US5-B5-B1 Powerful Programmable Logic Controller
“`html
Product Information
Specifications
-
Available Versions: UniStream Built-in and UniStream Built-in
Pro -
Model Numbers: US5, US7, US10, US15 with various
configurations -
Power Features: VNC, Multi-level password protection, Built-in
alarms -
I/O Options: Various COM protocols, Fieldbus support, Advanced
communication options -
Programming Software: All-in-One software for configuration and
applications
Product Usage Instructions
Before You Begin
Before installing the device, make sure to read and understand
the user manual and verify the kit contents.
Alert Symbols and General Restrictions
Pay attention to the alert symbols for potential dangers or
restrictions. Follow safety guidelines and dispose of the product
properly.
Environmental Considerations
-
Ensure proper ventilation with a 10mm space between device
edges and enclosure walls. -
Avoid installation in areas with excessive dust, moisture,
heat, or vibration. -
Avoid contact with water or high-voltage cables.
-
Do not connect/disconnect the device when power is on.
Frequently Asked Questions (FAQ)
Q: Can I use the device without reading the user manual?
A: It is highly recommended to read and understand the user
manual before using the device to ensure proper installation and
operation.
Q: What should I do if I encounter a warning symbol during
use?
A: If you encounter any warning symbols, refer to the associated
information in the manual carefully to prevent any potential
dangers or damages.
Q: Can I install the device in any environment?
A: No, follow the environmental considerations provided in the
manual to ensure optimal performance and safety of the device.
“`
User Guide
UniStream®
Built-in
US5-B5-B1, US5-B10-B1, US5-B5-TR22, US5-B10-TR22, US5-B5-T24, US5-B10-T24,
US5-C5-B1, US5-C10-B1, US5-C5-TR22, US5-C10-TR22, US5-C5-T24, US5-C10-T24
US7-B5-B1, US7-B10-B1, US7-B5-TR22, US7-B10-TR22, US7-B5-T24, US7-B10-T24,
US7-C5-B1, US7-C10-B1, US7-C5-TR22, US7-C10-TR22, US7-C5-T24, US7-C10-T24
US10-B5-B1, US10-B10-B1, US10-B5-TR22, US10-B10-TR22, US10-B5-T24, US10-B10-T24, US10-C5-B1, US10-C10-B1, US10-C5-TR22, US10-C10-TR22, US10-C5-T24, US10-C10-T24
US15-B10-B1, US15-C10-B1
This guide provides basic installation information for specific UniStream®
models with built-in I/O. Technical specifications may be downloaded from the
Unitronics website.
General Features
Unitronics’ UniStream® Built-in series are PLC+HMI All-in-One programmable controllers that comprise a built-in CPU, an HMI panel, and built-in I/Os.
The series is available in two versions: UniStream Built-in and UniStream Built-in Pro.
Note that a model number that includes:
· B5/C5 refers to UniStream Built-in
· B10/C10 refers to UniStream Built-in Pro. These models offer additional features, detailed below.
HMI
Resistive Color Touch-screens Rich graphic library for HMI design
Power Features
Built-in Trends and Gauges, auto-tuned PID, data tables, data sampling, and
Recipes UniAppsTM: Access & edit data, monitor, troubleshoot & debug and more
via HMI or remotely via
VNC
Security: Multi-level password protection Alarms: Built-in system, ANSI/ISA
standards
I/O Options
COM Options COM Protocols
Built-in I/O configuration, varies according to model Local I/O via UAG-CX
series I/O expansion adapters and standard UniStream Uni-I/OTM modules Remote
I/O using UniStream Remote I/O or via EX-RC1 US15 only Integrate I/O into
your system by using UAG-BACK-IOADP, snap onto the panel for an all-
in-one configuration.
Built-in ports: 1 Ethernet, 1 USB host, 1 Mini-B USB device port (USB-C in
US15) Serial and CANbus ports may be added via UAC-CX modules
Fieldbus: CANopen, CAN Layer2, MODBUS, EtherNetIP and more. Implement any
serial RS232/485, TCP/IP, or CANbus third-party protocols via Message Composer
Advanced: SNMP Agent/Trap, e-mail, SMS, modems, GPRS/GSM, VNC Client, FTP
Server/Client
Programming Software
All-in-One software for hardware configuration, communications, and HMI /PLC applications, available as a free download from Unitronics.
Comparison table
Feature System Memory Audio Jack Video/RSTP Support Web Server SQL Client
B5/C5 3GB No No No No
B10/C10 (Pro) 6GB Yes Yes Yes Yes
Unitronics
1
UniStream® Built-in
Before You Begin
Before installing the device, the user must: Read and understand this
document. Verify the Kit Contents.
