UNITRONICS USP-070-B08 UniStream HMI Panel Platform Comprises Control Device User Guide
- June 9, 2024
- UNITRONICS
Table of Contents
- UNITRONICS USP-070-B08 UniStream HMI Panel Platform Comprises Control
- User Guide
- Before You Begin
- Environmental Considerations
- UL Compliance
- Kit Contents
- HMI Panel Diagram
- Installation Space Considerations
- HMI Panel Mechanical Dimensions
- Panel Mounting
- Panel Support Installation
- Wiring Procedure
- Wiring Guidelines
- Wiring the Power Supply
- HMI Panel Interface Connections
- Installing CPU-for-Panel, Uni-I/O™ & Uni-COM™ Modules
- Removing the Panel
- Technical Specifications
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
UNITRONICS USP-070-B08 UniStream HMI Panel Platform Comprises Control
Device
HMI Panel
User Guide
USP-070-B08, USP-070-C08, USP-070-B10, USP-070-C10,
USP-104-B10, USP-104-C10, USP-104-M10,
USP-156-B10, USP-156-C10
Unitronics’ UniStream® platform comprises control devices that provide robust,
flexible solutions for industrial automation.
This guide provides basic installation information for the UniStream® HMI
Panel.
Technical specifications may be downloaded from the Unitronics website.
The UniStream® platform comprises CPU controllers, HMI panels, and local I/O
modules that snap together to form an all-in-one Programmable Logic Controller
(PLC). Expand the I/O configuration using a Local Expansion Kit or remotely
via CANbus.
CPU-for-Panel
CPUs are Programmable Logic Controllers (PLCs), the heart of the UniStream®
platform.
The CPU-for-Panel cannot operate independently. It must be plugged into the
back of a UniStream® HMI panel. The panel provides the CPU’s power source. The
CPU-for-Panel comprises:
- IO/COM Bus connector for interfacing Uni-I/O™ & Uni-COM™ modules
- Isolated RS485 and CANbus ports
- Backup battery
HMI Panels
A high-resolution touch screen provides the operator interface for the
system and the physical foundation for a PLC+HMI+I/Os all-in-one controller.
Available in different dimensions
The DIN-rail structure on the panel’s back is designed to physically support a
CPU-for-Panel controller, Uni-I/O™ and/or Uni-COM™ modules.
Each panel comprises:
- AUX connector to support the CPU
- 1 audio-out 3.5mm jack
- 1 microSD slot
- 2 type A, USB host ports and 1 Mini-B USB device port
- 2 Ethernet ports, RJ45, 10/100 Mbps
- 1 power input connector, 12/24 VDC
I/O Options
Integrate I/Os into your system by using:
- On-board I/Os: snap onto the panel for an all-in-one configuration
- Local I/O via a Local Expansion Kit
- Remote I/O via EX-RC1
Programming Software
All-in-one UniLogic™ software, for hardware configuration, communications, and
HMI/PLC applications, available as a free download from Unitronics web site.
Before You Begin
Before installing the device, the installer must:
- Read and understand this document.
- Verify the Kit Contents.
Note that the CPU-for-Panel is intended to be installed on the back of an HMI panel in accordance to a separate installation guide supplied with the CPU- for-Panel.
Alert Symbols and General Restrictions
When any of the following symbols appear, read the associated information
carefully.
- All examples and diagrams are intended to aid understanding, and do not guarantee operation. Unitronics accepts no responsibility for actual use of this product based on these examples.
- Please dispose of this product according to local and national standards and regulations.
- This product should be installed only by qualified personnel.
- Failure to comply with appropriate safety guidelines can cause severe injury or property damage.
- Do not attempt to use this device with parameters that exceed permissible levels.
- Do not connect/disconnect the device when power is on.
Environmental Considerations
- Ventilation: 10mm (0.4”) of space is required between the device top/bottom edges and the enclosure’s walls.
- Do not install in areas with: excessive or conductive dust, corrosive or flammable gas, moisture or rain, excessive heat, regular impact shocks or excessive vibration, in accordance with the standards and limitations given in the product’s technical specification sheet.
