UNITRONICS V120 Rugged Programmable Logic Controllers User Guide
- June 9, 2024
- UNITRONICS
Table of Contents
UNITRONICS V120 Rugged Programmable Logic Controllers
General Description
The products listed above are micro-PLC+HMIs and rugged programmable logic controllers that comprise built-in operating panels. Detailed Installation Guides containing the I/O wiring diagrams for these models, technical specifications, and additional documentation are located in the Technical Library in the Unitronics website: https://unitronicsplc.com/support- technical-library/.
Alert Symbols and General Restrictions
Alert Symbols and General Restrictions
When any of the following symbols appear, read the associated information
carefully.
Symbol| | Meaning| Description
| | Danger| The identified danger causes physical and property damage.
| | Warning| The identified danger could cause physical and property damage.
Caution| Caution| Use caution.
Before using this product, the user must read and understand this document.
All examples and diagrams are intended to aid understanding and do not guarantee operation. Unitronics accepts no responsibility for the actual use of this product based on these examples.
Please dispose of this product according to local and national standards and regulations.
Only qualified service personnel should open this device or carry out repairs.
| Failure to comply with appropriate safety guidelines can cause severe
injury or property damage.
| Do not attempt to use this device with parameters that exceed permissible
levels.
To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
- Do not install in areas with: excessive or conductive dust, corrosive or flammable gas, moisture or rain, excessive heat, regular impact shocks or excessive vibration, in accordance with the standards given in the product’s technical specification sheet.
- Do not place in water or let water leak onto the unit.
- Do not allow debris to fall inside the unit during installation.
- Ventilation: 10mm space required between the controller’s top/bottom edges & enclosure walls.
- Install at maximum distance from high-voltage cables and power equipment.
Mounting
Note that figures are for illustrative purposes only.
Dimensions
Model
- V120
- M91
Cut-out
- 92×92 mm (3.622”x3.622”)
- 92×92 mm (3.622”x3.622”)
View area
- 57.5×30.5mm (2.26″x1.2″)
- 62×15.7mm (2.44″x0.61″)
Panel Mounting
Before you begin, note that the mounting panel cannot be more than 5 mm
thick.
- Make a panel cut-out of the appropriate size:
- Slide the controller into the cut-out, ensuring that the rubber seal is in place.
- Push the mounting brackets into their slots on the sides of the panel as shown in the figure below.
- Tighten the bracket’s screws against the panel. Hold the bracket securely against the unit while tightening the screw.
- When properly mounted, the controller is squarely situated in the panel cut-out as shown in the accompanying figures.
DIN-rail Mounting
- Snap the controller onto the DIN rail as shown in the figure to the right.
- When properly mounted, the controller is squarely situated on the DIN rail as shown in the figure to the right.
Wiring
- Do not touch live wires.
- This equipment is designed to operate only in SELV/PELV/Class 2/Limited Power environments.
- All power supplies in the system must include double insulation. Power supply outputs must be rated as SELV/PELV/Class 2/Limited Power.
- Do not connect either the ‘Neutral or ‘Line’ signal of the 110/220VAC to the device’s 0V pin.
- All wiring activities should be performed while power is OFF.
- Use over-current protection, such as a fuse or circuit breaker, to avoid excessive currents into the power supply connection point.
- Unused points should not be connected (unless otherwise specified). Ignoring this directive may damage the device.
- Double-check all wiring before turning on the power supply.
- To avoid damaging the wire, do not exceed a maximum torque of:
- Controllers offering a terminal block with a pitch of 5mm: 0.5 N·m (5 kgf·cm).
- Controllers offering a terminal block with a pitch of 3.81mm f 0.2 N·m (2 kgf·cm).
Caution
- Do not use tin, solder, or any substance on the stripped wire that might cause the wire strand to break.
- Install at maximum distance from high-voltage cables and power equipment.
Wiring Procedure
Use crimp terminals for wiring;
- Controllers offering a terminal block with a pitch of 5mm: 26-12 AWG wire (0.13 mm2 –3.31 mm2).
- Controllers offering a terminal block with a pitch of 3.81mm: 26-16 AWG wire (0.13 mm2 – 1.31 mm2).
- Strip the wire to a length of 7±0.5mm (0.270–0.300“).
- Unscrew the terminal to its widest position before inserting a wire.
- Insert the wire completely into the terminal to ensure a proper connection.
- Tighten enough to keep the wire from pulling free.
Wiring Guidelines
- Use separate wiring ducts for each of the following groups:
- Group 1: Low voltage I/O and supply lines, communication lines.
- Group 2: High voltage Lines, Low voltage noisy lines like motor driver outputs. Separate these groups by at least 10cm (4″). If this is not possible, cross the ducts at a 90˚angle.
- For proper system operation, all 0V points in the system should be connected to the system 0V supply rail.