Alert Symbols and General Restrictions
When any of the following symbols appear, read the associated information carefully.
Symbol
Meaning
Description
Danger
The identified danger causes physical and property damage.
Warning
The identified danger could cause physical and property damage.
Caution
Caution
Use caution.
All examples and diagrams are intended to aid understanding, and do not
guarantee operation. Unitronics accepts no responsibility for actual use of
this product based on these examples.
Please dispose of this product according to local and national standards and
regulations.
This product should be installed only by qualified personnel.
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
Failure to comply with appropriate safety guidelines can cause severe injury or property damage. Do not attempt to use this device with parameters that exceed permissible levels. Do not connect/disconnect the device when power is on.
Environmental Considerations
Ventilation: 10mm space is required between the device top/bottom edges and
the enclosure’s walls Do not install in areas with: excessive or conductive
dust, corrosive or flammable gas, moisture or rain, excessive heat,
regular impact shocks or excessive vibration, in accordance with the standards
and limitations given in the product’s technical specification sheet. Do not
place in water or let water leak onto the unit. Do not allow debris to fall
inside the unit during installation. Install at maximum distance from high-
voltage cables and power equipment.
UL Compliance
The following section is relevant to Unitronics’ products that are listed with
the UL. The following models are UL listed for Hazardous Locations: US5-B5-B1,
US5-B10-B1, US7-B5-B1 and US7-B10-B1
The following models are UL listed for Ordinary Location: USL followed by -,
followed by 050 or 070 or 101, followed by B05 US followed by 5 or 7 or 10,
followed by -, followed by B5 or B10 or C5 or C10, followed by -, followed by
B1 or TR22 or T24 or RA28 or TA30 or R38 or T42
Models from series US5, US7 and US10 that include “T10” or “T5″ in the model
name are suitable for mounting on the flat surface of Type 4X enclosure. For
examples: US7-T10-B1, US7-T5-R38, US5-T10-RA22 and US5-T5-T42.
UL Ordinary Location
In order to meet the UL ordinary location standard, panel-mount this device on
the flat surface of Type 1 or 4X enclosures
UL Ratings, Programmable Controllers for Use in Hazardous Locations, Class I,
Division 2, Groups A, B, C and D
These Release Notes relate to all Unitronics products that bear the UL symbols
used to mark products that have been approved for use in hazardous locations,
Class I, Division 2, Groups A, B, C and D.
Caution
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and
D, or Nonhazardous locations only.
Input and output wiring must be in accordance with Class I, Division 2 wiring
methods and in accordance with the authority having jurisdiction.
WARNING–Explosion Hazard–substitution of components may impair suitability for
Class I, Division 2.
WARNING EXPLOSION HAZARD Do not connect or disconnect equipment unless
power has been switched off or the area is known to be non-hazardous.
WARNING Exposure to some chemicals may degrade the sealing properties of
material used in Relays.
2
Unitronics
UniStream® Built-in
This equipment must be installed using wiring methods as required for Class I,
Division 2 as per the NEC and/or CEC.
Panel-Mounting
For programmable controllers that can be mounted also on panel, in order to
meet the UL Haz Loc standard, panel-mount this device on the flat surface of
Type 1 or Type 4X enclosures.
Communication and Removable Memory Storage
When products comprise either USB communication port, SD card slot, or both,
neither the SD card slot nor the USB port are intended to be permanently
connected, while the USB port is intended for programming only.
Removing / Replacing the battery
When a product has been installed with a battery, do not remove or replace the
battery unless the power has been switched off, or the area is known to be
non-hazardous.
Please note that it is recommended to back up all data retained in RAM, in
order to avoid losing data when changing the battery while the power is
switched off. Date and time information will also need to be reset after the
procedure.
UL des zones ordinaires:
Pour respecter la norme UL des zones ordinaires, monter l’appareil sur une
surface plane de type de protection 1 ou 4X
Certification UL des automates programmables, pour une utilisation en
environnement à risques, Class I, Division 2, Groups A, B, C et D.
Cette note fait référence à tous les produits Unitronics portant le symbole UL
– produits qui ont été certifiés pour une utilisation dans des endroits
dangereux, Classe I, Division 2, Groupes A, B, C et D.
Attention
Cet équipement est adapté pour une utilisation en Classe I, Division 2,
Groupes A, B, C et D, ou dans Non-dangereux endroits seulement.
Le câblage des entrées/sorties doit être en accord avec les méthodes
de câblage selon la Classe I, Division 2 et en accord avec l’autorité
compétente. AVERTISSEMENT: Risque d’Explosion Le remplacement de certains
composants rend
caduque la certification du produit selon la Classe I, Division 2.