- Do not place in water or let water leak onto the unit.
- Do not allow debris to fall inside the unit during installation.
- Install at maximum distance from high-voltage cables and power equipment.
Caution
- The UniStream® HMI Panel is designed to comply with NEMA 4X, IP66 and IP65. Note however that the Audio Protection Seal must remain plugged in for NEMA 4X and IP66, in which case the audio sound level from the internal speaker is significantly reduced.
UL Compliance
The following section is relevant to Unitronics’ products that are listed with
the UL.
The following models: USP-070-B08, USP-070-C08, USP-104-B10, USP-104-C10,
USP-104-M10, USP-156-B10, USP-156-C10 are UL listed for Hazardous Locations.
The following models: USP-070-B08, USP-070-C08, USP-070-B10, USP-070-C10,
USP-104-B10, USP-104-C10, USP-104-M10, USP-156-B10, USP-156-C10 are UL listed
for Ordinary Location.
UL Ordinary Location
- In order to meet the UL ordinary location standard, panel-mount this device on the flat surface of Type 1 or 4 X enclosures
UL Ratings, Programmable Controllers for Use in Hazardous Locations, Class
I, Division 2, Groups A, B, C and D
These Release Notes relate to all Unitronics products that bear the UL symbols
used to mark products that have been approved for use in hazardous locations,
Class I, Division 2, Groups A, B, C and D.
Caution
- This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non-hazardous locations only.
- Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in accordance with the authority having jurisdiction.
- WARNING—Explosion Hazard—substitution of components may impair suitability for Class I, Division 2.
- WARNING – EXPLOSION HAZARD – Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
- WARNING – Exposure to some chemicals may degrade the sealing properties of material used in Relays.This equipment must be installed using wiring methods as required for Class I, Division 2 as per the NEC and/or CEC.
Panel-Mounting
For programmable controllers that can be mounted also on panel, in order to
meet the UL Haz Loc standard, panel-mount this device on the flat surface of
Type 1 or Type 4X enclosures.
Communication and Removable Memory Storage
When products comprise either USB communication port, SD card slot, or
both, neither the SD card slot nor the USB port are intended to be permanently
connected, while the USB port is intended for programming only.
Removing / Replacing the battery
When a product has been installed with a battery, do not remove or replace
the battery unless the power has been switched off, or the area is known to be
non-hazardous.
Please note that it is recommended to back up all data retained in RAM, in
order to avoid losing data when changing the battery while the power is
switched off. Date and time information will also need to be reset after the
procedure.
Kit Contents
- 1 HMI Panel: 7”, 10.4” or 15.6”
- 7” panel, includes 4 mounting brackets
- 10.4” panel, includes 8 mounting brackets and 2 panel supports
- 15.6” panel, includes 10 mounting brackets and 2 panel supports
- 1 panel mounting seal
- 1 power terminal block
HMI Panel Diagram
Installation Space Considerations
Allocate space for:
- The HMI Panel including the CPU and any modules that will be installed on it
- Opening the doors of the CPU and modules
For exact dimensions, please refer to the Mechanical Dimensions shown below.
HMI Panel Mechanical Dimensions
Panel Mounting
NOTE
- Mounting panel thickness must be less or equal to 5mm (0.2”).
- Ensure that the space considerations are met.
- Prepare a panel cut-out according to the dimensions of your model as shown in the previous section.
- Slide the panel into the cut-out, ensuring that the Panel Mounting Seal is in place as shown on the right.
- Push the mounting brackets into their slots on the sides of the panel as shown below.
- Tighten the bracket screws against the panel. Hold the brackets securely against the unit while tightening the screws. The torque required is 0.35 N·m (3.1 in-lb).
When properly mounted, the panel is squarely situated in the panel cut-out as shown below.
Caution
- Do not apply torque exceeding 0.35 N·m (3.1 in-lb) of torque to tighten the bracket screws. Using excessive force to tighten the screw can damage this product.
Panel Support Installation
-
Insert the Panel Support tabs into their location.
Note that the exact location varies according to the panel model. -
Pull on the Panel Support until it locks (clicks) into it’s place.