- Product-specific documentation must be fully read and understood before performing any wiring.
Allow for voltage drop and noise interference with input lines used over an extended distance. Use wire that is properly sized for the load.
Earthing the product
To maximize system performance, avoid electromagnetic interference as follows:
- Use a metal cabinet.
- Connect the 0V and functional ground points (if exist) directly to the earth ground of the system.
- Use the shortest, less than 1m (3.3 ft.) and thickest, 2.08mm² (14AWG) min, wires possible.
UL Compliance
The following section is relevant to Unitronics’ products that are listed
with the UL.
The following models:
V120-22-T1, V120-22-T2C, V120-22-UA2, V120-22-UN2, M91-2-R1, M91-2-R2C,
M91-2-R6, M91-2-R6C, M91-2-T1, M91-2-T2C, M91-2-UA2, M91-2-UN2 are UL listed
for Hazardous Locations.
The following models:
V120-22-R1, V120-22-R2C, V120-22-R34, V120-22-R6, V120-22-R6C, V120-22-RA22,
V120-22-T1, V120-22-T2C, V120-22-T38, V120-22-UA2, V120-22-UN2, M91-2-FL1,
M91-2-PZ1, M91-2-R1, M91-2-R2, M91-2-R2C, M91-2-R34, M91-2-R6, M91-2-R6C,
M91-2-RA22, M91-2-T1, M91-2-T2C, M91-2-T38, M91-2-TC2, M91-2-UA2, M91-2-UN2,
M91-2-ZK, M91-T4-FL1, M91-T4-PZ1, M91-T4-R1, M91-T4-R2, M91-T4-R2C,
M91-T4-R34, M91-T4-R6, M91-T4-R6C, M91-T4-RA22, M91-T4-T1, M91-T4-T2C,
M91-T4-T38, M91-T4-TC2, M91-T4-UA2, M91-T4-UN2, M91-T4-ZK are UL listed for
Ordinary Location.
For models from series M91, that include “T4” in the Model name, Suitable for mounting on the flat surface of Type 4X enclosure. For examples: M91-T4-R6
UL Ordinary Location
In order to meet the UL ordinary location standard, panel-mount this device on
the flat surface of Type 1 or 4 X enclosures.
UL Ratings, Programmable Controllers for Use in Hazardous Locations, Class
I, Division 2, Groups A, B, C and D
These Release Notes relate to all Unitronics products that bear the UL
symbols used to mark products that have been approved for use in hazardous
locations, Class I, Division 2, Groups A, B, C and D.
Caution
- This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non-hazardous locations only.
- Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in accordance with the authority having jurisdiction.
- WARNING—Explosion Hazard—substitution of components may impair suitability for Class I, Division 2.
- WARNING – EXPLOSION HAZARD – Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
- WARNING – Exposure to some chemicals may degrade the sealing properties of material used in Relays.
- This equipment must be installed using wiring methods as required for Class I, Division 2 as per the NEC and/or CEC.
Panel-Mounting
For programmable controllers that can be mounted also on panel, in order to
meet the UL Haz Loc standard, panel-mount this device on the flat surface of
Type 1 or Type 4X enclosures.
Relay Output Resistance Ratings
The products listed below contain relay outputs:
Programmable controllers, Models: M91-2-R1, M91-2-R2C,M91-2-R6C, M91-2-R6
- When these specific products are used in hazardous locations, they are rated at 3A res.
- when these specific products are used in non-hazardous environmental conditions, they are rated at 5A res, as given in the product’s specifications.
Temperature Ranges
Programmable Logic Controllers, Models, M91-2-R1, M91-2-R2C, M91-2-R6C.
- When these specific products are used in hazardous locations, they may be used only within a temperature range of 0-40ºC (32- 104ºF).
- When these specific products are used in non-hazardous environmental conditions, they function within the range of 0-50ºC (32- 122ºF) given in the product’s specifications.
Removing / Replacing the battery
When a product has been installed with a battery, do not remove or replace the
battery unless the power has been switched off, or the area is known to be
non-hazardous. Please note that it is recommended to back up all data retained
in RAM, in order to avoid losing data when changing the battery while the
power is switched off. Date and time information will also need to be reset
after the procedure.
24VDC, 12 pnp/npn digital inputs, 2 universal inputs*, high-speed counter/shaft encoder input, 10 transistor outputs, 2 analog outputs, 1/0 expansion port, 2 RS232/RS485 ports.
Notes:
- All 12 inputs can be set to 10 pnp (source) or npn (sink) via a single jumper and appropriate wiring.
- npn (sink) inputs use voltage supplied from the controller’s power supply.
- Input #0 can function as either a high-speed counter or as part of a shaft encoder. In each case, high-speed input specifications apply, When used as an n0<mal digital input, normal input specifications apply.