AVERTISSEMENT – DANGER D’EXPLOSION – Ne connecter pas ou ne débranche pas
l’équipement sans avoir préalablement coupé l’alimentation électrique ou la
zone est reconnue pour être non dangereuse. AVERTISSEMENT – L’exposition à
certains produits chimiques peut dégrader les propriétés des matériaux
utilisés pour l’étanchéité dans les relais. Cet équipement doit être installé
utilisant des méthodes de câblage suivant la norme Class I, Division 2 NEC et
/ou CEC.
Montage de l’écran:
Pour les automates programmables qui peuvent aussi être monté sur l’écran,
pour pouvoir être au standard UL, l’écran doit être monté dans un coffret avec
une surface plane de type 1 ou de type 4X.
Communication et de stockage amovible de mémoire (carte mémoire)
Produits comprend un port USB de communication, soit un port carte SD ou les
deux, ni le port SD, ni le port USB ne sont censés être utilisés en
permanence, tandis que l’USB est destiné à la programmation uniquement.
Retrait / Remplacement de la batterie
Lorsqu’un produit a été installé avec une batterie, retirez et remplacez la
batterie seulement si l’alimentation est éteinte ou si l’environnement n’est
pas dangereux.
Veuillez noter qu’il est recommandé de sauvegarder toutes les données
conservées dans la RAM, afin d’éviter de perdre des données lors du changement
de la batterie lorsque l’alimentation est coupée. Les informations sur la date
et l’heure devront également être réinitialisées après la procedure.
Kit Contents
1 PLC+HMI controller 4,8,10 mounting brackets (US5/US7, US10, US15) 1 panel
mounting seal 2 panel supports (US7/US10/US15 only)
1 power terminal block 2 I/O terminal blocks (provided only with models
comprising
built-in I/Os)
1 Battery
Unitronics
3
Product Diagram US5/7/10
UniStream® Built-in
US15
1
8 3 9 2 5 6
11 8 12
7 5
Front and Rear View
1
Screen Protection
2
Battery Cover
3
Power Supply Input
4
microSD Slot
5
USB Host port
6
Ethernet port
7
USB Device
8
I/O Expansion Jack
9
Audio Jack
10
Built-in I/O
11
Uni-COMTM CX Module
Jack
12
UAG-BACK-IOADP
Adapter Jack
A plastic sheet attached to the screen for protection. Remove it during
installation of the HMI Panel. The battery is supplied with the unit, but must
be installed by the user. Connection point for the controller power source.
Connect the Terminal Block supplied with the kit to the end of the power
cable. Supports standard microSD cards. Provides the interface for external
USB devices. Supports high-speed Ethernet communications. Use for application
download and direct PC-UniStream communication. Connection point for an I/O
Expansion Port. Ports are supplied as part of I/O Expansion Model Kits. Kits
are available by separate order. Note that UniStream® Built-in is compatible
only with adapters from the series UAG-CX. Pro models only. This 3.5mm Audio
jack enables you to connect external audio equipment. Model-dependent. Present
in models with built-in I/O configurations. Connection point for up to 3
stack-on modules. These are available by separate order.
Connection point for snap onto the panel for an all-in-one configuration.
Adapter is available by Separate order.
Installation Space Considerations Allocate space for: the controller any
modules that will be installed access to ports, jacks, and the microSD card
slot For exact dimensions, please refer to the Mechanical Dimensions shown
below.
4
Unitronics
UniStream® Built-in
Mechanical Dimensions
UniStream 5″
UniStream 7″
Unitronics
5
UniStream 10.1″
UniStream® Built-in
UniStream 15.6″
6
Unitronics
UniStream® Built-in
NOTE
Allow space for modules to be snapped onto the back of the controller, if required by your application. Modules are available by separate order.
Panel Mounting
NOTE
Mounting panel thickness must be less or equal to 5mm (0.2″). Ensure that the space considerations are met.
1. Prepare a panel cut-out according to the dimensions as shown in the
previous section. 2. Slide the controller into the cut-out, ensuring that the
Panel Mounting Seal is in place as shown below. 3. Push the mounting brackets
into their slots on the sides of the panel as shown below. 4. Tighten the
bracket screws against the panel. Hold the brackets securely against the unit
while tightening the
screws. The torque required is 0.35 N·m (3.1 in-lb). When properly mounted,
the panel is squarely situated in the panel cut-out as shown below.
Caution
Do not apply torque exceeding 0.35 N·m (3.1 in-lb) of torque to tighten the
bracket screws. Using excessive force to tighten the screw can damage this
product.
