step 4 Cut off the plastic windings.
Step 5 Take out of the cabinet.
Step 6 Ensure that the unit is intact without any damage.
Note: Dispose of or recycle packaging in accordance with local regulations.
1
2 4
2 3
No
Na m e
1
Cover
3
2 Front and rear panels
3 Left and right panels
4
EPE
5
Base plate
5
Figure 4-9 Unpacking
-25-
IPE300 series engineering VFD (Booksize)
Installation guidelines
To lift the device with the steel lifting holes at the top corners, the lifting rope or slings must be installed into the hole of the lifting holes and fixed to ensure safety. See Figure 4-10 for details.
Figure 4-10 Lifting diagram
4.4.3 Installation 4.4.3.1 Installation site check The installation site
should be well ventilated or shaded for a good heat dissipation. The
installation environment meets the specification requirements. The
wall/material near the installation site should be non-combustible material.
The floor should be made of non-combustible material, and flat and strong to
withstand the weight of the device. Check the level of the floor with a level,
and ensure that the maximum allowable deviation of the level of the ground
surface is 5mm per 3m. The installation site should be leveled if necessary,
as the cabinet is not equipped with adjustable feet. To facilitate
maintenance, do not install the cabinet in a high place (i.e. higher than the
front place). 4.4.3.2 Installation description The cabinet is floor mounted
and fixed to the ground. When the channel steel base is not available on the
site, fix the cabinet directly to the ground through 4 fixing anchor bolts.
For the installation dimensions, see section C.4 VFD cabinet dimensions.
-26-
IPE300 series engineering VFD (Booksize)
Installation guidelines
Figure 4-11 Anchor bolt installation diagram
600
4 13
653
Figure 4-12 Installation without channel steel base
When the channel steel base is available on the site, fix the channel steel base with the ground, and then fix the base and the cabinet with screws. For the installation dimensions, see section C.4 VFD cabinet dimensions.
735
4-M12
575
Figure 4-13 Installation with channel steel base -27-
IPE300 series engineering VFD (Booksize)
Installation guidelines
To ensure reliable cabinet installation and good heat dissipation, the
ventilation clearances must be kept from the front, back, top and sides of the
cabinet. For the minimum clearance, see Figure 4-11.
A minimum clearance of 800mm should be reserved in front of the cabinet to
facilitate cabinet maintenance.
Side view
260
800
100
Figure 4-14 Installation space requirements Violation of the requirements in
the installation space and heat dissipation will shorten the VFD life and may
result in VFD failure or malfunction.
-28-
IPE300 series engineering VFD (Booksize)
4.5 Standard wiring of the main circuit
4.5.1 Main circuit wiring diagram of VFD unit
Braking resistor
+ PB –
3-phase power 380V(-15%) ~ 440V(+10%)
50/60Hz
Input
R
reactor
S Input
filter
T
Fuse
0045 and lower
Installation guidelines
U
Output
reactor
V
M
Output
W
filter
PE
Braking unit
+ –
DC+ DC-
Braking resistor
U
Output
reactor
3-phase power 380V(-15%) ~ 440V(+10%)
50/60Hz
Input
R
reactor
00550132 (inclusive) V
Output
M
S
W
filter
Input
filter
T
PE
Fuse
Braking unit
+ –
DC+ DC-
Braking resistor
3-phase power 380V(-15%) ~ 440V(+10%)
50/60Hz
Input
R
reactor S
Input
filter
T
Fuse
U
Output
reactor
V
M
0160 and higher
Output
W
filter
PE
Note:
Figure 4-15 Main circuit wiring diagram for AC 3PH 380V(-15%) 440V(+10%)
1. The fuse, braking unit, braking resistor, input reactor, input filter, output reactor and output filter are optional parts. For details, see Appendix D “Optional peripheral accessories”.
2. Before connecting the braking resistor, remove the yellow warning label with PB, (+) and (-) from the terminal block; otherwise, poor contact may occur.
3. Built-in braking unit is optional for the 380V 00550132 models.
-29-
IPE300 series engineering VFD (Booksize) 4.5.2 Main circuit terminal diagram of VFD unit
Installation guidelines
Figure 4-16 Main circuit terminal diagram for 3PH 380V 0030kW and lower
Figure 4-17 Main circuit terminal diagram for 3PH 380V 00370045kW
Figure 4-18 Main circuit terminal diagram for 3PH 380V 00550132kW
280
40
34
67 35
( )( )
( )( )
Figure 4-19 Main circuit terminal diagram for 3PH 380V 01600185kW (unit: mm)
-30-
IPE300 series engineering VFD (Booksize)
U V W
38
Installation guidelines
197
13 (-)
85 (+)
50
R S T
50 38
154
154
104.5
Right view
Front view
142
142
122.5
M12
Left view
Figure 4-20 Main circuit terminal diagram for 3PH 380V 02000355kW (unit: mm)
(+)
(-)
197 85
13
(-)
(+)
50
U
V
W
R S
T
45
60
Right view
Front view
148
148
121.5
M12
Left view
Figure 4-21 Main circuit terminal diagram for 3PH 380V 04000500kW (unit: mm)
Terminal R, S, T U, V, W
Terminal name
380V 0045 380V 00550132 380V 0160
and lower
(inclusive) and higher
Description
Main circuit power input
3PH AC input terminals, connecting to the grid
VFD outputs
3PH AC output terminals, which connect to the motor in most cases
-31-
IPE300 series engineering VFD (Booksize)
Installation guidelines
Terminal name
Terminal 380V 0045 380V 00550132 380V 0160
and lower
(inclusive) and higher
Description
(+)
Braking unit terminal 1
(+) and (-) connect to the external
(-) Not available
Braking unit terminal 2
braking unit.
PB and (+) connect to external
PB
Braking resistor terminal 2 Not available
braking resistor terminal
Each machine must carry two PE
PE
Grounding terminal for safe protection
terminals and proper grounding is
required
Note:
1. It is not recommended to use asymmetrical motor cables. If there is a symmetrical grounding conductor in the motor cable besides the conductive shielded layer, ground the grounding conductor on the VFD end and motor end.
2. Braking resistor, braking unit and DC reactor are optional parts.
3. Route the motor cable, input power cable and control cable separately.
4. “Not available” means this terminal is not for external connection. 4.5.3 Main circuit wiring diagram of VFD cabinet
R
U
S
V
T
W
PE
Figure 4-22 Main circuit wiring diagram of VFD cabinet 4.5.4 Main circuit terminal diagram of VFD cabinet
Figure 4-23 Main circuit terminal diagram for 110185kW VFD cabinet -32-
IPE300 series engineering VFD (Booksize)
Installation guidelines
Front door of the cabinet
Figure 4-24 Main circuit terminal diagram for 200500kW VFD cabinet Main circuit terminal description of VFD cabinet:
No.
Name
Description
1
R, S, T
3PH AC input terminals
2
U, V, W
3PH AC output terminals
3
PE
Grounding terminal
4.5.5 Wiring procedure for main circuit terminals 1. Connect the grounding
line of the input power cable to the grounding terminal (PE) of the VFD,
and connect the 3PH input cable to R, S and T terminals and tighten up. 2.
Connect the ground wire of the motor cable to the PE terminal of the VFD,
connect the motor 3PH
cable to the U, V and W terminals, and tighten up. 3. Connect optional parts
such as the braking resistor that carries cables to designated positions. 4.
Fasten all the cables outside the VFD mechanically if allowed.
NG
The screw is not fastened.
Y
The screw is fastened.