- Input #1 can function as either counter reset, or as a normal digital input; in either case, specifications are those of a normal digital input. This input may also be used as part of a shaft encoder. In this case, high-speed input specifications apply.
Power supply, pnp (source) inputs
Note:
To avoid electromagnetic interference, mount the controller in a metal
paneVcabinet and earth the power supply. Earth the power supply signal to the
metal using a wire whose length does not exceed 10cm. If your conditions do
not permit this, do not earth the power supply.
npn (sink) inputs
pnp (source) high-speed counter
npn (sink) high-speed counter
Shaft encoder
Universal Inputs
Voltage / Current connection
Notes:
- Shields should be connected at the signals’ source.
- The OV signal of the analog input must be connected to the controller’s OV.
Current connection
Notes:
- Shields should be connected at the signals’ source.
- The av signal of the analog input must be connected to the controller’s OV.
Notes:
- Thermocouple #0: use Input #10 as positive input & Input #9 as negative input. Thermocouple #1: use Input #8 as positive input & Input #7 as negative input. To use inputs as thermocouples, set the relevant jumpers and use appropriate wiring.
Input Ranges
Thermocouple connection
Note:
Shields should be connected at the signals’ source.
Note:
Output #0 and Output #1 may be used as high-speed outputs.
Digital Outputs connection
Note:
Each analog output range is defined by wiring, jumpers and within the
controller’s software.
Analog outputs connection
Notes:
- Shields should be earthed, and connected to the earth of the cabinet.
- The OV signal of the analog outputs must be the same OV used by the controller’s power supply.
Note:
- RS232/RS485 is determined by jumper settings and wiring.
- Refer to the controller’s User Guide regarding communication.
24 VDC, 12 pnp/npn digital inputs, *2 universal inputs, high-speed counter/shaft encoder input, 10 transistor outputs, 2 analog outputs, I/O expansion port, R$232/RS485 port.
Notes:
- All 12 inputs can be set to pnp (source) or npn (sink) via a single jumper and appropriate wiring.
- npn (sink) inputs use voltage supplied from the controller’s power supply.
- 1nput #0 can function as either high-speed counter 0( as part of a shaft encoder. In each case, high-speed input specifications apply. When used as a normal digital input, normal input specifications apply.
- Input #1 can function as either counter reset, or as a normal digital input; in either case. specifications are those of normal digital input. This input may also be used as part of a shaft encoder. 1n this case, high. speed input specifications apply.
- Certain inputs can function as normal digital inputs, analog inputs or thermocouple inputs, in accordance with jumper settings and wiring connections.
Warnings
- Unused pins should not be connected. Ignoring this directive may damage the controller.
- Improper use of this product may severely damage the controller.
- Refer to the controller’s User Guide regarding wiring considerations.
- Before using this product, it is the responsibility of the user to read the product’s User Guide and all accompanying documentation.
Power supply, pnp (source) inputs
Note:
To avoid electromagnetic interference, mount the controller in a metal panel
cabinet and earth the power supply. Earth the power supply signal to the metal
using a wire whose length does not exceed 10cm If your conditions do not
permit this, do not earth the power supply.
npn (sink) Inputs
pnp (source) high-speed counter
npn (sink) high-speed counter
Shaft encoder
Shaft encoder
Universal Inputs
Voltage/Current connection
Notes:
- Shields should be connected at the signals’ source.
- The av signal of the analog Input must be connected to the controller’s OV.
Notes:
Thermocouple #0: use lnput#10 as positive input & Input #9 as negative input.
Thermocouple #1: use lnput#8 as positive input & Input #7 as negative input.
To use inputs as thermocouples, set the relevant jumpers and use appropriate
wiring.
Thermocouple connection
Note:
Shields should be connected to the signals’ source.
Digital outputs connection
Note:
Each analog output range is defined by wiring, jumpers, and within the
controller’s software.
Analog outputs connection
Notes:
- Shields should be earthed, and connected to the earth of the cabinet.
- The OV signal of the analog outputs must be the same OV used by the controller’s power supply.
Note:
RS232/RS485 fS determined by jumper settings and wiring as described in the
document · M91 RS485 Port Settings packaged with the
controller.
Jumpers Settings
The tables below show how to set a specific jumper to change the functionality of a specific input or analog output. To open the controller and access the jumpers, refer to the directions at the end of these specifications.
Important:
Incompatible jumper settings and wiring connections may severely damage the
controller.
JP2, JP3, JP6, JPS
lnput#9 and lnput#10 (universal input no. 0)
Notes:
- Thermocouple input is between lnpul#10 (T+) and lnpu1#9 (T-).
- When using lnput#10 as an analog input, lnput#9 can be used as a normal digital input.
- Analog inputs are related to signal OV.