UniStream 5″
UniStream 7″
UniStream 10.1″
Unitronics
7
UniStream 15.6”
UniStream® Built-in
Battery: Back-up, First Use, Installation, and Replacement
Back-up In order to preserve back-up values for RTC and system data in the
event of power off, the battery must be connected.
First Use The battery is protected by a removable cover on the side of the
controller. The battery is supplied installed inside the unit, with a plastic
tab preventing contact which must be removed by the user.
Battery Installation and Replacement Use proper precautions to prevent Electro-Static Discharge (ESD) while servicing the battery.
Caution
To preserve back-up values for RTC and system data during battery replacement, the controller must be powered. Note that disconnecting the battery halts the preservation of back-up values and causes them to be deleted.
1. Remove the battery cover from the controller as shown in the accompanying
figure: – Press the tab on the module to disengage it. – Slide it up to remove
it.
2. If you are replacing the battery, remove the battery from its slot on the
side of the controller.
3. Insert the battery, ensuring that the polarity is aligned with the
polarity marking as shown in the accompanying figure.
4. Replace the battery cover.
5. Dispose of the used battery according to local and national standards and regulations.
8
Unitronics
UniStream® Built-in
Wiring
This equipment is designed to operate only at SELV/PELV/Class 2/Limited Power
environments. All power supplies in the system must include double insulation.
Power supply outputs must be rated as
SELV/PELV/Class 2/Limited Power. Do not connect either the Neutral’ or
Line’
signal of the 110/220VAC to device’s 0V point. Do not touch live wires. All
wiring activities should be performed while power is OFF. Use over-current
protection, such as a fuse or circuit breaker, to avoid excessive currents
into the power supply
connection point. Unused points should not be connected (unless otherwise
specified). Ignoring this directive may damage the device. Double-check all
wiring before turning on the power supply.
Caution
To avoid damaging the wire, use a maximum torque of 0.5 N·m (4.4 in-lb). Do not use tin, solder, or any substance on stripped wire that might cause the wire strand to break. Wire and cable should have a temperature rating of minimum 75°C. Install at maximum distance from high-voltage cables and power equipment.
Wiring Procedure Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm2 3.31 mm2 ) 1. Strip the wire to a length of 7±0.5mm (0.2500.300 inches). 2. Unscrew the terminal to its widest position before inserting a wire. 3. Insert the wire completely into the terminal to ensure a proper connection. 4. Tighten enough to keep the wire from pulling free.
Wiring Guidelines
In order to ensure that the device will operate properly and to avoid
electromagnetic interference: Use a metal cabinet. Make sure the cabinet and
its doors are properly earthed. Use wires that are properly sized for the
load. Use shielded twisted pair cables for wiring High Speed and Analog I/O
signals.
In either case, do not use the cable shield as a signal common / return path.
Route each I/O signal with its own dedicated common wire. Connect common wires
at their respective common (CM) points
at the controller. Individually connect each 0V point and each common (CM)
point in the system to the power supply 0V terminal, unless
otherwise specified. Individually connect each functional ground point ( ) to
the earth of the system (preferably to the metal cabinet chassis).
Use the shortest and thickest wires possible: less than 1m (3.3′) in length,
minimum thickness 14 AWG (2 mm2). Connect the power supply 0V to the earth of
the system.
Unitronics
9
UniStream® Built-in
Earthing the cables’ shield: Connect the cable shield to the earth of the system (preferably to the metal cabinet chassis). Note that the shield must be connected only at one end of the cable; it is recommended to earth the shield at the PLC-side. Keep shield connections as short as possible. Ensure shield continuity when extending shielded cables.
NOTE
For detailed information, refer to the document System Wiring Guidelines, located in the Technical Library in the Unitronics’ website.
Wiring the Power Supply The controller requires an external power supply.
In the event of voltage fluctuations or non-conformity to voltage power supply
specifications, connect the device to a regulated power supply.
Connect the +V and 0V terminals as shown in the accompanying figure.
Connecting Ports Ethernet USB Device USB Host
CAT-5e shielded cable with RJ45 connector Standard USB cable with Mini-B USB plug (USC-C plug in US15) Standard USB device with Type-A plug
Connecting Audio Audio-Out
Use 3.5mm stereo audio plug with shielded audio cable Note that only Pro models support this feature.
Audio Pinout
1
Headphone Left Out (Tip)
2
Headphone Right Out (Ring)
3
Ground (Ring)
4
Don’t connect (Sleeve)
Note that below, the letters “xx” that is used in the model numbers means that the section refers both to B5/C5 and B10/C10 models.
US5-xx-TR22, US5-xx-T24
US5-xx-TR22, US7-xx-TR22, US10-xx-TR22
US7-xx-TR22, US7-xx-T24
US10-xx-TR22, US10-xx-T24
I/O Connection Points
The IOs for these models are arranged in two groups of fifteen points each, as
shown in the figures to the right.
