invt GD380L Series Elevator AC Drive Instruction Manual
- June 3, 2024
- invt
Table of Contents
Series Elevator AC Drive
Instruction Manual
GD380L Series Elevator AC Drive
Goodrive380L series lift-dedicated VFD
This guide describes the instructions of operating INVT variable-frequency
drive (VFD), including information about the safety precautions, terminal
functions, quick startup, common function parameters, keypad, external wiring,
and common faults. Please scan the e-manual platform QR code provided in part
8 or marked on the VFD housing for more information. If the end user is a
military unit or the product is used for weapon manufacturing, please comply
with relevant export control regulations in the Foreign Trade Law of the
People’s Republic of China, and complete necessary formalities.
Safety precautions
1.1 Warning signs
Sign
| Name| Description|
Abbreviation
---|---|---|---
Danger
| Danger| Severe personal injury or even death can result if related requirements are not followed.|
Warning
| Warning| Personal injury or equipment damage can result if related requirements are not followed.|
Forbid
| Electrostatic sensitive| The PCBA may be damaged if related requirements are not followed.|
Hot
| Attention Hot sides| Do not touch. The VFD base may become hot.|
| Electric
shock risk| As high voltage still presents in the bus capacitor after power
off, wait for at least five minutes (or 15 min / 25 min, depending on the
warning symbols on the machine) after power off to prevent electric shock.|
| Read manual| Read the operation manual before operating the equipment.|
Attention
| Attention| Actions taken to ensure proper running.|
Attention
1.2 Safety guidelines
| |
◊ Only trained and qualified professionals are allowed to carry out related
operations.
◊ Do not perform wiring, inspection or component replacement when power supply
is applied. Ensure all the input power supplies have been disconnected before
wiring or inspection, and wait for at least the time designated on the VFD or
until the DC bus voltage is less than 36V. The minimum waiting time is in the
following.
---|---|---
VFD model| Minimum waiting time
1 PH 220V 2.2kW| 5 minutes
3PH 220V 2.2kW-4kW| 5 minutes
3PH 380V 4kW-7.5kW| 5 minutes
| + Do not refit the VFD unless authorized; otherwise fire, electric shock or
other injury may result.
| +The base may become hot when the machine is running. Do not touch.
Otherwise, you may get burnt.
| +The electrical parts and components inside the VFD are electrostatic
sensitive.
Take measurements to prevent electrostatic discharge when performing related
operations.
1.3 Environment condition
Environment | Condition |
---|
Ambient
temperature| ◊-10—+50°C
◊ When the ambient temperature exceeds 40°C, derate 1% for every increase of
1°C.
◊ Do not use the VFD when the ambient temperature exceeds 50°C.
◊ In order to improve reliability, do not use the VFD in the places where the
temperature changes rapidly.
◊ When the VFD is used in a closed space, such as control cabinet, use a
cooling fan or air conditioner for cooling, preventing the internal
temperature from exceeding the temperature required.
◊ When the temperature is too low, if you want to use the VFD that has been
idled for a long time, install an external heating device before the use to
eliminate the freeze inside the VFD. Otherwise, the VFD may be damaged.
Relative humidity (RH)| ◊ RH: less than 90%
◊ Condensation is not allowed.
◊ The max. RH cannot exceed 60% in the environment where there are corrosive
gases.
Running environment| Install the VFD in a place:
◊ Away from electromagnetic radiation sources
◊ Without oil mist, corrosive gas, flammable gas, radioactive gas,
contaminative air, or contaminative liquid.
◊ Without the chance for foreign objects such as metal powder, dust, oil and
water to fall into the VFD (do not install the VFD onto combustible objects
such as wood)
◊ With low salt content
◊ Without direct sunlight.
Altitude| ◊ Lower than 1000 meters
◊ When the altitude exceeds 1000m, derate by 1% for every additional 100m.
4-When the installation site altitude exceeds 3000m, consult the local INVT
dealer or office.
Vibration| The max. amplitude of vibration cannot exceed 5.8m/s2 (0.6g).
Installation direction| Install the VFD vertically to ensure good heat
dissipation performance.
Peripheral wiring
Figure2-1 Peripheral equipment connection
Terminal function
3.1 Main circuit terminal diagram
Table 3-1 Main circuit terminals
Terminal symbol | Terminal name | Function |
---|---|---|
R/L1, S/L2, T/L3 | Main circuit power input | Connect R, S, T terminals when the |
input is 3PH AC 380V. Connect L1, L2, L3 terminals when the input is 3PH AC
220V. Connect any two of L1, L2, L3 terminals when the input is single phase
AC 220V.