Figure 4-25 Screw installation diagram
-33-
IPE300 series engineering VFD (Booksize)
4.6 Standard wiring of the control circuit
4.6.1 Wiring of basic control circuit
Installation guidelines
Forward running Reverse running Fault reset
Multi-function analog inputs
-10V (External)
S1 S2
S3 S4 HDIA HDIB
COM PW +24V PE
VFD
J7 AO0 V I GND
J6 AO1 V I GND
J10 S4 Y1
S4/Y1 COM HDO COM
Power used for +10V frequency setting
AI1
J11
J8 ON OFF
485+ 485-
PE
AI2 GND
VI
PE
RO1A RO1B RO1C
RO2A RO2B RO2C
Analog output 010V/020mA
Analog output 010V/020mA
Y1 output High speed pulse output RS485 communication
Relay output 1
Relay output 2
Figure 4-26 Wiring diagram of basic control circuit
Terminal name
Description
+10V Locally provided +10.5V power supply
AI1 Input range: For AI1, 010V or 020mA; for AI2, -10V +10V
Input impedance: 20k for voltage input or 250 for current input
AI2
Function code P05.50 specifies whether to use voltage or current input.
Resolution: 5mV when 10V corresponds to 50Hz
Deviation: ±0.5% at 25°C, when input is above 5V/10mA
GND Reference ground of +10.5V
AO0 Output range: 0(2)10V or 0(4)20mA
-34-
IPE300 series engineering VFD (Booksize)
Installation guidelines
Terminal name
Description
AO1
Whether voltage or current is used for output of AO0 and AO1 is set through jumpers J7 and J6. Error: ±0.5% when output is 5V at 25°C.
RO1A RO1B RO1C
RO1 output; RO1A: NO; RO1B: NC; RO1C: common Contact capacity: 3A/AC250V, 1A/DC30V
RO2A RO2B RO2C
RO2 output; RO2A: NO; RO2B: NC; RO2C: common Contact capacity: 3A/AC250V, 1A/DC30V
HDO
Switch capacity: 200mA/30V Output frequency range: 050kHz Duty ratio: 50%
COM Reference ground of +24V
Switch capacity: 50mA/30V Y1 Output frequency range: 01kHz
Y1 and S4 share the output terminal. The selection is made through J10.
485+ RS485 communication port, RS485 differential signal port and standard RS485
485-
communication port must use shielded twisted pairs; the 120ohm terminal matching resistor for RS485 communication is connected through jumper J8.
PE Grounding terminal
External power input terminal for digital input circuits PW
Voltage range: 1224V
24V User power supply provided by the VFD. Max. output current: 200mA
S1
Digital input 1 1. Internal impedance: 3.3k
S2
Digital input 2 2. 1230V voltage input is acceptable
S3
Digital input 3 3. Bi-direction input terminals, supporting both NPN and PNP
connection methods
4. Max. input frequency: 1kHz
5. Programmable digital input terminals, the functions of which can
S4
Digital input 4
be set through the related parameters
6. S4 and Y1 share the output terminal. The selection is made
through J10.
HDIA Channels for both high frequency pulse input and digital input
Max. input frequency: 50kHz
HDIB Duty ratio: 30%70%
Supporting quadrature encoder input; with the speed measurement function
-35-
IPE300 series engineering VFD (Booksize)
Installation guidelines
4.6.2 Input/output signal connection diagram
Set NPN /PNP mode and internal/external power via U-shaped jumper. NPN internal mode is adopted by default.
HDIB HDO COM
RO1ARO1B RO1C
S1 S2 S3 S4/Y1 HDIA AO1 AI1 AI2 +10V
RO2ARO2B RO2C
+24V PW COM COM AO0 GND 485+ 485-
U-shaped jumper of +24V and PW
Figure 4-27 Position of U-shaped jumpers
Keypad port
Note: As shown in the figure above, the keypad port can be used to connect an external keypad. The external keypad cannot be used when the local VFD keypad is used.
If the input signal comes from the NPN transistor, set the U-shaped jumper between +24V and PW based on the power used according to the following figure.
S1
S1
S2
S2
COM PW + 24V
COM + 24V
+ 24V
COM PW + 24V
COM +24V
Internal powerNPN mode
External powerNPN mode
Figure 4-28 NPN mode
If the input signal comes from the PNP transistor, set the U-shaped jumper based on the power used according to the following figure.
S1
S1
S2
S2
COM PW + 24V
COM + 24V
COM PW + 24V
COM + 24V
Internal powerPNP mode
External powerPNP mode
Figure 4-29 PNP mode
-36-
IPE300 series engineering VFD (Booksize)
Installation guidelines
4.7 Wiring protection
4.7.1 Protecting the VFD and input power cable in case of short circuit
The VFD and input power cable can be protected in case of short circuit, avoiding thermal overload.
Carry out protective measures according to the following figure.
VFD
Input cable Fuse
M3 ~
Figure 4-30 Fuse configuration
Note: Select the fuse according to the manual. In case of short circuit, the fuse protects input power cables to avoid damage to the VFD; if internal short-circuit occurs to the VFD, it can protect neighboring equipment from being damaged. 4.7.2 Protecting the motor and motor cable in case of short circuit
If the motor cable is selected based on VFD rated current, the VFD is able to protect the motor cable and motor during short circuit without other protective devices.
If the VFD is connected to multiple motors, use a separated thermal overload switch or breaker to protect the cable and motor, which may require the fuse to cut off the short circuit current.
4.7.3 Protecting the motor against thermal overload
The motor must be protected against thermal overload. Once overload is
detected, current must be cut off. The VFD is equipped with the motor thermal
overload protection function, which can block output and cut off the current
(if necessary) to protect the motor. 4.7.4 Bypass connection
In some critical scenarios, the power/variable frequency conversion circuit
needs to be configured to ensure proper operation of the system when a fault
occurs to the VFD.
In some special scenarios, such as in soft startup, power-frequency running is
directly performed after the startup, which requires bypass connection.
Do not connect any power source to the VFD output terminals U, V, and W. The
voltage applied to the motor cable may cause permanent damage to the VFD.
If frequent switchover is needed, you can use the switch which carries
mechanical interlock or a contactor to ensure motor terminals are not
connected to input power cables and VFD output ends simultaneously.
-37-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
5 Basic operation guidelines
5.1 What this chapter contains
This chapter describes the buttons, indicators, and display of the keypad, as
well as the method of using the keyboard to view and modify the function code
settings.
5.2 Keypad instruction
The keypad is provided to control the VFD, read status data and set
parameters.
RUN/TUNE
FWD/REV
LOCAL/REMOT TRIP Hz RPM
A% V
PRG ESC
QUICK JOG
RUN
DATA ENT
SHIFT
STOP RST
Figure 5-1 Keypad
Note: The LED keypad is a standard part for the VFD. In addition, the LCD keypad (an optional part) can be provided as required. The LCD keypad supports HD display in multi language, with parameter copy function. Its installation size is compatible with LED keypad.
No. Status
1 indicator
Name RUN/TUNE FWD/REV
LOCAL/REMOT
Description Off: The VFD is stopped Blinking: The VFD is in parameter autotuning. On: The VFD is running. Forward or reverse running indicator Off: The VFD is running forward. On: The VFD is running. Indicates whether the VFD is controlled through the keypad, terminals, or communication. Off: The VFD is controlled through the keypad. Blinking: The VFD is controlled through terminals. On: The VFD is controlled remotely.
-38-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
No.
Name
Description
Fault indicator
TRIP
On: The VFD is in fault state. Off: The VFD is in normal state.
Blinking: The VFD is in pre-alarm state.
Unit displayed currently
Hz
Frequency unit
2 Unit indicator
RPM A
Rotation speed unit Current unit
%
Percentage
V
Voltage unit
Five-digit LED displays various monitoring data and alarm codes such as
the frequency setting and output frequency.
Display Means Display Means Display Means
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Digital display 3
9
9
A
A
B
B
zone
C
C
d
d
E
E
F
F
H
H
I
I
L
L
N
N
n
n
o
P
P
r
r
S
S
t
t
U
U
v
v
.
.
–
–
Digital
4
Reserved
potentiometer
PRG Programming Press it to enter or exit level-1 menus or
ESC
key
delete a parameter.
DATA ENT
Confirmation Press it to enter menus in cascading mode or
key
confirm the setting of a parameter.
5
Keys
UP key Press it to increase data or move upward. Down key Press it to decrease data or move downward.