Top group Input connection points
US5-xx-T24, US7-xx-T24, US10-xx-T24
Bottom group Output connection points
The function of certain I/Os may be adapted via wiring and software settings.
Wiring the Digital Inputs
All 10 digital inputs share the common point CM0. The digital inputs may be
wired together as sink or source.
Input wiring, sink
Input wiring, source
NOTE
Use sink input wiring to connect a sourcing (pnp) device. Use source input wiring to connect a sinking (npn) device.
10
Unitronics
UniStream® Built-in
Wiring the Analog Inputs Both inputs share the common point CM1.
NOTE
The inputs are not isolated.
Each input offers two modes: voltage or current. You can set each input
independently.
The mode is determined by the hardware configuration within the software
application.
Note that if, for example, you wire the input to current, you must also set it
to current in the software application.
Differential
Voltage
Single-ended
2-wire
Current
3-wire
4-wire
Unitronics
11
UniStream® Built-in
Wiring the Relay Outputs (US5-xx-TR22, US7-xx-TR22, US10-xx-TR22) To avoid
risk of fire or property damage, always use a limited current source or
connect a current limiting device in series with the relay contacts
The relay outputs are arranged in two isolated groups: O0-O3 share the common
return CM2. O4-O7 share the common return CM3.
Increasing Contact Life Span To increase the life span of the relay contacts
and protect the controller from potential damage by reverse EMF, connect: a
clamping diode in parallel with each inductive DC load, a RC snubber circuit
in parallel with each inductive AC load
Wiring the Sink Transistor Outputs (US5-xx-TR22, US7-xx-TR22, US10-xx-TR22)
Connect a current limiting device in series with outputs O8 and O9. These
outputs are not short-circuit protected.
Outputs O8 and O9 can independently be configured as either normal digital
outputs or as high speed PWM outputs.
Outputs O8 and O9 share the common point CM4.
Normal Transistor Output
High Speed PWM Output
12
Unitronics
UniStream® Built-in
Wiring the Source Transistor Outputs (US5-xx-T24, US7-xx-T24, US10-xx-T24)
Output’s power supply The use of any of the outputs requires an external 24VDC
power supply as shown in the accompanying figure. Outputs Connect the +VO and
0VO terminals as shown in the accompanying figure. O0-O11 share common return
0VO.
Installing Uni-I/OTM & Uni-COMTM Modules Refer to the Installation Guides
provided with these modules.
Turn off system power before connecting or disconnecting any modules or
devices. Use proper precautions to prevent Electro-Static Discharge (ESD).
Uninstalling the Controller 1. Disconnect the power supply. 2. Remove all
wiring and disconnect any installed devices according to the device’s
installation guide. 3. Unscrew and remove the mounting brackets, taking care
to support the device to prevent it from falling during this procedure.
The information in this document reflects products at the date of printing.
Unitronics reserves the right, subject to all applicable laws, at any time, at
its sole discretion, and without notice, to discontinue or change the
features, designs, materials and other specifications of its products, and to
either permanently or temporarily withdraw any of the forgoing from the
market.
All information in this document is provided “as is” without warranty of any
kind, either expressed or implied, including but not limited to any implied
warranties of merchantability, fitness for a particular purpose, or
noninfringement. Unitronics assumes no responsibility for errors or omissions
in the information presented in this document. In no event shall Unitronics be
liable for any special, incidental, indirect or consequential damages of any
kind, or any damages whatsoever arising out of or in connection with the use
or performance of this information.
The tradenames, trademarks, logos and service marks presented in this
document, including their design, are the property of Unitronics (1989) (R”G)
Ltd. or other third parties and you are not permitted to use them without the
prior written consent of Unitronics or such third party as may own them
Unitronics
13
UniStream® Built-in
UniStream® Built-in
Technical Specifications
US5-B5-B1, US5-B10-B1, US5-B5-TR22, US5-B10-TR22, US5-B5-T24, US5-B10-T24,
US5-C5-B1, US5-C10-B1, US5-C5-TR22, US5-C10-TR22, US5-C5-T24, US5-C10-T24
US7-B5-B1, US7-B10-B1, US7-B5-TR22, US7-B10-TR22, US7-B5-T24, US7-B10-T24,
US7-C5-B1, US7-C10-B1, US7-C5-TR22, US7-C10-TR22, US7-C5-T24, US7-C10-T24
US10-B5-B1, US10-B10-B1, US10-B5-TR22, US10-B10-TR22, US10-B5-T24,
US10-B10-T24, US10-C5-B1, US10-C10-B1, US10-C5-TR22, US10-C10-TR22,
US10-C5-T24, US10-C10-T24
US15-B10-B1, US15-C10-B1
Unitronics’ UniStream® Built-in series are PLC+HMI All-in-One programmable controllers that comprise built-in HMI and built-in I/Os. UniStream connects directly to UniCloud, Unitronics’ IIoT cloud platform using built-in UniCloud connectivity. More information about UniCloud is available at www.unitronics.cloud.