(+), PB| Reserved terminals to connect to the external braking resistor|
Reserved terminals to connect to the external braking resistor
(-)| DC negative bus output terminal| DC negative bus output terminal
RO, TO| Emergency power main power input
port| When using the emergency rescue function, DC48V or AC220V power can be
input.
Al, A2| Emergency power auxiliary power input port| When using the emergency
rescue function normally, UPS AC220V power can be connected.
T1, T2| Inspection input port| For equipment maintenance and debugging in the
case of main power failure. AC220V power supply can be connected.
U, V, W| VFD outputs| 3PH AC output terminals, which connect to the motor in
most cases
| OGrounding terminal| Grounding terminal
3.2 Control circuit wiring diagram
Table 3-2 Control circuit terminals
Terminal name | Description |
---|---|
+24V | Used to provide input digital working power from the internal to the |
external Capacity: 200mA
COM| +24V common terminal
Y1| 1. Switch capacity: 50mA/30V
2. Output frequency range: 0-1kHz
CME| Common terminal of open collector output
PA11| Encoder interface
1. Applicable to 24V push-pull, OC encoders
2. Response frequency: 100kHz
P13(1)
PT+| PT100 interface
1. Resolution: 1°C
2. Range: -20°C-150°C
3. Detection precision: ±3°C
PT-
+10V| Used to externally provide 10V reference power supply. Max. output
current: 50mA.
Generally used as the regulation power supply of the external potentiometer
whose impedance is greater than 5k0.
GND| Reference zero potential
All| 1. Input range: For Al, 0-10V/0-20mA. All is switched by jumper J8.
2. Input impedance: 20k0 for voltage input or 5000 for current input.
3. Resolution: 5mV when 10V corresponds to 50Hz.
4. Error: ±1% at 25°C
GND| Reference zero potential of +10V
A01| 1. Output range: 0-10V or 0-20mA
2. Whether voltage or current is used for output is set through the jumper
J3.
3. Resolution: 10mV when 10V corresponds to 50Hz.
CANN| CANopen communication interface
CANL
+24V| STO function input terminal
H1
+24V
H2
Note:
- When jumper cap J5/J6 is shorted to Simple, a simple closed-loop control can be achieved.
- RJ45 is an external keypad interface. It is recommended to use standard RJ45 connectors with short body.
3.3 Terminal block circuit wiring diagram
Table 3-3 Terminal block circuit terminals
Terminal name | Description |
---|---|
S1-511 | Regular digital input terminal |
1. Internal impedance: 3.3k0
2. 12-30V voltage input is acceptable.
3. Bi-direction input terminal, supporting both NPN and PNP
4. Max. input frequency: 1kHz
5. All of them are programmable digital input terminals. Users can set the
terminal function by function code.
COM| +24V common terminal
Al2| 1. Input range: For Al2, 0-10V/0-20mA. Al2 is switched by DIP switch
SW1.
2. Input impedance: 20k0 for voltage input or 5000 for current input
3. Resolution: 10mV when 5mV corresponds to 50Hz.
4. Error: ±1% at 25°C
GND| Reference zero potential of +10V
Y2| 1. Switch capacity: 50mA/30V
2. Output frequency range: 0-1kHz
CME| Common terminal of open collector output
RO1A| RO1 output; RO1A: NO; RO1B: NC; RO1C: common Contact capacity:
3A/AC250V, 1A/DC3OV
RO16
RO1C
RO2A| RO2 output; RO2A: NO; RO2B: NC; RO2C: common Contact capacity:
3A/AC250V, 1A/DC3OV
RO26
RO2C
RO3A| RO3 output. RO3A: NO; RO3C: NC Contact capacity: 3A/AC250V, 1A/DC3OV
RO3C
Quick startup
4.1 Check before power-on
| Ensure that all terminals have been securely connected.
---|---
Ensure that the motor power matches the VFD power.
4.2 First power-on
After confirming the wiring and power are correct, close the air switch of the AC power supply at the VFD input side to power on the VFD. The keypad displays as the following figure, indicating that the VFD is ready for run.
The quick startup diagram is as follows:
Keypad
Table 5-1 LCD keypad
No. | Item | Description |
---|---|---|
1 | Status indicator | RUN/TUNE |
running.
FWD/REV| Forward or reverse running indicator Off: The VFD is running
forward.
On: The VFD is running reversely.
No.| Item|
Description
---|---|---
| |
LOCAUREMOT
| Indicates whether the VFD is controlled through the keypad, terminals, or
communication.
Off: The VFD is controlled through the keypad. Blinking: The VFD is controlled
through terminals.
On: The VFD is controlled through remote communication.
TRIP
| Fault indicator
On: The VFD is in fault state. Off: The VFD is in normal state.