SHIFT
Press it to select display parameters
Right-shifting rightward in the interface for the VFD in
key
stopped or running state or to select digits to
change during parameter setting.
-39-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
No.
Name
Description
RUN
STOP RST
Run key
Stop/ Reset key
Press it to run the VFD when using the keypad for control. Press it to stop the VFD that is running. The function of this key is restricted by P07.04. In fault alarm state, this key can be used for reset in any control modes.
QUICK JOG
Multifunction The function of this key is determined by shortcut key P07.02.
5.3 Keypad display
The keypad displays information such as the stopped-state parameters, running-
state parameters, and fault status, and allows you to modify function codes.
5.3.1 Displaying stopped-state parameters
When the VFD is in stopped state, the keypad displays stopped-state
parameters. See Figure 5-2.
In the stopped state, various kinds of parameters can be displayed. You can
determine which parameters are displayed in stopped state by setting function
code P07.07. For details, see the description of P07.07.
In stopped state, there are 15 parameters that can be selected for display,
including the set frequency, bus voltage, PID reference value, PID feedback
value, input terminal status, output terminal status, torque setting, PLC and
the present step of multi-step speed, AI1 value, AI2 value, AI3 value, high-
speed pulse HDI frequency, pulse counting value, length value, and upper limit
frequency (Hz on). You can press >>/SHIFT to shift selected parameters from
left to right or press QUICK/JOG (P07.02=2) to shift selected parameters from
right to left. 5.3.2 Displaying running-state parameters
After receiving a valid running command, the VFD enters the running state, and
the keypad displays running-state parameters, with the RUN/TUNE indicator on.
The on/off state of the FWD/REV indicator is determined by the actual running
direction. See Figure 5-2.
In running state, there are 25 parameters that can be selected for display,
including the running frequency, set frequency, bus voltage, output voltage,
output current, running speed, output power, output torque, PID reference
value, PID feedback value, input terminal status, output terminal status,
torque setting, length value, PLC and the current step of multi-step speed,
AI1, AI2, AI3, high-speed pulse HDI frequency, motor overload percentage, VFD
overload percentage, ramp reference value, linear speed, AC input current, and
upper limit frequency (Hz on). You can determine which parameters are
displayed in stopped state by setting function codes P07.05 and P07.06. You
can press >>/SHIFT to shift selected parameters from left to right or press
QUICK/JOG to shift selected parameters from right to left.
-40-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
5.3.3 Displaying fault information
After detecting a fault signal, the VFD enters the fault alarm state immediately, the fault code blinks on the keypad, and the TRIP indicator is on. You can perform fault reset by using the STOP/RST key, control terminals, or communication commands.
If the fault persists, the fault code is continuously displayed. 5.3.4 Editing function codes
You can press the PRG/ESC key to enter the editing mode in stopped, running, or fault alarm state (if a user password is used, see the description of P07.00). The editing mode contains two levels of menus in the following sequence: Function code group or function code number Function code setting. You can press the DATA/ENT key to enter the function parameter display interface. In the function parameter display interface, you can press the DATA/ENT key to save parameter settings or press the PRG/ESC key to exit the parameter display interface.
PRG ESC
DATA ENT
PRG ESC
DATA ENT
PRG ESC
DATA ENT
QUICK JOG
SHIFT
QUICK JOG
SHIFT
QUICK JOG
SHIFT
RUN
STOP RST
RUN
STOP RST
RUN
STOP RST
Display state of stopping parameters
Display state of running parameters
Display state of fault parameters
5.4 Operation procedure
Figure 5-2 Status display
You can operate the VFD by using the keypad. For details about function code descriptions, see the function code list. 5.4.1 Modifying function codes The VFD provides three levels of menus, including:
· Function code group number (level-1 menu)
· Function code number (level-2 menu)
· Function code setting (level-3 menu)
Note: When performing operations on the level-3 menu, you can press the PRG/ESC or DATA/ENT key to return to the level-2 menu. If you press the DATA/ENT key, the set value of the parameter is saved to the control board first, and then the level-2 menu is returned, displaying the next function
-41-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
code. If you press the PRG/ESC key, the level-2 menu is returned directly, without saving the set value of the parameter, and the current function code is displayed.
If you enter the level-3 menu but the parameter does not have a digit blinking, the parameter cannot be modified due to either of the following reasons:
· It is read only. Read-only parameters include actual detection parameters and running record parameters.
· It cannot be modified in running state and can be modified only in stopped state.
Example: Change the value of P00.01 from 0 to 1.
PRG ESC
DATA ENT
All digits are
PRG ESC
The units place
PRG ESC
blinking
is blinking
The units place is blinking
The units place is blinking
PRG ESC
DATA ENT
DATA ENT
The units place is blinking Note: When setting the value, you can press and + to modify the value.
Figure 5-3 Modifying a parameter
5.4.2 Setting a password for the VFD
The VFD provides the user password protection function. When you set P07.00 to
a non-zero value, the value is the user password. If password protection is
enabled, “0.0.0.0.0” is displayed when you press the PRG/ESC key again to
enter the function code editing interface. You need to enter the correct user
password to enter the interface.
To disable the password protection function, you need only to set P07.00 to 0.
After you exit the function code editing interface, the password protection
function is enabled within 1 minute. If password protection is enabled,
“0.0.0.0.0” is displayed when you press the PRG/ESC key again to enter the
function code editing interface. You need to enter the correct user password
to enter the interface.
-42-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
PRG ESC
All digits are blinking
PRG ESC
The units place
is blinking
DATA ENT
The units place is blinking
PRG ESC
DATA ENT
DATA ENT
The units place is blinking
PRG
The units place is blinking ESC
The units place is blinking
Note: When setting the value, you can press
and
+ to modify the value.
5.4.3 Viewing VFD status
Figure 5-4 Setting a password
The VFD provides group P17 for status viewing. You can enter group P17 for viewing.
PRG ESC
All digits are blinking
PRG ESC
The units place
is blinking
The units place is blinking
PRG ESC
DATA ENT
PRG ESC
DATA ENT
The units place is blinking
Note: When setting the value, you can press
DATA ENT
The units place is blinking
and
to modify the value.
Figure 5-5 Viewing a parameter
5.5 Basic operation description
5.5.1 What this section describes
This section introduces the function modules inside the VFD.
Ensure that all terminals have been securely connected. Ensure that the motor
power matches the VFD power.
5.5.2 Common commissioning procedure The common commissioning procedure is as follows (taking motor 1 as an example).
-43-
IPE300 series engineering VFD (Booksize)
Start
Power up after confirming the wiring is correct
Restore to default value (P00.18=1)
Basic operation guidelines
Set the motor parameters of P02.01P02.05 as per the
motor nameplate
Set the motor parameters of P02.15P02.19 as per the
motor nameplate
Press QUICK/JOG to start pilot run
If the motor rotates in wrong direction, power off and exchange the motor
wires of any two phases,
and power on again
Set autotuning mode (P00.15)
Complete parameter rotary autotuning
Complete parameter static autotuning
Start autotuning after pressing RUN key, and stop after autotuning is done
Set running command channel (P00.01, P00.02)
Set running frequency
Set speed control mode (P00.00)
Partial parameter rotary autotuning
SVC 0 (P00.00=0)
SVC 1 (P00.00=1)
Set vector control parameters in P03 group
Set vector control parameters in P03 group
SVPWM control mode (P00.00=2)
Set V/F parameters in P04 group
Set start/stop control parameters in P01 group
Run after running command
Stop after stop command
End
Note: If a fault occurred, find out the fault cause according to
“Troubleshooting”. The running command channel can be set by terminal commands
besides P00.01 and P00.02.
-44-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Multifunction terminal Multifunction terminal Multifunction terminal
Channel of running
function 36
function 37
function 38
commands
Switch the running Switch the running Switch the running
P00.01
command channel to command channel to command channel to
keypad
terminal
communication
Keypad
/
Terminal
Communication
Terminal
Keypad
/
Communication
Communication
Keypad
Terminal
/
Note: “/” indicates this multifunction terminal is invalid under present reference channel.