Model numbers in this document
US 5 – B 5 – B1 15
B1 TR22 T24
· No built-in I/Os
· 10 x Digital inputs, 24VDC, sink/source · 2 x Analog inputs, 0÷10V / 0÷20mA,
12 bits · 2 x Transistor outputs, npn,
including 2 High speed PWM output channels · 8 x Relay outputs
· 10 x Digital inputs, 24VDC, sink/source · 2 x Analog inputs, 0÷10V / 0÷20mA,
12 bits · 12 x Transistor outputs, pnp,
including 2 PWM output channels
5
Standard
10
Pro, offers additional features, detailed below
B
With UniCloud enabled functionality
C
With built-in 5 years UniCloud start-up subscription with no
additional payment required for this period.
5
5″ 800×480 (WVGA) display
7
7″ 800×480 (WVGA) display
10
10.1″ 1024×600 (WSVGA) display
15.6″ 1366 x 768 (HD) display
Installation Guides are available in the Unitronics Technical Library at www.unitronicsplc.com.
14
Unitronics
UniStream® Built-in
Power Supply
Input voltage
Permissible range
Max.
US5
current
consumption
US7
US10
US15
Isolation
USx-xx-B1 12VDC or 24VDC 10.2VDC to 28.8VDC 0.7A@12VDC 0.4A@24VDC
0.79A@12VDC 0.49A@24VDC
0.85A@12VDC 0.52A@24VDC
2.2A@12VDC 1.1A@24VDC
None
USx-xx-TR22 24VDC 20.4VDC to 28.8VDC 0.44A@24VDC
0.53A@24VDC
0.56A@24VDC
None
USx-xx-T24 24VDC 20.4VDC to 28.8VDC 0.4A@24VDC
0.49A@24VDC
0.52A@24VDC
None
Display LCD type
Backlight type
UniStream 5″ TFT
White LED
UniStream 7″
Luminous intensity (brightness)
Backlight longevity
(1)
Typically 350 nits (cd/m2), at 25°C
30k hours
Resolution (pixels) 800 x 480 (WVGA)
Typically 400 nits (cd/m2), at 25°C
Size
5″
7″
Viewing area
Width x Height (mm) 108 Width x Height (mm)
x 64.8
154.08 x 85.92
Color support
65,536 (16bit)
Surface treatment Touch screen
Actuation force (min)
Anti-glare Resistive Analog > 80 g (0.176 lb)
UniStream 10.1″
Typically 300 nits (cd/m2), at 25°C
1024 x 600 (WSVGA) 10.1″ Width x Height (mm) 222.72 x 125.28
UniStream 15.6″
Typically 400 nits (cd/m2), at 25°C
1366 x 768 (HD) 15.6″ Width x Height (mm) 344.23 x 193.53
General I/O support
Built-in I/O Local I/O expansion
Remote I/O Communication ports Built-in COM ports Add-on Ports
Internal memory
Ladder memory
Unitronics
Up to 2,048 I/O points
According to model
To add local I/Os, use UAG-CX I/O Expansion Adapters (2). These adapters
provide the connection point for standard UniStream Uni-I/OTM modules. You can
connect up to 80 I/O modules to a single controller using these adapters. US15
only Integrate I/O into your system by using UAG-BACK-IOADP adapter, snap
onto the panel for an all-in-one configuration.
Up to 8 UniStream Remote I/O Adapters (URB)
Specifications are provided below in the section Communications Add up to 3 ports to a single controller using Uni-COMTM UAC-CX Modules (3).
Standard (B5/C5) RAM: 512MB ROM: 3GB system memory
1GB user memory 1 MB
Pro (B10/C10) RAM: 1GB ROM: 6GB system memory
2GB user memory
15
External memory
Bit operation Battery
microSD or microSDHC card Size: up to 32GB, Data Speed: up to 200Mbps
0.13 µs Model: 3V CR2032 Lithium battery (4) Battery lifetime: 4 years
typical, at 25°C Battery Low detection and indication (via the HMI and via
System Tag).