2| Keys| | Programming key| Press it to enter or exit level-1 menus
| Confirmation key| Press it to enter menus in cascading mode or confirm the
setting of a parameter.
| UP key| Press it to increase data or move upward.
| Down key| Press it to decrease data or move downward.
| Right-shifting key| Press it to select display parameters rightward in the
interface for the VFD in stopped or running state or to select digits to
change during parameter setting.
| Run key| Press it to run the VFD when using the keypad for control.
| Stop/Reset key| Press it to stop the VFD that is running. The function of
this key is restricted by P07.05.
In fault alarm state, this key can be used for reset in any control modes.
| Multifunction shortcut key| The function is determined by P07.04.
Common function parameters
6 Common function parameters
The following table briefly describes some common function parameters and typical values.
“0” indicates that the value of the parameter can be modified when the VFD is in stopped or running state.
“©” indicates that the value of the parameter cannot be modified when the VFD is in running state.
“•” indicates that the value of the parameter is detected and recorded, and cannot be modified.
(The VFD automatically checks and constrains the modification of parameters, which helps prevent incorrect modifications.)
Function code | Name | Description | Default | Modify |
---|---|---|---|---|
P00.00 | Speed control mode | 0: Sensorless vector control (SVC) 0 |
1: SVC 1
2: Reserved
3: Closed-loop vector control| 0|
P00.01| Channel of running
commands| 0: LED keypad (the indicator is off)
1: Terminal (the indicator blinks)
2: LCD keypad (the indicator is off)
3: CAN (the indicator is on)
4: CANopen (the indicator is on)| 1|
P00.02| Rated speed of the elevator| 0‘100-4.000m/s| 1.000m/s|
P00.03| Speed command selection| 0: Keypad
1: All
2: Al2
3: Multi-step speed running
4: Remote communication
5: All tracking running
6: CAN communication-based setting
7: CAN communication-based reference
8: CANopen communication-based setting
9: CANopen communication-based reference| 3|
P00.04| Max. output frequency| 1.00-600.00Hz| 50.00Hz|
P00.05| Speed set through keypad| 0.00Hz—P00.02 (Rated speed of the elevator)|
0.00Hz| 0
P00.06| Running direction| 0: Run at the default direction.
1: Run at the opposite direction.
2: Disable reverse running| 0|
P00.07| Carrier frequency| 0: Fixed carrier frequency. The VFD runs at the
carrier frequency set in P00.08.
1: Automatic regulation| 0|
P00.08| Carrier frequency setting| | 8.0kHZ|
Function
code| Name| Description| Default| Modify
---|---|---|---|---
| | Advantage of high carrier frequency: ideal current waveform,little
current harmonic wave and motor noise.
Disadvantage of high carrier frequency: increasing the switch loss,
increasing VFD temperature and the impact to the output capacity. The VFD
needs to derate on high carrier frequency. At the same time, the leakage and
electrical magnetic interference will increase.
On the contrary, an extremely-low carrier frequency may cause unstable
operation at low frequency, decrease the torque, or even lead to oscillation.
The carrier frequency has been properly set in the factory before the VFD is
delivered. In general, you do not need to modify it.
When the frequency used exceeds the default carrier frequency, the VFD needs
to derate by 20% for each increase of 1k carrier frequency. Setting range:
1.0-16.0kHz| |
P00.09| Motor parameter autotuning| 0: No operation
1: Rotating parameter autotuning on empty-load asynchronous motor
2: Static parameter autotuning on asynchronous motor
3: Rotating parameter autotuning on empty-load synchronous motor
4: Static parameter autotuning on synchronous motor
5: Rotating parameter autotuning on synchronous motor with load| 0| 0
P00.10| Function
parameter
restore| 0: No operation
1: Restore default values
2: Clear fault records
3. Roll back function parameters, reading function parameters that are saved
when the LSB of P07.01 is set to 5.| 0|
P01.00| Start mode| 0: Start-up directly: start from the starting frequency
P01.01
1: Start-up after DC braking: start the motor from the starting frequency
after DC braking (setting P01.04 and P01.05) It is suitable in the cases where
reverse rotation may occur to the low inertia load during starting.| 0|
P01.07| Stop mode| 0: Decelerate to stop. After the stop command becomes
valid, the VFD decelerates to decrease the output frequency during the set
time. When the frequency decreases to the stop speed, the VFD stops.
1: Coast to stop: after the stop command becomes valid, the VFD ceases the
output immediately. And the load coasts to stop at the mechanical inertia. And
the load coasts to stop according to mechanical inertia.| 0| 0
P01.08| Starting
frequency of
DC braking for
stop| Starting frequency of DC braking for stop: During the deceleration to
stop, the VFD starts DC braking for stop when running frequency reaches the
starting frequency determined by P01.09.
Wait time before DC braking: The VFD blocks the output before starting DC braking. After this wait time, DC braking is started so as to prevent overcurrent caused by DC braking at high speed.