Related parameter list:
Function code
Name
Description
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode P00.00 Speed control mode
Note: Before using a vector control mode (0 or 1),
enable the VFD to perform motor parameter
autotuning first.
P00.01
0: Keypad Channel of running
1: Terminal commands
2: Communication
0: Modbus/Modbus TCP
P00.02
Communication mode of running
commands
1: PROFIBUS/CANopen/DeviceNet 2: Ethernet 3: EtherCAT/PROFINET/EtherNet IP 4: Programmable expansion card
5: Wireless communication card
0: No operation
1: Complete rotary parameter autotuning
2: Complete static parameter autotuning
P00.15
Motor parameter 3: Partial static parameter autotuning
autotuning
4: Complete rotary parameter autotuning 2 (for
asynchronous motors)
5: Partial static parameter autotuning 2 (for
asynchronous motors)
P00.18
0: No operation Function parameter
1: Restore default values (excluding motor restore
parameters)
Default 2 0 0
0 0
-45-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code
Name
Description
Default
2: Clear fault records
3: Lock keypad parameters
4: Reserved
5: Restore default values (for factory test mode)
6: Restore default values (including motor
parameters)
Note: After the selected operation is performed,
the function code is automatically restored to 0.
Restoring the default values may delete the
user password. Exercise caution when using
this function.
0: Asynchronous motor (AM)
P02.00 Type of motor 1
0
1: Synchronous motor (SM)
Rated power of AM
P02.01
1
0.13000.0kW
Model depended
Rated frequency of
P02.02
0.01HzP00.03(Max. output frequency)
AM 1
50.00Hz
Rated speed of AM
P02.03
160000rpm
1
Model depended
Rated voltage of AM
P02.04
01200V
1
Model depended
Rated current of AM
P02.05
0.86000.0A
1
Model depended
Rated power of SM
P02.15
0.13000.0kW
1
Model depended
Rated frequency of
P02.16
SM 1
0.01HzP00.03 (Max. output frequency)
50.00Hz
Number of pole pairs
P02.17
1128
2
of SM 1
Rated voltage of SM
P02.18
01200V
1
Model depended
Rated current of SM
P02.19
0.86000.0A
1
Model depended
Function selection of 36: Switch the running command channel to
P05.01 multifunction digital keypad
P05.06
input terminals 37: Switch the running command channel to
(S1S4, HDIA, terminal
-46-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code P07.01
P07.02
Name
Description
HDIB) Parameter copy
Function of QUICK/JOG
38: Switch the running command channel to communication Range: 04 0: No operation 1: Upload parameters to the keypad 2: Download all parameters (including motor parameters) 3: Download non-motor parameters 4: Download motor parameters Range: 0x000x27 Ones place: Function of QUICK/JOG 0: No function 1: Jog 2: Reserved 3: Switch between forward and reverse rotating 4: Clear the UP/DOWN setting 5: Coast to stop 6: Switch command channels in sequence 7: Reserved Tens place: Reserved
Default 0
0x01
5.5.3 Vector control
AMs feature high order, nonlinearity, strong coupling and multi-variables,
which increase difficulty to control AMs during actual application. The vector
control technology solves this situation as follows: measures and controls the
stator current vector of the AM, and then decomposes the stator current vector
into exciting current (current component that generates internal magnet field)
and torque current (current component that generates torque) based on field
orientation principle, and therefore controls the amplitude values and phase
positions of the two components (namely, controls the stator current vector of
the AM) to realize decoupled control on exciting current and torque current,
thus achieving high-performance speed regulation of the AM.
The VFD uses the sensor-less vector control algorithm, which can be used to
drive AMs and permanent-magnet SMs simultaneously. As the core algorithm of
vector control is based on accurate motor parameter models, the accuracy of
motor parameters affects vector control performance. It is recommended to
enter accurate motor parameters and autotune motor parameters before executing
vector control.
As the vector control algorithm is complicated, exercise caution before
modifying vector control function parameters.
-47-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
RST
Rectifier bridge
Calculate im
–
Calculate iT
–
–
ACR exciting current
Park conversion
PWM pulse
ACR torque current
iT
Position
1wr observation
Uu UW UV
1wr
Speed identific
ation
Uu
UV Voltage UW detection
Flux linkage observation
Park
iM
conversio n
iT
Clark conversion
iU
Current
iV
detection iW
IGBT bridge
Motor
Function code
Name
Description
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
Speed control 2: Space voltage vector control mode
P00.00
mode
Note: Before using a vector control mode (0 or 1),
enable the VFD to perform motor parameter autotuning
first.
0: No operation
1: Complete rotary parameter autotuning
2: Complete static parameter autotuning
Motor parameter 3: Partial static parameter autotuning P00.15
autotuning 4: Complete rotary parameter autotuning 2 (for
asynchronous motors)
5: Partial static parameter autotuning 2 (for
asynchronous motors)
0: Asynchronous motor (AM) P02.00 Type of motor 1
1: Synchronous motor (SM)
Speed-loop
P03.00 proportional 0.0200.0
gain 1
Speed-loop
P03.01
0.00010.000s
integral time 1
Default 2
0 0 20.0 0.200s
-48-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code P03.02 P03.03 P03.04 P03.05 P03.06 P03.07
P03.08 P03.09 P03.10
P03.11
Name
Description
Low-point frequency for 0.00HzP03.05
switching Speed-loop proportional 0.0200.0
gain 2 Speed-loop
0.00010.000s integral time 2
High-point frequency for P03.02P00.03 (Max. output frequency)
switching Speed-loop 08 (028/10ms) output filter Electromotive
slip compensation 50%200% coefficient of vector control
Braking slip compensation
50%200% coefficient of vector control Current-loop proportional 065535
coefficient P Current-loop
integral 065535 coefficient I
01: Keypad (P03.12) 2: AI1 3: AI2 4: AI3 Torque setting 5: Pulse frequency
HDIA method 6: Multi-step torque 7: Modbus/Modbus TCP communication 8:
PROFIBUS/CANopen/DeviceNet communication 9: Ethernet communication 10: Pulse
frequency HDIB
Default 5.00Hz
20.0 0.200s 10.00Hz
0 100%
100% 1000 1000
1
-49-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code
Name
Description
Default
11: EtherCAT/PROFINET/EtherNet IP communication 12: Programmable expansion card
Note: For these settings, 100% corresponds to the motor rated current.
Torque set
P03.12
-300.0%300.0% (of the motor rated current)
through keypad
50.0%
Torque
P03.13 reference filter 0.00010.000s
0.010s
time
0: Keypad (P03.16) 1: AI1 2: AI2
3: AI3
Setting source 4: Pulse frequency HDIA
of forward 5: Multi-step setting
rotation
6: Modbus/Modbus TCP communication
P03.14
7: PROFIBUS/CANopen/DeviceNet communication
0
upper-limit 8: Ethernet communication
frequency in 9: Pulse frequency HDIB
torque control 10: EtherCAT/PROFINET/EtherNet IP communication
11: Programmable expansion card
12: Reserved
Note: For these settings, 100% corresponds to the
maximum frequency.
Setting source
of reverse
rotation 0: Keypad (P03.17)
P03.15
upper-limit 111: Same as those for P03.14
0
frequency in
torque control
P03.16
Forward rotation upper-limit
frequency set through keypad
50.00Hz
in torque control Reverse rotation Setting range: 0.00HzP00.03 (Max. output frequency)
P03.17
upper-limit frequency set through keypad in torque control
50.00Hz
-50-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code
Name
Description
0: Keypad (P03.20)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
Setting source 5: Modbus/Modbus TCP communication
of electromotive 6: PROFIBUS/CANopen/DeviceNet communication P03.18
torque upper 7: Ethernet communication
limit
8: Pulse frequency HDIB
9: EtherCAT/PROFINET/EtherNet IP communication
10: Programmable expansion card
11: Reserved
Note: For these settings, 100% corresponds to triple
the motor rated current.