Audio (Pro B10/C10 models only)
Bit Rate Audio compatibility Interface
Impedance Isolation
192kbps Stereo MP3 files 3.5mm Audio-out jack – use shielded audio cable of up to 3 m (9.84 ft) 16, 32 None
Video (Pro B10/C10 models only)
Supported Formats
MPEG-4 Visual , AVC/H.264
UniStream® Built-in
Communication (Built-in Ports) US5, US7, US10
US15
Ethernet port Number of ports Port type Auto crossover Auto negotiation Isolation voltage Cable USB device Port type Data rate Isolation Cable USB host Over current protection
1
2
10/100 Base-T (RJ45)
Yes
Yes
500VAC for 1 minute
Shielded CAT5e cable, up to 100 m (328 ft)
Mini-B USB 2.0 (480Mbps) None USB 2.0 compliant; < 3 m (9.84 ft)
USB-C
Yes
Digital Inputs (T24,TR22 models)
Number of inputs Type Isolation voltage Input to bus Input to input Nominal
voltage Input voltage Sink/Source
Nominal impedance Filter
10 Sink or Source
500VAC for 1 minute None 24VDC @ 6mA
On state: 15-30VDC, 4mA min. Off state: 0-5VDC, 1mA max. 4k 6ms typical
Analog Inputs (T24,TR22 models)
Number of inputs Input range (6) (7)
2 Input Type
0 ÷ 10VDC
16
Nominal Values 0 Vin 10VDC
Over-range Values *
10 < Vin 10.15VDC
Unitronics
UniStream® Built-in
Absolute maximum rating Isolation Conversion method Resolution Accuracy (25°C
/ -20°C to 55°C) Input impedance Noise rejection Step response (9) (0 to 100%
of final value)
0 ÷ 20mA
0 in 20mA
20 < in 20.3mA
- Overflow (8) is declared when an input value exceeds the Over-range boundary.
±30V (Voltage), ±30mA (Current)
None
Successive approximation
12 bits
±0.3% / ±0.9% of full scale
541k (Voltage), 248 (Current) 10Hz, 50Hz, 60Hz, 400Hz
Smoothing
Noise Rejection Frequency
None Weak Medium Strong
400Hz 2.7ms 10.2ms 20.2ms 40.2ms
60Hz 16.86ms 66.86ms 133.53ms 266.86ms
50Hz 20.2ms 80.2ms 160.2ms 320.2ms
10Hz 100.2ms 400.2ms 800.2ms 1600.2ms
Update time (9)
Operational signal range (signal + common mode) Cable Diagnostics (8)
Noise Rejection Frequency
Update Time
400Hz
5ms
60Hz
4.17ms
50Hz
5ms
10Hz
10ms
Voltage mode AIx: -1V ÷ 10.5V ; CM1: -1V ÷ 0.5V
Current mode AIx: -1V ÷ 5.5V ; CM1: -1V ÷ 0.5V (x=0 or 1)
Shielded twisted pair
Analog input overflow
Relay Outputs (USx-xx-TR22)
Number of outputs Output type Isolation groups
8 (O0 to O7) Relay, SPST-NO (Form A) Two groups of 4 outputs each
Isolation voltage Group to bus Group to group Output to output within group
Current
Voltage Minimum load Switching time Short-circuit protection
Life expectancy (10)
1,500VAC for 1 minute 1,500VAC for 1 minute None
2A maximum per output (Resistive load) 250VAC / 30VDC maximum 1mA, 5VDC 10ms
maximum None
100k operations at maximum load
Unitronics
17
Sink Transistor Outputs (USx-xx-TR22)
Number of outputs Output type Isolation Output to bus Output to output Current
Voltage
On state voltage drop Off state leakage current Switching times
High speed outputs
PWM Frequency
Cable
2 (O8 and O9) Transistor, Sink
1,500VAC for 1 minute None 50mA max. per output Nominal: 24VDC Range: 3.5V to
28.8VDC 1V max 10µA max
Turn-on: 1.6s max. )4k load, 24V) Turn-off: 13.4s max. )4k load, 24V)
0.3Hz min.