DC braking current for stop: It indicates the applied DC braking energy.
Stronger current indicates greater DC braking effect.
DC braking time for stop: It indicates the hold time of DC braking. If the
time is 0, DC braking is invalid, and the VFD decelerates to stop within the
specified time. Setting range of P01.08: 0.00Hz—P00.04 (Max. output frequency)
Setting range of P01.09: 0.00-30.00s Setting range of P01.10: 0.0-100.0% (of
the VFD rated output current)
Setting range of P01.11: 0.0-50.0s
| 0.00Hz| 0
P01.09| Demagnetizati
on time| “Os| 0
P01.10| DC braking _current for stoa , _DC braking time for stop| 0.0%| 0
P01.11| 0.0s| 0
P02.00| Motor type| 0: Asynchronous motor (AM) 1: Synchronous motor (SM)| 0| 0
P02.01| Motor rated power| 0.1-3000.0kW| Model depended| 0
P02.02| Motor rated frequency| 0.01 Hz—P00.04 (Max. frequency)| 50.00Hz| 0
P02.03| Motor rated speed| 1-36000rpm| Model depended| 0
Function code| Name| Description| Default| Modify
---|---|---|---|---
P02.04| Motor rated voltage| 0-1200V| Model depended| 0
P02.05| Motor rated current| 0.8-6000.0A| Model depended| 0
P02.06| Stator resistance of AM| 0.001-65.5350| Model depended|
P02.07| Rotor resistance of AM| 0.001-65.5350| Model depended| 0
P02.08| Leakage inductance of
AM| 0.1-6553.5mH| Model depended|
P02.09| Mutual inductance of AM| 0.1-6553.5mH| Model depended|
P02.10| No-load current of AM| 0.1-6553.5A| Model depended| 0
P02.11| Direct-axis inductance of SM| 0.01-655.35mH| Model depended| 0
P02.12| Quadrature-axis inductance of SM| 0.01-655.35mH| Model depended| 0
P02.13| CountS er-emf of M| 0-10000V| 320V| 0
P02.14| Pulley diameter| 100-2000m| 500mm| 0
P02.15| DEC ratio| 0.50-50.00| 1.00| 0
P02.16| Speed ratio| 0-65535| 1000| 0
P05.01| Function of Si terminal| 0: No function
1: Up running (FWD)
2: Down running (REV)
3: Running in inspection (EXM)
4: Emergency operation (EMER)
5: Coast to stop (FSTP)
6: Fault reset (RET)
7: External fault (EF)
8: Multi-step speed terminal 1 (MS1)
9: Multi-step speed terminal 2 (MS2)
10: Multi-step speed terminal 3 (MS3)
11: Up forced DEC 1 (UFS1) 12. Up forced DEC 2 (UFS2) 13: Up forced DEC 3
(UFS3) 14. Down forced DEC 1 (DFS1)
15: Down forced DEC 2 (DFS2)
16. Down forced DEC 3 (DFS3)
17: Contactor feedback signal (TB)
18: Brake feedback signal (FB)
19: VFD enabling (ENA)
20: Forced decelerate to stop
21: Emergency mode
22. Motor overheating
23: Main power supply input disconnected (for India)
24: UPS input disconnected by main control (for India)
25: Base lockout
26: Leveling signal
27-40: Reserved| 0| 0
P05.02| Function of S2 terminal| 1|
P05.03| Function of S3 terminal| 2|
P05.04| Function of S4 terminal| 8|
P05.05| Function of S5 terminal| 9|
P05.06| Function of S6 terminal| 10| 0
P05.07| Function of S7 terminal| 0| 0
P05.08| Function of S8 terminal| 4| 0
P05.09| Function of S9 terminal| 0| 0
P05.10| Function of 510 terminal| 0| 0
P05.11| Function of S11 terminal| 0| 0
P05.12| Reserved| 0| 0
P05.13| Input terminal
polarity| The function code is used to set the polarity of input terminals.
When a bit is 0, the input terminal is positive; when a bit is 1, the input
terminal is negative.Setting range: 0x000-0x7FF| Ox000| 0
P05.14| Digital input filter time| The function code is used to specify the
filter time of S1-S11 terminal sampling. In strong interference cases,
increase the value to avoid maloperation.