Setting source
P03.19
of braking 0: Keypad (P03.21) torque upper 110: Same as those for P03.18
limit
Electromotive
torque upper P03.20
limit set through
keypad 0.0300.0% (of the motor rated current)
Braking torque
P03.21 upper limit set
through keypad
Weakening
coefficient in
P03.22
0.12.0
constant power
zone
Lowest
weakening point
P03.23
10%100%
in constant
power zone
P03.24
Max. voltage 0.0120.0%
limit
P03.25
Pre-exciting 0.00010.000s
time
Default
0
0 180.0% 180.0%
0.3 20% 100.0% 0.300s
-51-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code
Name
Description
Enabling torque 0: Disable P03.32
control 1: Enable
0x00000x1111
Ones place: Reserved
0: Reserved
1: Reserved
Tens place: Reserved
P03.35
Control optimization
setting
0: Reserved 1: Reserved Hundreds place: indicates whether to enable speed-loop integral separation
0: Disable
1: Enable
Thousands place: Reserved
0: Reserved
1: Reserved
Speed-loop
P03.36
0.0010.00s
differential gain
High-frequency
P03.37
current-loop In the vector control mode, when the frequency is lower proportional than the current-loop high-frequency switching threshold
coefficient (P03.39), the current-loop PI parameters are P03.09 and
High-frequency P03.10; and when the frequency is higher than the
P03.38
current-loop current-loop high-frequency switching threshold, the integral current-loop PI parameters are P03.37 and P03.38.
coefficient P03.37 setting range: 020000
Current-loop P03.38 setting range: 020000
high-frequency P03.39 setting range: 0.0100.0% (of the max. P03.39
switching frequency)
threshold
P17.32 Flux linkage 0.0200.0%
Default 0
0x0000
0.00s 1000 1000 100.0% 0.0%
5.5.4 Space voltage vector control mode
The VFD also carries built-in space voltage vector control function. The space
voltage vector control mode can be used in cases where mediocre control
precision is enough. In cases where a VFD needs to drive multiple motors, it
is also recommended to adopt space voltage vector control mode.
The VFD provides multiple kinds of V/F curve modes to meet different field
needs. You can select corresponding V/F curve or set the V/F curve as needed.
-52-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Suggestions:
1. For the load featuring constant moment, such as conveyor belt which runs
in straight line, as the whole running process requires constant moment, it is
recommended to adopt the straight line V/F curve.
2. For the load featuring decreasing moment, such as fan and water pumps, as
there is a power (square or cube) relation between its actual torque and
speed, it is recommended to adopt the V/F curve corresponding to the power of
1.3, 1.7 or 2.0.
Output voltage
Vb
Straight-type
Torque -down V/F curve (power of 1.3) Torque -down V/F curve (power of 1.7) Torque -down V/F curve (power of 2.0)
Square-type
f Output frequency b
The VFD also provides multi-point V/F curves. You can change the V/F curves
output by the VFD by setting the voltage and frequency of the three points in
the middle. A whole curve consists of five points starting from (0Hz, 0V) and
ending at (motor fundamental frequency, motor rated voltage). During setting,
follow the rule: 0 f1 f2 f3 Motor fundamental frequency, and, 0 V1 V2 V3 Motor
rated voltage
Output voltage
100%Vb
V3
V2
V1
f1
f2
f3
f Output frequency
b
Hz
The VFD provides dedicated function codes for the space voltage control mode. You can improve the space voltage control performance by means of setting.
(1) Torque boost
The torque boost function can effectively compensate for the low-speed torque performance in space voltage control. Automatic torque boost has been set by default, which enables the VFD to adjust the torque boost value based on actual load conditions.
Note:
1. Torque boost takes effect only at the torque boost cut-off frequency.
2. If torque boost is too large, the motor may encounter low-frequency vibration or overcurrent. If such a situation occurs, reduce the torque boost value.
-53-
IPE300 series engineering VFD (Booksize)
Output voltage V
Basic operation guidelines
boost
cut-off
Output frequency
(2) Energy-saving run
During actual running, the VFD can search for the max. efficiency point to
keep running in the most efficient state to save energy.
Note:
1. This function is generally used in light load or no-load cases.
2. This function is no applicable to the cases where sudden load changes
often occur.
(3) V/F slip compensation gain
Space voltage vector control belongs to an open-loop mode. Sudden motor load
changes cause motor speed fluctuation. In cases where strict speed
requirements must be met, you can set the slip compensation gain to compensate
for the speed change caused by load fluctuation through VFD internal output
adjustment.
The setting range of slip compensation gain is 0200%, in which 100%
corresponds to the rated slip frequency.
Note: Rated slip frequency = (Rated synchronous rotation speed of motor
Rated rotation speed of motor) x (Number of motor pole pairs)/60
(4) Oscillation control
Motor oscillation often occurs in space voltage vector control in large-power
driving applications. To solve this problem, the VFD provides two oscillation
factor function codes. You can set the function codes based on the oscillation
occurrence frequency.
Note: A greater value indicates better control effect. However, if the value
is too large, the VFD output current may be too large.
(5) AM IF control
Generally, the IF control mode is valid for AMs. It can be used for SMs only
when the frequency is extremely low. Therefore, the IF control mode described
in this manual is only involved with AMs. IF control is implemented by
performing closed-loop control on the total output current of the VFD. The
output voltage adapts to the current reference, and open-loop control is
separately performed over the frequency of the voltage and current.
-54-
IPE300 series engineering VFD (Booksize) Customized V/F curve (V/F separation) function:
When selecting the customized V/F curve function, you can specify the setting
channels and acceleration/deceleration time of voltage and frequency
respectively, which form a real-time V/F curve in combination manner.
-55-
P04.28
Keypad
Voltage setup
AI1
AI2 AI3 HDIA Multi-step speed PID MODBUS PROFIBUSCANopen Ethernet HDIB
0 1 2 3 4 5 6 7 8
9
10
P04.27(voltage setup channel)
P04.29 voltage acceleration time P04.30 voltage deceleration time
P04.31 output max. voltage P04.32 output min. voltage
Keypad
Frequency setup
Straight-type V/F curve
0
Multi-point V/F curve
1 Torque-down V/F curve (power
1.3)
2
Torque-down V/F curve (power
1.7)
3
Torque-down V/F curve (power
4
2.0)
Customized V/F curve
5
P04.00 Motor 1 V/F curve setup
EtherCat/Profinet PLC card
AI1
0 AI2
1
Keypad setting frequency
AI3
2
P00.10
3 HDIA
4
Simple PLC
5
6 Multi-step speed
7
PID
8
MODBUS
9
P00.11 acceleration time 1 P00.12 deceleration time 1
P00.04 running frequency upper limit
P00.05 running frequency lower limit
V /F curve
PROFIBUSCANopen Ethernet
Pulse string AB
10 11
P00.06 (A frequency command selection)
PWM output
HDIB
Basic operation guidelines
EtherCat/Profinet
PLC card
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Note: This type of V/F curve separation can be applied in various variable- frequency power sources. However, exercise caution when setting parameters as improper settings may cause equipment damage.
Function code
Name
Description
Default
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
P00.00 Speed control mode
2
Note: Before using a vector control mode (0 or 1),
enable the VFD to perform motor parameter
autotuning first.