JP4, JPS, JP7, JP9
lnput#7 and lnput#S (universal input no. 1)
Notes:
- Thermocouple input is between lnput#8 (T+} and lnput#7 (T-).
- When using lnput#8 as an analog input, lnput#7 can be used as a normal digital input.
- Analog inputs are related to signal OV.
JP10
Input type (for all digital Inputs)
Note:
Inputs# 0-6, input #11 and #7-10 when these are set as normal digital inputs.
In this figure, the jumper settings will cause the inputs and the analog outputs to function as follows:
- Universal Input #0 (Input #10): Voltage input, related to OV
- Universal Input #1 (Input #7 and Input #8): Thermocouple input
- lnput#9: Normal npn, 24VDC digital input
- lnput#0 to Input #6 and input # 11: npn, 24VDC digital inputs.
(Note that these inputs can only function as normal digital inputs.)
- Analog output #0: Voltage output
- Analog output #1: Current output
Note:
Jumper #1 is reserved – do not use it.
Communication Ports
Note that different controller models offer different serial and CANbus communication options. To see which options are relevant, check your controller’s technical specifications.
-
Turn off the power before making communications connections.
Caution -
Note that the serial ports are not isolated.
-
Signals are related to the controller’s 0V; the same 0V is used by the power supply.
-
Always use the appropriate port adapters.
Serial Communications
This series comprises 2 serial ports that can be set to either RS232 or RS485 according to jumper settings. By default, the ports are set to RS232. Use RS232 to download programs from a PC, and to communicate with serial devices and applications, such as SCADA. Use RS485 to create a multi-drop network containing up to 32 devices.
Caution
The serial ports are not isolated. If the controller is used with a
nonisolated external device, avoid potential voltage that exceeds ± 10V.
Pinouts
The pinouts below show the signals between the adapter and
port.
Standard programming cables do not provide connection points for pins 1 and 6.
RS232 to RS485: Changing Jumper Settings
-
To access the jumpers, open the controller and then remove the module’s PCB board. Before
you begin, turn off the power supply, and disconnect and dismount the controller. -
When a port is adapted to RS485, Pin 1 (DTR) is used for signal A, and Pin 6 (DSR) signal is\ used for signal B.
-
If a port is set to RS485, and flow signals DTR and DSR are not used, the port can also be used to communicate via RS232; with the appropriate cables and wiring.
-
Before performing these actions, touch a grounded object to discharge any electrostatic charge.
-
Avoid touching the PCB board directly. Hold the PCB board by its connectors.
Opening The Controller
- Turn the power off before opening the controller.
- Locate the 4 slots on the sides of the controller.
- Using the blade of a flat-bladed screwdriver, gently pry off the back of the controller.
- Gently remove the top PCB board:
- Use one hand to hold the topmost PCB board by its top and bottom connectors.
- On the other hand, grasp the controller, while keeping hold of the serial ports; this will keep the bottom board from being removed together with the top board.
- Steadily pull the top board off.
- Locate the jumpers, and then change the jumper settings as required.
- Gently replace the PCB board. Make certain that the pins fit correctly into their matching receptacle.
- Do not force the board into place; doing so may damage the controller.
- Close the controller by snapping the plastic cover back in its place. If the card is placed correctly, the cover will snap on easily.
M91: RS232/RS485 Jumper Settings
RS232/RS485 Jumper Setting
To use as| Jumper 1| Jumper 2
**RS232*| A| A
RS485| B| B
RS485 Termination**
Termination| Jumper 3| Jumper 4
**ON*| A| A
OFF**| B| B
Default factory setting.
V120: RS232/RS485 Jumper Settings
Jumper Settings | |
---|---|
Jumper | **RS232*** |
COM 1 | 1 |
2 | A |
COM 2 | 5 |
6 | A |
RS485 Termination
Jumper| **ON*| OFF**
3| A| B
4| A| B
7| A| B
8| A| B
Default factory setting.
CANbus
These controllers comprise a CANbus port. Use this to create a decentralized
control network of up to 63 controllers, using either Unitronics’ proprietary
CANbus protocol or CANopen.
The CANbus port is galvanically isolated.
CANbus Wiring
- Use twisted-pair cable. DeviceNet® thick
- shielded twisted pair cable is recommended.
- Network terminators: These are supplied with the controller. Place terminators at each end of the CANbus network.
- Resistance must be set to 1%, 1210, 1/4W.
- Connect the ground signal to the earth at only one point, near the power supply.
- The network power supply need not be at the end of the network
CANbus Connector
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.
All information in this document is provided “as is” without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non- infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos, and service marks presented in this document, including their design, are the property of Unitronics (1989) (R”G) Ltd. or other third parties and you are not permitted to use them without the prior written consent of Unitronics or a such third party as may own them UG_V120_M91-UA2.pdf 11/22.
https://unitronicsplc.com/support-technical-library/.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>