0.000-1.000s| 0.002s| 0
P05.16| Enable power-on terminal detection| 0: Disable
1: Enable (terminal command power-on response and terminal command response to
UV fault rectification)| 1| 0
P06.01| Y1 output| 0: No output
1: Lift in operation
2: Up operation
3: Down running
4: Fault output
5: Running at zero speed
6: Ready for running
7: Brake control
8: Contactor control
9: Frequency reached
10: Frequency level detection FDT output
11: Reserved
12: Reserved
13: Light-load direction detection completed
14: Down as the light-load direction detection result| 1| 0
P06.02| Y2 output selection| 0| 0
P06.03| Relay output RO1| 0| 0
P06.04| Relay output RO2| 7| 0
P06.05| Relay output RO3| 8| 0
Function code| Name| Description| Default| Modify
---|---|---|---|---
| | 15: Up as the light-load direction detection result
16: Running 1 (excluding current withdrawal)
17: STO action
18: SPI fault output
19: UPS control signal output (India)
20: Sealed-star output
21: Waiting after autonomous rescue leveling| |
P06.07| Output terminal polarity
selection| The function code is used to set the polarity of output terminals.
When the current bit is set to 0, the output terminal is positive.
When the current bit is set to 1, the output terminal is negative.
Setting range: 0x00-0x1F| Ox00| 0
P06.08| A01 output| 0: Running speed 1. Set speed
2: Rotational speed
3: Output Current
4: Output voltage
5: Output power
6: Output torque
7: All input
8: Al2 input| 0| 0
P07.01| Parameter
copy| Ones place:
0: No operation
1: Upload parameters from the local address to the keypad
2: Download parameters (including motor parameters) from the keypad to the
local address
3: Download parameters (excluding group P02) from the keypad to the local
address
4: Download parameters (including only motor parameters of P02) from the
keypad to machine.
5:Save parameters (including motor parameters) of the machine
Note: After any operation among 1-5 is complete, the parameter restores
to 0. Tens place: Reserved
Thousands place:
Indicates the response speed of the keypad. 0: Low speed
1: Medium speed
2: High speed| Ox100| 0
P09.00| Multi-step speed 0| 0.000m/s-P00.02| 0.080m/s| 0
P09.01| Multi-step speed 1| 0.000m/s-P00.02| 0.700m/s| 0
P09.02| Multi-step speed 2| 0.000m/s-P00.02| 0.180m/s| 0
P09.03| Multi-step speed 3| 0.000m/s-P00.02| 0.300m/s| 0
P09.04| Multi-step speed 4| 0.000m/s-P00.02| 0.000m/s| 0
P09.05| Multi-step speed 5| 0.000m/s-P00.02| 0.000m/s| 0
P09.06| Multi-step speed 6| 0.000m/s-P00.02| 0.000m/s| 0
P09.07| Multi-step speed 7| 0.000m/s-P00.02| 0.000m/s|
P09.08| Multi-step speed priority| 0: CHINESE TYPE
1: ISTANBUL TYPE
2: KONYA TYPE
3: ADANA TYPE| 0| 0
P09.09| ACC time| 0.1-360.0s| 2.0s| 0
P09.10| DEC time| 0.1-360.0s| 2.0s|
P09.11| S-curve ACC start segment duration| 0.1-360.0s| 2.0s| 0
P09.12| S-curve ACC end segment duration| 0.1-360.0s| 2.0s| 0
P09.13| S-curve DEC start segment duration| 0.1-360.0s| 2.0s|
P09.14| S-curve DEC end segment duration| 0.1-360.0s| 2.0s|
P09.15| S-curve start segment duration during stop| 0.1-360.0s| 2.0s| 0
P09.16| S-curve end segment duration during stop| 0.1-360.0s| 2.0s| 0
Function
code| Name| Description| Default| Modify
---|---|---|---|---
P09.17| Running speed
at maintenance| 0.001m/s—P00.02| 0.200m/s| 0
P09.18| ACC/DEC time at maintenance| 0.1-360.0s| 4.0s| 0
P09.19| Forced DEC time| 0.0-360.0s| 0.0s| 0
P09.20| Emergency running speed| 0.001m/s—P00.02| 0.100m/s| 0
P09.21| Emergency ACC/DEC time| 0.1-360.0s| 20.0s| 0
P09.22| Leveling segment| 0-7| 0| 0
P09.23| Leveling speed| 0.001m/s—P00.02| 0.010m/s| 0
P09.24| DEC time for creeping to stop| 0.1-360.0s
During deceleration to stop, when the speed reached the value set in P01.12,
the curve of deceleration to stop switches to those set in P09.15, P09.16, and
P09.24.| 2.0s| 0
P09.25| Speed threshold for light-load detection in open-loop control|
5.00-20.00Hz| 5.00Hz| 0
P11.00| Protection against phase
loss| Ox000-0x111
Ones place:
0: Protection against input phrase loss disabled 1: Protection against input
phrase loss enabled Tens place:
0: Protection against output phrase loss disabled 1: Protection against output
phrase loss enabled LED hundreds place:
0: Hardware input phrase loss protection disabled
1: Hardware input phrase loss protection enabled| Ox110| 0
P11.01| Frequency drop at transient power-off| 0: Disable 1: Enable| 0| 0
P11.02| Frequency drop rate at transient power-off| Setting range:
0.00Hz/s—P00.04 (max. output frequency) After the power loss of the grid, the
bus voltage drops to the sudden frequency-decreasing point, the VFD begin to
decrease the running frequency at P11.02, to make the VFD generate power
again. The returning power can maintain the bus voltage to ensure a rated
running of the VFD until the recovery of Power.| Voltage class| 380V| 660V
---|---|---
Frequency decease at sudden power fallure| 460V| 800V
Note:
1. Adjusting the parameter properly can prevent the stop aused by the
VFD protection during shifting the gird.