P00.03 Max. output frequency P00.04400.00Hz
50.00Hz
Upper limit of running
P00.04
P00.05P00.03
frequency
50.00Hz
Lower limit of running
P00.05
0.00HzP00.04
frequency
0.00Hz
P00.11
ACC time 1
0.03600.0s
Model depended
P00.12
DEC time 1
0.03600.0s
Model depended
0: Asynchronous motor (AM)
P02.00
Type of motor 1
0
1: Synchronous motor (SM)
P02.02
Rated
frequency 1
of
AM
0.01HzP00.03(Max.
output
frequency)
50.00Hz
P02.04 Rated voltage of AM 1 01200V
Model depended
0: Straight-line V/F curve 1: Multi-point V/F curve
V/F curve setting of 2: Torque-down V/F curve (power of 1.3)
P04.00
motor 1
3: Torque-down V/F curve (power of 1.7)
0
4: Torque-down V/F curve (power of 2.0)
5: Customized V/F curve (V/F separation)
Torque boost of motor 0.0%: (automatic)
P04.01
1
0.1%10.0%
0.0%
Torque boost cut-off of
P04.02
0.0%50.0% (of the rated frequency of motor 1)
motor 1
20.0%
V/F frequency point 1
P04.03
0.00HzP04.05
of motor 1
0.00Hz
V/F voltage point 1 of
P04.04
0.0%110.0%
motor 1
0.0%
-56-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code
Name
Description
V/F frequency point 2
P04.05
P04.03P04.07
of motor 1
V/F voltage point 2 of
P04.06
0.0%110.0%
motor 1
V/F frequency point 3
P04.07
P04.05P02.02 or P04.05P02.16
of motor 1
V/F voltage point 3 of
P04.08
motor 1
0.0%110.0%
V/F slip compensation
P04.09
0.0200.0%
gain of motor 1
Low-frequency
P04.10 oscillation control 0100
factor of motor 1
High-frequency
P04.11 oscillation control 0100
factor of motor 1
Oscillation control P04.12 threshold of motor 1 0.00HzP00.03 (Max. output frequency)
0: Straight-line V/F curve
1: Multi-point V/F curve
P04.13
V/F curve setting of 2: Torque-down V/F curve (power of 1.3)
motor 2
3: Torque-down V/F curve (power of 1.7)
4: Torque-down V/F curve (power of 2.0)
5: Customized V/F curve (V/F separation)
Torque boost of motor 0.0%: (automatic)
P04.14
2
0.1%10.0%
Torque boost cut-off of
P04.15
motor 2
0.0%50.0% (of the rated frequency of motor 1)
V/F frequency point 1
P04.16
of motor 2
0.00HzP04.18
V/F voltage point 1 of
P04.17
motor 2
0.0%110.0%
V/F frequency point 2
P04.18
of motor 2
P04.16P04.20
V/F voltage point 2 of
P04.19
motor 2
0.0%110.0%
V/F frequency point 3
P04.20
P04.18P02.02 or P04.18P02.16
of motor 2
Default 0.00Hz 0.0% 0.00Hz 0.0% 100.0%
10
10 30.00Hz
0
0.0% 20.0% 0.00Hz 0.0% 0.00Hz 0.0% 0.00Hz
-57-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code
Name
Description
V/F voltage point 3 of
P04.21
0.0%110.0%
motor 2
V/F slip compensation
P04.22
0.0200.0%
gain of motor 2
Low-frequency
P04.23 oscillation control 0100
factor of motor 2
High-frequency
P04.24 oscillation control 0100
factor of motor 2
Oscillation control
P04.25
0.00HzP00.03 (Max. output frequency)
threshold of motor 2
P04.26
0: Disable Energy-saving run
1: Automatic energy-saving run
0: Keypad; Output voltage is determined by
P04.28
1: AI1
2: AI2
3: AI3
4: HDIA
5: Multi-step running
6: PID
P04.27 Voltage setting channel 7: Modbus/Modbus TCP communication
8: PROFIBUS/CANopen/DeviceNet
communication
9: Ethernet communication
10: HDIB
11: EtherCAT/PROFINET/EtherNet IP
communication
12: Programmable expansion card
13: Reserved
P04.28
Voltage set through 0.0%100.0% (of the motor rated voltage)
keypad
P04.29 Voltage increase time 0.03600.0s
P04.30 Voltage decrease time 0.03600.0s
P04.31 Max. output voltage P04.32 100.0% (of the motor rated voltage)
P04.32 Min. output voltage 0.0%P04.31 (motor rated voltage)
Default 0.0%
100.0% 10 10
30.00Hz 0
0
100.0% 5.0s 5.0s
100.0% 0.0%
-58-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code
Name
Description
Default
Weakening coefficient
P04.33
1.001.30
1.00
in constant power zone
When the SM VF control mode is enabled, the
function code is used to set the reactive current of
Pull-in current 1 in SM the motor when the output frequency is lower than
P04.34
20.0%
V/F control
the frequency specified by P04.36.
Setting range: -100.0%+100.0% (of the motor
rated current)
When the SM VF control mode is enabled, the
function code is used to set the reactive current of
Pull-in current 2 in SM the motor when the output frequency is higher
P04.35
V/F control
than the frequency specified by P04.36.
10.0%
Setting range: -100.0%+100.0% (of the motor
rated current)
When the SM VF control mode is enabled, the
Frequency threshold function code is used to set the frequency
P04.36
for pull-in current switching in SM V/F
control
threshold for the switching between pull-in current 1 and pull-in current 2.
Setting range: 0.00HzP00.03 (Max. output
50.00Hz
frequency)
Reactive current When the SM VF control mode is enabled, the
closed-loop
function code is used to set the proportional
P04.37
50
proportional coefficient coefficient of reactive current closed-loop control.
in SM V/F control Setting range: 03000
Reactive current When the SM VF control mode is enabled, the
function code is used to set the integral coefficient
P04.38 closed-loop integral of reactive current closed-loop control.
30
time in SM V/F control Setting range: 03000
When the SM VF control mode is enabled, the
function code is used to set the output limit of the
P04.39
Reactive current reactive current closed-loop control. A greater value
indicates a higher reactive closed-loop
closed-loop output limit compensation voltage and higher output power of in SM
VF control the motor. In general, you do not need to modify
8000
the function code. Setting range: 016000
Enabling IF mode for 0: Disable
P04.40
0
AM 1
1: Enable
-59-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code
Name
Description
Default
When IF control is adopted for AM 1, the function
P04.41
code is used to set the output current. The value is Forward current setting
a percentage in relative to the rated current of the in IF mode for AM 1
motor.
120.0%
Setting range: 0.0200.0%
When IF control is adopted for AM 1, the function
Proportional coefficient code is used to set the proportional coefficient of
P04.42
350
in IF mode for AM 1 the output current closed-loop control.
Setting range: 05000
When IF control is adopted for AM 1, the function
Integral coefficient in IF code is used to set the integral coefficient of the
P04.43
150
mode for AM 1 output current closed-loop control.
Setting range: 05000
When IF control is adopted for AM 1, the function
code is used to set the frequency threshold for
switching off the output current closed-loop
P04.44
Frequency threshold for switching off IF mode for AM 1
control. When the frequency is lower than the value of the function code, the current closed-loop control in the IF control mode is enabled; and when the frequency is higher than that, the
10.00Hz
current closed-loop control in the IF control mode
is disabled.
Setting range: 0.00HzP04.50
Enabling IF mode for 0: Disable
P04.45
0
AM 2
1: Enable
When IF control is adopted for AM 2, the function
P04.46
Forward current setting code is used to set the output current. The value is a
percentage in relative to the rated current of the
in IF mode for AM 2 motor.
120.0%
Setting range: 0.0200.0% When IF control is adopted for AM 2, the function Proportional coefficient code is used to set the proportional coefficient of P04.47 in IF mode for AM 2 output current closed-loop control. Setting range: 350 05000
When IF control is adopted for AM 2, the function
Integral coefficient in IF code is used to set the integral coefficient of
P04.48
150
mode for AM 2 output current closed-loop control. Setting range:
05000
-60-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code
Name
Description
Default
When IF control is adopted for AM 2, the function
code is used to set the frequency threshold for
switching off the output current closed-loop
P04.49
Frequency threshold for switching off IF mode for AM 2
control. When the frequency is lower than the value of the function code, the current closed-loop control in the IF control mode is enabled; and when the frequency is higher than that, the
10.00Hz
current closed-loop control in the IF control mode
is disabled.