Wiring
- This equipment is designed to operate only at SELV/PELV/Class 2/Limited Power environments.
- All power supplies in the system must include double insulation. Power supply outputs must be rated as SELV/PELV/Class 2/Limited Power.
- Do not connect either the ‘Neutral’ or ‘Line’ signal of the 110/220VAC to device’s 0V point.
- Do not touch live wires.
- All wiring activities should be performed while power is OFF.
- Use over-current protection, such as a fuse or circuit breaker, to avoid excessive currents into the HMI Panel supply port.
- Unused points should not be connected (unless otherwise specified). Ignoring this directive may damage the device.
- Double-check all wiring before turning on the power supply.
Caution
- To avoid damaging the wire, use a maximum torque of 0.5 N·m (4.4 in-lb).
- Do not use tin, solder, or any substance on stripped wire that might cause the wire strand to break.
- Install at maximum distance from high-voltage cables and power equipment.
Wiring Procedure
Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm2 –3.31 mm2).
- Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).
- Unscrew the terminal to its widest position before inserting a wire.
- Insert the wire completely into the terminal to ensure a proper connection.
- Tighten enough to keep the wire from pulling free.
Wiring Guidelines
In order to ensure that the device will operate properly and to avoid electromagnetic interference:
-
Use a metal cabinet. Make sure the cabinet and its doors are properly earthed.
-
Use wires that are properly sized for the load.
-
Individually connect each 0V point in the system to the power supply 0V terminal.
-
Individually connect each functional ground point ( ) to the earth of the system (preferably to the metal cabinet chassis).
Use the shortest and thickest wires possible: less than 1m (3.3’) in length, minimum thickness 14 AWG (2 mm2). -
Connect the power supply 0V to the earth of the system.
NOTE
For detailed information, refer to the document System Wiring Guidelines,
located in the Technical Library in the Unitronics’ website.
Wiring the Power Supply
The UniStream® HMI Panel device requires an external 12/24VDC power supply.
In the event of voltage fluctuations or non-conformity to voltage power supply
specifications, connect the device to a regulated power supply.v Connect the
+V and 0V terminals as shown in the accompanying figure.
HMI Panel Interface Connections
Use the following:
-
Ethernet
CAT-5e shielded cable with RJ45 connector -
USB Device
Use a standard USB cable, Type mini-B -
USB Host
Standard USB cable with Type-A plug -
microSD
Standard microSD -
Audio Out
3.5mm stereo audio plug with shielded audio cable
Installing CPU-for-Panel, Uni-I/O™ & Uni-COM™ Modules
Refer to the Installation Guides provided with these modules.
- Turn off system power before connecting or disconnecting any modules or devices.
- Use proper precautions to prevent Electro-Static Discharge (ESD).
Removing the Panel
- Disconnect the power supply.
- Remove all wiring and disconnect any installed devices according to the device’s installation guide.
- Unscrew and remove the mounting brackets, taking care to support the panel to prevent it from falling during this procedure.
Technical Specifications
Power Supply| USP-070-x08| USP-070-x10| USP-104-x10|
USP-104-x10| USP-156-x10
Input voltage| 12VDC or 24VDC
Permissible range| 10.2VDC to 28.8VDC
Max. current consumption| 1.35A@12VDC,
0.65A@24VDC
| 1.5A@12VDC,
0.75A@24VDC
| 1.62A@12VDC,
0.81A@24VDC
| 2.5A@12VDC,
1.25A@24VDC
Display| USP-070-x08| USP-070-x10| USP-104-x10|
USP-104-M10| USP-156-x10
---|---|---|---|---|---
LCD type| TFT
Backlight type| White LED
Luminous intensity (brightness)| Typically 400 nits (cd/m2), at 25°C
Backlight longevity (1)| 30k hours| 50k hours
Resolution (pixels)| 800 x 480 (WVGA)| 800 x 480 (WVGA)| 800 x 600 (SVGA)|
1366 x 768
Size| 7”| 7”| 10.4”| 15.6”
Viewing area
Width x Height (mm)
| 154.08 x 85.92| 152.4 x 91.44| 211.2 x 158.4| 344.23 x 193.53
Color support| 65,536 (16bit)| 16M (24bit)
Surface treatment| Anti-glare
Touch screen| Resistive Analog| Capacitive multi-touch, 5-fingers| Resistive
Analog
Actuation force (min)| > 80 g (0.176 lb)
System
Processor| 32 bit, 800MHz RISC Processor, with Graphic Accelerator
Internal memory| RAM: 512 MB
ROM: 3GB system memory 1GB user memory
External memory| microSD or microSDHC card
Size: up to 32GB, Data Speed: up to 200Mbps
Bit Rate | 192kbps |
---|---|
Internal speaker | Audio compatibility: mono MP3 files. Frequency range: 500Hz |
to 20KHz
External audio| Audio compatibility: stereo MP3 files.