2. The function can be enabled only after the input phase loss protection is
disabled.
10.00 Hz/s|
P11.03| Overvoltage stalling
protection| 0: Disable
1: Enable| 0| 0
P11.04| Overvoltage stalling protection voltage| 120-145% (standard bus
voltage) (380V)| 136%| 0
120-145% (standard bus voltage) (220V)| 120%
P11.05| Current limit action| During accelerated running, as the load is too
large, the actual acceleration rate of motor is lower than that of output
frequency, if no measures are taken, the VFD may trip due to overcurrent
during acceleration.
Ones place: Current limit action
0: Invalid
1: Always valid| 0| 0
P11.06| Automatic current limit threshold| Current-limit protection function
detects output current during running, and compares it with the current-limit
level defined by P11.06, if it exceeds the current-limit level, the VFD will
run at stable frequency during accelerated running, or run in decreased
frequency during constant-speed running; if it exceeds the current-limit level
continuously, the VFD output frequency will drop continuously until reaching
lower limit frequency. When the output current is detected to be lower than
the current-limit level again, it will continue accelerated running. Setting
range of P11.06: 50.0-200.0% (of the VFD rated output current)
Setting range of P11.07: 0.00-50.00Hz/s| 160.0%| 0
P11.07| Frequency drop rate
during current limit| 10.00 Hz/s| 0
Function
code| Name| Description| Default| Modify
---|---|---|---|---
P11.20| STO function selection| Ones place:
0: STO function disabled
1: STO function enabled
Tens place:
0: Alarm locked (the SAFE fault can be reset manually)
1: Alarm not locked (the SAFE fault can be reset automatically)| 0x01| 0
P15.27| CAN/CANopen communication baud rate| 0: 1000kbps
1: 800kbps
2: 500kbps
3: 250kbps
4: 125kbps
5: 100kbps
6: 50kbps
7: 20kbps| 3|
P15.28| CAN/CANopen communication address| 0-127| 1| O
P20.00| Encoder type selection| 0: Incremental encoder (AB)
1: ABZUVW encoder
2: Resolver-type encoder
3: Sin/Cos encoder without CD signals
4: Sin/Cos encoder with CD signals
5: EnDat absolute encoder| 0| 0
P20.01| Encoder pulse
count| Number of pulses generated when the encoder revolves for one circle.
Setting range: 0-60000| 1024| ©
P20.02| Encoder direction| Ones place: AB direction
0: Forward 1: Reverse Tens place: Reserved
Hundreds place: CD/UVW pole signal direction
0: Forward 1: Reverse| Ox000| 0
P20.06| Speed ratio between encoder mounting shaft and motor| You need to set
the function parameter when the encoder is not installed on the motor shaft
and the drive ratio is not 1.
Setting range: 0.001-65.535| 1.000| 0
P20.09| Initial angle of
Z pulse| Relative electric angle between the encoder Z pulse and the motor
pole position.
Setting range: 0.00-359.99| 0.00| 0
P20.10| Pole initial angle| Relative electric angle between the encoder
position and the motor pole position.
Setting range: 0.00-359.99| 0.00| 0
Common faults and solutions
This chap er briefly describes some common faults and the solutions.
Fault
code| Fault type| Possible cause| Solution
---|---|---|---
OUt1| 111 Inverter unit U-phase protection| ACC is too fast.
IGBT module is damaged. Misoperation caused by interference.
Drive wires are poorly connected.
To-ground short circuit occurs.| Increase ACC time.
Replace the power unit; Check drive wires;
Check whether there is strong interference surrounding the peripheral device.
OUt2| [2] Inverter unit V-phase protection
OUt3| [3] Inverter unit W-phase protection
OV1| [7] Overvoltage during ACC| Exception occurred to input voltage.
Large energy feedback;
Lack of braking units; Energy-consumption braking is not enabled.| Check the
input power. Check whether load DEC time is too short or the motor starts
during rotating;
Install dynamic brake components.
Check the setting of related function codes.