Setting range: 0.00HzP04.51
End frequency point for
P04.50 switching off IF mode P04.44 P00.03
25.00Hz
for AM 1
End frequency point for
P04.51 switching off IF mode P04.49 P00.03
25.00Hz
for AM 2
0: Max. efficiency
VF energy-saving
P04.52
1: Optimal power factor
0
mode selection
2: MTPA
VF energy-saving gain
P04.53
0.0%400.0%
coefficient
100.0%
5.5.5 Torque control
The VFD supports torque control and speed control. Speed control aims to
stabilize the speed to keep the set speed consistent with the actual running
speed, meanwhile, the max. load-carrying capacity is restricted by the torque
limit. Torque control aims to stabilize the torque to keep the set torque
consistent with the actual output torque, meanwhile, the output frequency is
restricted by the upper and lower limits.
-61-
IPE300 series engineering VFD (Booksize)
Function code
P00.00
Name
Speed control mode
Speed control
P03.32=0 (Disable torue control)
P00.00 (Speed control mode)
2
1
Start
0
Description
0: Sensorless vector control (SVC) mode 0 1: Sensorless vector control (SVC)
mode 1 2: Space voltage vector control mode
2 Note: Before using a vector control mode (0 or 1), enable the VFD to perform
motor parameter autotuning first.
-62-
P03.12 Torque set by
keypad
Keypad AI1
AI2
AI3
HDIA
Multi-step speed
MODBUS PROFIBUS/CANopen/DeviceNet
Ethernet
HDIB
EtherCAT/Profinet PLC card
0,1
P03.13
Set upper limit
2
Terminal function 29
Torque reference filter time
Motoring
3
Switching between torque
control and speed control
4
Valid Speed control
5 Invalid
6
Upper limit of brake torque
Upper limit of the torque during motoring
7 8 9 10
11
12
P03.11 Torque setup mode
selection
P17.15
Torque reference value
Keypad AI1
P03.21 Set upper limit of brake torque via
keypad
AI2 AI3 HDIA MODBUS
PROFIBUS/CANopen/DeviceNet
Ethernet
HDIB
P03.19 (Source of upper limit setup of
brake torque) 0
1
2
3 4
5
6 7 8
Brake
EtherCAT/Profinet
9
PLC card
10
P03.20 Set upper limit of the torque when motoring
via keypad
P03.18 (Source of upper limit setup of
the torque when motoring)
Keypad
0
AI1
1
AI2
2
AI3
3
HDIA
4
MODBUS
5
PROFIBUS/CANopen/DeviceNet
6
Ethernet
7
HDIB
8
EtherCAT/Profinet
9
Torque control limit
Output torque P17.09
Torque control
P03.14 (Source of upper limit frequency setup
of forward rotation in torque control)
0
Keypad
1
AI1
2
AI2
P03.16 Keypad limit value of upper limit frequency
of forward rotation in torque control
3
AI3
4
HDIA
5
Multi-step speed
6
MODBUS
7
PROFIBUS/CANopen/DeviceNet
8
Ethernet
9
HDIB
P03.15 (Source of upper limit frequency setup of reverse rotation in torque
control)
0
1 2 3 4 5 6 7 8 9
10
EtherCAT/Profinet
11
PLC card
Keypad AI1 AI2
P03.17 Keypad limit value of upper limit frequency of reverse rotation in
torque control
AI3
HDIA
Multi-step speed
MODBUS
PROFIBUS/CANopen/DeviceNet
Ethernet
HDIB
10
EtherCAT/Profinet
11
PLC card
PLC card
10
Basic operation guidelines
Default
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code
Name
Description
Default
Enabling torque 0: Disable
P03.32
0
control
1: Enable
0: Keypad (P03.12)
1: Keypad (P03.12)
2: AI1
3: AI2
4: AI3
5: Pulse frequency HDIA
6: Multi-step torque
Torque setting
P03.11
7: Modbus/Modbus TCP communication
0
method
8: PROFIBUS/CANopen/DeviceNet communication
9: Ethernet communication
10: Pulse frequency HDIB
11: EtherCAT/PROFINET/EtherNet IP communication
12: Programmable expansion card
Note: For these settings, 100% corresponds to the
motor rated current.
Torque set through
P03.12
-300.0%300.0% (of the motor rated current)
keypad
50.0%
Torque reference
P03.13
0.00010.000s
filter time
0.010s
0: Keypad (P03.16)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
Setting source of 5: Multi-step setting
forward rotation 6: Modbus/Modbus TCP communication
P03.14
upper-limit 7: PROFIBUS/CANopen/DeviceNet communication
0
frequency in torque 8: Ethernet communication
control
9: Pulse frequency HDIB
10: EtherCAT/PROFINET/EtherNet IP communication
11: Programmable expansion card
12: Reserved
Note: For these settings, 100% corresponds to the
maximum frequency.
P03.15 Setting source of 0: Keypad (P03.17)
0
-63-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code
Name
Description
Default
reverse rotation 1: AI1
upper-limit 2: AI2
frequency in torque 3: AI3
control
4: Pulse frequency HDIA
5: Multi-step setting
6: Modbus/Modbus TCP communication
7: PROFIBUS/CANopen/DeviceNet communication
8: Ethernet communication
9: Pulse frequency HDIB
10: EtherCAT/PROFINET/EtherNet IP communication
11: Programmable expansion card
12: Reserved
Note: For these settings, 100% corresponds to the
maximum frequency.
Forward rotation
upper-limit
P03.16 frequency set 0.00HzP00.03 (Max. output frequency)
50.00Hz
through keypad in
torque control
Reverse rotation
upper-limit
P03.17 frequency set 0.00HzP00.03 (Max. output frequency)
50.00Hz
through keypad in
torque control
0: Keypad (P03.20)
1: AI1
2: AI2
3: AI3
Setting source of 4: Pulse frequency HDIA
P03.18 electromotive 5: Modbus/Modbus TCP communication
0
torque upper limit 6: PROFIBUS/CANopen/DeviceNet communication
7: Ethernet communication
8: Pulse frequency HDIB
9: EtherCAT/PROFINET/EtherNet IP communication
10: Programmable expansion card
-64-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code
Name
Description
Default
11: Reserved
Note: For these settings, 100% corresponds to
triple the motor rated current.
0: Keypad (P03.21)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
5: Modbus/Modbus TCP communication
Setting source of
6: PROFIBUS/CANopen/DeviceNet communication
P03.19 braking torque
0
7: Ethernet communication
upper limit
8: Pulse frequency HDIB
9: EtherCAT/PROFINET communication
10: Programmable expansion card
11: Reserved
Note: For these settings, 100% corresponds to
triple the motor rated current.
Electromotive
P03.20 torque upper limit 0.0300.0% (of the motor rated current)
180.0%
set through keypad
Braking torque
P03.21 upper limit set 0.0300.0% (of the motor rated current)
180.0%
through keypad
P17.09 Output torque -250.0250.0%
0.0%
Torque reference
P17.15
-300.0300.0% (of the motor rated current)
value
0.0%
5.5.6 Motor parameters Check the safety conditions surrounding the motor and
load machineries before autotuning as physical injury may occur due to sudden
start of motor during autotuning. Although the motor does not run during
static autotuning, the motor is still supplied with power. Do not touch the
motor during autotuning; otherwise, electric shock
-65-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
may occur. Do not touch the motor before autotuning is completed. If the motor
has been connected to a load, do not carry out rotary autotuning.
Otherwise, the VFD may malfunction or may be damaged. If rotary autotuning is
carried out on a motor which has been connected to a load, incorrect motor
parameter settings and motor action exceptions may occur. Disconnect from the
load to carry out autotuning if necessary.
The VFD can drive both AMs and SMs, and it supports two sets of motor
parameters, which can be switched over by multifunction digital input
terminals or communication modes.