30kHz max. )4k load(
Shielded twisted pair
Source Transistor Outputs (USx-xx-T24)
Number of outputs Output type Isolation voltage Output to bus Output to output
Outputs power supply to bus Outputs power supply to output Current Voltage ON
state voltage drop OFF state leakage current Switching times
PWM Frequency (11)
Short-circuit protection
12 Transistor, Source (pnp)
500VAC for 1 minute None 500VAC for 1 minute
None
0.5A maximum per output See Source Transistor Outputs Power Supply
specification below 0.5V maximum 10µA maximum
Turn-on: 80s maximum, Turn-off: 155s maximum
(Load resistance < 4k(
O0, O1: 3kHz max. (Load resistance < 4k) Yes
Source Transistor Outputs Power Supply (USx-xx-T24)
Nominal operating voltage
Operating voltage
Maximum current consumption
24VDC
20.4 28.8VDC 30mA@24VDC Current consumption does not include load current
UniStream® Built-in
18
Unitronics
UniStream® Built-in
Environmental Protection
Operating temperature
Storage temperature
Relative Humidity (RH) Operating Altitude Shock Vibration
US5, US7, US10
Front face: IP66, NEMA 4X Rear side: IP20, NEMA1 -20°C to 55°C (-4°F to 131°F)
US15 0°C to 50°C (32°F to 122°F)
-30°C to 70°C (-22°F to 158°F)
-20°C to 60°C (-4°F to 140°F)
5% to 95% (non-condensing) 2,000 m (6,562 ft) IEC 60068-2-27, 15G, 11ms duration IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude, 8.4Hz to 150Hz, 1G acceleration
Dimensions
US5-xx-B1 US5-xx-TR22 US5-xx-T24 US7-xx-B1 US7-xx-TR22 US7-xx-T24 US10-xx-B1
US10-xx-TR22 US10-xx-T24 US15-xx-B1
Weight 0.31 Kg (0.68 lb) 0.37 Kg (0.81 lb) 0.35 Kg (0.77 lb) 0.62 Kg (1.36 lb) 0.68 Kg (1.5 lb) 0.68 Kg (1.5 lb) 1.02 Kg (2.25 lb) 1.08 Kg (2.38 lb) 1.08 Kg (2.38 lb) 2.68Kg (5.9 lb)
Size Refer to the images on page 7 Refer to the images on page 8 Refer to the images on page 8 Refer to the images on page 9
Unitronics
19
UniStream 5″
UniStream® Built-in
UniStream 7″
UniStream 10.1″
20
Unitronics
UniStream® Built-in
UniStream 15.6″
Unitronics
21
UniStream® Built-in
Notes:
1. The HMI panel’s backlight longevity is the typical operating time after which the brightness drops to 50% of its original level.
2. UAG-CX Expansion Adapter Kits comprise a Base unit, an End unit, and a
connecting cable. You plug the Base Unit into the
controller’s I/O Expansion Jack and connect standard UniStream Uni-I/OTM
modules. For more information, refer to the product’s installation guide and
technical specifications.
3. Uni-COMTM CX modules plug directly into the Uni-COMTM CX Module Jack on the back of the controller. UAC-CX modules may be installed in the following configurations: – If a module comprising a serial port is snapped directly into to the back of UniStream, it may be followed only by another serial module, for a total of 2. – If your configuration includes a CANbus module, it must be snapped directly to the back of UniStream. The CANbus module may be followed by up to two serial modules, for a total of 3. For more information, refer to the product’s installation guide and technical specifications.
4. When replacing the unit’s battery, make sure that the new one has environmental specifications that are similar or better than the one specified in this document.
5. The USB device port is used to connect the device to a PC.
6. The 4-20mA input option is implemented using 0-20mA input range.
7. The analog inputs measure values that are slightly higher than the nominal input range (Input Over-range).
Note that when the input overflow occurs, it is indicated in the corresponding I/O Status tag while the input value is registered as the maximum permissible value. For example, if the specified input range is 0 ÷ 10V, the Over-range values can reach up to 10.15V, and any input voltage higher than that will still register as 10.15V while the Overflow system tag is turned on.
8. The diagnostics results are indicated in the system tags and can be observed through the UniAppsTM or the online state of the UniLogicTM.
9. Step response and update time are independent of the number of channels that are used.
10. Life expectancy of the relay contacts depends on the application that they are used in. The product’s installation guide provides procedures for using the contacts with long cables or with inductive loads.
11. Outputs O0 and O1 can be configured as either normal digital outputs or as PWM outputs. apply only when outputs are configured as PWM outputs.
PWM outputs specifications
The information in this document reflects products at the date of printing.
Unitronics reserves the right, subject to all applicable laws, at any time, at
its sole discretion, and without notice, to discontinue or change the
features, designs, materials and other specifications of its products, and to
either permanently or temporarily withdraw any of the forgoing from the
market.
All information in this document is provided “as is” without warranty of any
kind, either expressed or implied, including but not limited to any implied
warranties of merchantability, fitness for a particular purpose, or
noninfringement. Unitronics assumes no responsibility for errors or omissions
in the information presented in this document. In no event shall Unitronics be
liable for any special, incidental, indirect or consequential damages of any
kind, or any damages whatsoever arising out of or in connection with the use
or performance of this information.
The tradenames, trademarks, logos and service marks presented in this
document, including their design, are the property of Unitronics (1989) (R”G)
Ltd. or other third parties and you are not permitted to use them without the
prior written consent of Unitronics or such third party as may own them.