OV2| [8] Overvoltage during DEC
OV3| [9] Overvoltage during constant
speed running
0C1| [4] Overcurrent during ACC| ACC/DEC is too fast;
The voltage of the grid is too low; VFD power is too small.
Load transient or exception occurred.
To-ground short circuit or output phase loss occurred; Strong external
interference sources;
The overvoltage stall protection is not enabled. Phase loss on output side.|
Increase ACC/DEC time. Check the input power; Select the VFD with larger
power;
Check whether the load is short circuited (to-ground short circuit or line-to-
line short circuit) or the rotation is not smooth.
Check the output wiring; Check if there is strong interference;
Check the related function code settings.
Check whether phase loss occurred on output side.
0C2| [5] Overcurrent during DEC
0C3| [6] Overcurrent during constant speed running
UV| [10] Bus undervoltage| The voltage of the grid is too low. The overvoltage
stall protection is not enabled.| Check the grid input power supply.
Check the setting of related function codes.
OL1| [11] Motor overload| The voltage of the grid is too low. The motor rated
current is set incorrectly.
The motor stall occurs or the load transient is too large.| Check the grid
voltage. Reset the motor rated current.
Check the load and adjust the torque boost quantity.
OL2| [12] VFD overload| ACC is too fast.
The motor in rotating is restarted. The voltage of the grid is too low. Load
too large.
The motor power is too large.| Increase ACC time.
Avoid restart after stop. Check the grid voltage; Select the VFD with larger
power; Select a proper motor.
Fault code| Fault type| Possible cause| Solution
---|---|---|---
SPI| [13] Phase loss on input side| Phase loss or violent fluctuation occurred
on input R, S, T.| Check the input power. Check the installation wiring.
SPO| [14] Phase loss on output side| Phase loss output occurs to U, V, W (or
the three phases of the load are seriously asymmetrical).| Check the output
wiring. Check the motor and cable.
OH1| [15] Rectifier module overheating| Air duct is blocked or fan is damaged.
Amb hige temperature is too Long-time overload running.| Ventilate the air
duct or replace the fan.
Lower the ambient temperature.
OH2| [16] Inverter module overheat
EF| [17] External fault| SI external faulty input terminal action.| Check
external device input.
CE| [18] RS485 communication fault| Incorrect baud rate. Communication line
fault; Incorrect communication address. Communication suffers from strong
interference.| Set proper baud rate;
Check the wiring of communication interfaces; Set the proper communication
address. Replace or change the wiring to enhance the anti-interference
capacity.
HE| [19] Current detection fault| Poor contact of the connector of control
board.
Hall component is damaged. Exception occurred to amplification circuit.| Check
the connector and re-plug;
Replace the hall component. Replace the main control board.
tE| [20] Motor
autotuning fault| The motor capacity does not match the VFD capacity. Motor
parameter is set improperly.
The parameters gained from autotuning deviate sharply from the standard
parameters; Autotuning timeout.| Change the VFD model. Set proper motor type
and nameplate parameters. Empty the motor load and carry out autotuning again.
Check the motor wiring and parameter setup;
Check whether the upper limit frequency is larger than 2/3 of the rated
frequency.
EEP| [21] EEPROM operation fault| Error in reading or writing control
parameters.
EEPROM is damaged.| Press STOP/RST to reset. Replace the main control board.
PIDE| [22] PID feedback offline fault| PID feedback offline.
PID feedback source disappears.| Check PID feedback signal wires;
Check PID feedback source.
bCE| [23] Braking unit fault| Fault occurred to the brake circuit or the
braking pipe is damaged.
Resistance of the external braking resistor is small.| Check the braking unit,
and replace with new braking pipe;
Increase the brake resistance.
END| [24] Running time
reached| The actual running time of the VFD is longer than the internal set
running time.| Ask for the supplier and adjust the set running time.
OL3| [25] Electronic
overload fault| The VFD reports overload pre-alarm according to the setting.|
Check the load and the overload pre-alarm points.
PCE| [26] Keypad
communication fault| Keypad cable connected improperly or disconnected. Keypad
cable too long, causing strong interference. Keypad or mainboard communication
circuit error.| Check the keypad cable to determine whether a fault occurs.
Check for and remove the external interference source. Replace the hardware
and seek maintenance services.
UPE| [27] Parameter
upload error| Keypad cable connected improperly or disconnected. Keypad cable
too long, causing strong interference. Keypad or mainboard communication
circuit error.| Check for and remove the external interference source. Replace
the hardware and seek maintenance services. Replace the hardware and seek
maintenance services.
DNE| [28] Parameter
download error| Keypad cable connected improperly or disconnected. Keypad
cable too long, causing strong interference. Data storage error occurred to
the keypad.| Check for and remove the external interference source. Replace
the hardware and seek maintenance services. Re-back up the data on the keypad.