Start
Select running command channel
(P00.01)
Terminal (P00.01=1)
Communication (P00.01=0)
Keypad (P00.01=2)
P08.31 ones = 0
Terminal function 35 Switch motor 1 to motor 2
Switchover channel for motor 1 and
motor 2 (P08.31)
P08.31 ones = 2 P08.31ones = 3 P08.31 ones = 4
P08.31 ones = 1
Modbus/ Modbus TCP communication
PROFIBUS/ CANopen/ DeviceNet communication
Ethernet communication
EtherCAT/PROFINET/ EtherNet IP
communication
Invalid
Valid
Communication set value 2009H
BIT01=00
BIT01=01
Motor 1
Motor 2
The control performance of the VFD is based on accurate motor models. Therefore, you need to carry out motor parameter autotuning before running a motor for the first time (taking motor 1 as an example).
-66-
IPE300 series engineering VFD (Booksize)
Ready
Basic operation guidelines
P00.01=0 (controlled by keypad)
Synchronous motor
P02.00=1
Input motor nameplate (P02.15P02.19)
Motor type (P02.00)
Asynchronous motor
P02.00=0
Input motor nameplate (P02.01P02.05)
Set autotuning mode (P00.15)
Complete parameter rotary autotuning
Complete parameter static autotuning
Partial parameter rotary autotuning
Press “RUN” key to start autotuning
During autotuning
Autotuning finished
Note: 1. Motor parameters must be set correctly according to the motor
nameplate. 2. If rotary autotuning is selected during motor autotuning,
disconnect the motor from the load to put
the motor in static and no-load state. Otherwise, the motor parameter
autotuning results may be incorrect. In addition, autotune P02.06P02.10 for
AMs and autotune P02.20P02.23 for SMs. 3. If static autotuning is selected
for motor autotuning, there is no need to disconnect the motor from the load,
but the control performance may be impacted as only a part of the motor
parameters have been autotuned. In addition, autotune P02.06P02.10 for AMs
and autotune P02.20P02.22 for SMs. P02.23 can be obtained through
calculation. 4. Motor autotuning can be carried out on the present motor only.
If you need to perform autotuning on the other motor, switch the motor through
selecting the switch-over channel of motor 1 and motor 2 by setting the ones
place of P08.31.
-67-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Related parameter list:
Function code P00.01
P00.15
P02.00 P02.01 P02.02 P02.03 P02.04 P02.05 P02.06 P02.07 P02.08 P02.09 P02.10
P02.15 P02.16 P02.17
Name
Description
Channel of running commands
Motor parameter autotuning
Type of motor 1
0: Keypad 1: Terminal 2: Communication 0: No operation 1: Complete rotary parameter autotuning 2: Complete static parameter autotuning 3: Partial static parameter autotuning 4: Complete rotary parameter autotuning 2 (for asynchronous motors) 5: Partial static parameter autotuning 2 (for asynchronous motors) 0: Asynchronous motor (AM) 1: Synchronous motor (SM)
Rated power of AM 1 0.13000.0kW
Rated frequency of AM
1
0.01HzP00.03 (Max. output frequency)
Rated speed of AM 1 160000rpm
Rated voltage of AM 1 01200V
Rated current of AM 1 0.86000.0A
Stator resistance of AM
1
0.00165.535
Rotor resistance of AM 1
0.00165.535
Leakage inductance of
AM 1
0.16553.5mH
Mutual inductance of AM 1
0.16553.5mH
No-load current of AM 1 0.16553.5A
Rated power of SM 1 0.13000.0kW
Rated frequency of SM
1
0.01HzP00.03 (Max. output frequency)
Number of pole pairs of SM 1
1128
Default
0
0
0 Model depended 50.00Hz Model depended Model depended Model depended Model
depended Model depended Model depended Model depended Model depended Model
depended 50.00Hz
2
-68-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code
Name
P02.18 Rated voltage of SM 1 01200V
Description
P02.19 Rated current of SM 1 0.86000.0A
P02.20 P02.21 P02.22 P02.23 P05.01 P05.06
P08.31
P12.00
Stator resistance of SM
1
0.00165.535
Direct-axis inductance
of SM 1
0.01655.35mH
Quadrature-axis inductance of SM 1 0.01655.35mH
Counter-emf constant of
SM 1
010000
Function selection of
multifunction digital 35: Switch from motor 1 to motor 2
input terminals (S1S4, HDIA, HDIB)
0x000x14
Ones place: Switchover channel
0: Terminal
1: Modbus/Modbus TCP communication
2: PROFIBUS/CANopen/DeviceNet
Switching between motor 1 and motor 2
communication 3: Ethernet communication 4: EtherCAT/PROFINET/EtherNet IP
communication
Tens place: indicates whether to enable
switchover during running
0: Disable
1: Enable
Type of motor 2
0: Asynchronous motor (AM) 1: Synchronous motor (SM)
P12.01 Rated power of AM 2 0.13000.0kW
Rated frequency of AM
P12.02
2
0.01HzP00.03 (Max. output frequency)
P12.03 Rated speed of AM 2 160000rpm
P12.04 Rated voltage of AM 2 01200V
P12.05 Rated current of AM 2 0.86000.0A
Default Model depended Model depended Model depended Model depended Model
depended
300
00
0 Model depended 50.00Hz Model depended Model depended Model depended
-69-
IPE300 series engineering VFD (Booksize)
Basic operation guidelines
Function code P12.06
P12.07 P12.08
P12.09
Name
Stator resistance of AM 2
0.00165.535
Rotor resistance of AM
2
0.00165.535
Leakage inductance of
AM 2
0.16553.5mH
Mutual inductance of
AM 2
0.16553.5mH
Description
P12.10 No-load current of AM 2 0.16553.5A
P12.15 Rated power of SM 2 0.13000.0kW
P12.16 P12.17
Rated frequency of SM
2
0.01HzP00.03 (Max. output frequency)
Number of pole pairs of
SM 2
1128
P12.18 Rated voltage of SM 2 01200V
P12.19 Rated current of SM 2 0.86000.0A
P12.20 P12.21 P12.22 P12.23
Stator resistance of SM
2
0.00165.535
Direct-axis inductance
of SM 2
0.01655.35mH
Quadrature-axis inductance of SM 2 0.01655.35mH
Counter-emf constant of
SM 2
010000
Default
Model depended
Model depended
Model depended
Model depended
Model depended
Model depended
50.00Hz
2
Model depended
Model depended
Model depended
Model depended
Model depended
300
5.5.7 Start/stop control The start/stop control of the VFD involves three
states: start after a running command is given at power-on; start after power-
off restart is effective; start after automatic fault reset. The three
start/stop control states are described in the following.
There are three start modes for the VFD, which are start at starting
frequency, start after DC braking, and start after speed tracking. You can
select the proper start mode based on actual conditions.
For large-inertia load, especially in cases where reversal may occur, you can
choose to start after DC braking or start after speed tracking.
Note: It is recommended to drive SMs in direct start mode.
-70-
-71-
Direct start
P01.00 Running mode of start
Starting frequency of direct start
Hold time of starting frequency
0
Start after DC brake
N Jogging?
Y
1
2
Brake current
before start
Brake time before start
Straight-type
1f acceleration/deceleration P00.03
Apcrcoecleesrsation
Decperleorcaetsiosn
1t
0
P00.11
Acceleration
time
P01.05
Acceleration/deceleration mode
1
selection
P00.12 Deceleration time
1f P00.03
S curve-type acceleration/deceleration
Acprcoelceersatsion
Decperolecreastison
Start after speed-tracking
Apcrcoecleesrsation
Decperleorcaetsiosn
1f P08.06 Running frequency of jogging
1t
P08.07 Acceleration
time
P08.08 Deceleration time
1t
P00.11 Acceleration
time
P00.12 Deceleration time
1f
Jump frequency 3
Jump frequency 2
Jump frequency 1
1/2 jump amplitude 3 1/2 jump amplitude 3 1/2 jump amplitude 2 1/2 jump
amplitude 2 1/2 jump amplitude 1 1/2 jump amplitude 1
1t
1. Logic diagram for start after a running
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>