Interface: 3.5mm Audio-out jack – use shielded audio cable of up to 3 m (9.84 ft).
Impedance: 32Ω
No isolation
Video
Support Formats| MPEG-4 Visual , AVC/H.264
Communication
Ethernet port|
Number of ports| 2
Port type| RJ45, 10BASE-T/100BASE-TX
Auto crossover| Yes
Auto negotiation| Yes
Isolation voltage| 500VAC for 1 minute
Cable| Shielded CAT5e cable, up to 100 m (328 ft)
USB device (3)|
Number of ports| 1
Port type| Mini-B
Data rate| USB 2.0 (480Mbps)
Isolation| None
Cable| USB 2.0 compliant; < 3 m (9.84 ft)
USB host|
Number of ports| 2
Port type| Type A
Data rate| USB 2.0 (480Mbps)
Isolation| None
Cable| USB 2.0 compliant; < 3 m (9.84 ft)
Over current protection| Yes
On-board I/O or COM modules (4)|
USP-070-x08, USP-070-x10
| USP-104-x10, USP-104-M10 USP-156-x10
---|---|---
Number of modules| Up to 3| Up to 5
(up to 4 of them can be COM modules)
Note that the numbers above relate to Uni-I/O and Uni-COM modules. You can mix Uni-I/O and Uni-COM modules with Uni-I/O Wide modules, considering that 1 Uni-I/O Wide module equals 1½ Uni-I/O module. For example, the USP-104-x10 and USP-104-M10 back panel can host 2 Uni-I/O and 2 Uni-I/O Wide modules in any order.
Environmental|
---|---
Protection| Front face (2) : IP65/IP66, NEMA 4X Rear side: IP20, NEMA1
| USP-070-x08, USP-070-x10, USP-104-x10, USP-104-M10| USP-156-x10
Operating temperature| -20°C to 55°C (-4°F to 131°F)| 0°C to 50°C (32°F to
122°F)
Storage temperature| -30°C to 70°C (-22°F to 158°F)| -20°C to 60°C (-4°F to
140°F)
Relative Humidity (RH)| 5% to 95% (non-condensing)
Operating Altitude| 2,000 m (6,562 ft)
Shock| IEC 60068-2-27, 15G, 11ms duration
Vibration| IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude, 8.4Hz to
150Hz, 1G acceleration
Dimensions| USP-070-x08| USP-070-x10| USP-104-x10|
USP-104-M10| USP-156-x10
---|---|---|---|---|---
Weight| 0.7 Kg (1.54 lb)| 0.7 Kg (1.54 lb)| 1.45 Kg (3.20 lb)| 1.45 Kg (3.20
lb)| 3 Kg (3.60 lb)
Size| Refer to the images below
USP-104-x10, USP-104-M10 10.4” Panel USP-156-x10 15.6” Panel
Notes:
- Panel’s longevity is the typical operating time after which the brightness drops to 50% of its original level.
- The audio outlet seal must be inserted in the outlet in order to comply with IP66 or NEMA 4X.
- The USB device port is used to connect the device to a PC.
- The panel back is molded into a DIN rail-like structure which provides the physical support for a UniStream® CPU-for-Panel, Uni-I/O™ modules and Uni-Com™ modules. Details are provided in the UniStream® UG_USP-070-104-156 installation guides.
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market. All information in this document is provided “as is” without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information. The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R”G) Ltd. or other third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.