E-DP| [29] PROFIBUS
communication fault| Communication address is not correct.
The matching resistance is not set well.
The master GSD file is not set up. The peripheral interference is too large.|
Check the related settings; Check the surrounding environment, and eliminate
interference effects.
E-NET| [30] Ethernet
communication fault| The address of Ethernet is set improperly.
The communication mode is set improperly.
The peripheral interference is too large.| Check the related settings; Check
the communication mode selection;
Check the surrounding environment, and eliminate interference effects.
E-CAN| [31) CANopen communication fault| Line contact is poor.
The matching resistor is not switched on.
Communication baud rates do not match.
The peripheral interference is too large.| Check the line: switch on the
matching resistor.
Set the same baud rate; Check the surrounding environment, and eliminate
interference effects.
ETH1| [32] To-ground short-circuit fault 1| VFD output is short connected to
the ground.
There is a fault in the current detection circuit.| Check whether the motor
wiring is normal.
Replace the hall component; Replace the main control board.
ETH2| [33] To-ground short-circuit fault 2| VFD output is short connected to
the ground.| Check whether the motor wiring is normal.
Fault code| Fault type| Possible cause| Solution
---|---|---|---
| | There is a fault in the current detection circuit.| Replace the hall
component; Replace the main control board.
dEu| [34] Speed deviation fault| The load is too heavy or stalled.| Check the
load to ensure it is proper, and increase the detection time;
Check whether the control parameters are set properly.
STo| [35] Mal-adjustment fault| Control parameters of the synchronous motor is
set improperly.
Autotuned parameters are not accurate;
The VFD is not connected to the motor.| Check the load and ensure the load is
normal.
Check whether control parameters are set correctly. Increase the mal-
adjustment detection time.
LL| [36] Electronic underload fault| The VFD reports underload pre-alarm
according to the setting.| Check the load and the underload pre-alarm points.
ENC1O| [37] Encoder disconnection fault| Incorrect encoder wiring, causes
the failure to get the encoder signal.
Incorrect encoder parameter settings.| Check the wiring.
Check encoder parameter settings.
ENC1D| [38] Encoder reserve-rotation fault| Incorrect encoder signal
direction.| Set the function code to change the direction or reverse the AB
signal wires.
ENC1Z| [39] Encoder Z-pulse disconnection fault| The Z-pulse signal cable is
not connected.| Check the Z-pulse signal cable.
ENC1U| [40] U disconnection| There are no U, V, or W signals or there is
interference.| Check the U, V, and W signal wiring.
OT| [43] Motor overtemperature fault| Motor overtemperature signal.|
BAE| [45] Brake fault| Brake signal and control signal are inconsistent.
Feedback terminal signal is interfered.| Check whether the brake is in good
condition.
Check feedback terminal signal.
CONE| [46] Contactor fault| Brake signal and control signal are inconsistent.
Feedback terminal signal is interfered.| Check whether the contactor is in
good condition.
Check feedback terminal signal.
nPoS| :47] CD signal unavailable| The sine-cosine or absolute-value encoder
position signal is lost. The encoder is interfered.| Check whether the encoder
is in good condition.
Check whether the VFD and encoder are grounded.
SAFE| [49] STO card fault| The STO card safety circuit does not work.
The expansion card type is incorrect.| Check whether the STO cardis in good
condition.
Check whether the expansion card type is correct.
STL1| [50] STO card circuit 1 exception| Circuit 1 of the STO card does
not work.| Check whether the STO card is in good condition.
Check circuit 1 of the STO card.
STL2| [51] STO card circuit 2 exception| Circuit 2 of the STO card does not
work.| Check whether the STO card is in good condition.
Check circuit 2 of the STO card.
STL3| [52] STO internal circuit exception| The internal circuits of the STO
card do not work.| Check whether the circuits of the VFD control board is in
good condition.
CrCE| [53] Safety code CRC exception| Exceptions occur in the verification of
the safety circuit code.| Check whether the control board is in good
condition.
bOC| [54] Braking pipe overcurrent fault| Braking pipe resistance is
unmatched.| Check the resistance of braking pipe.
bOL| [55] Braking pipe overload| Braking pipe resistance is unmatched.
The device is in the energy feedback state for long period.| Check the
resistance of braking pipe.
Check the operating conditions.
C2-Er| [64] Expansion card communication fault| Expansion card is connected
improperly.
Expansion card is damaged.| Check the expansion card connection.
Check whether the expansion card is in good condition.
More information
Please contact us for any information about the products. It is necessary to
provide the product model and serial number during consultation.
To obtain more information, you can: Contact INVT local office. Visit
www.invt.com or scan the QR code of INVT.
Manual information may be subject to change without prior notice. 202208(V1.0)
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>