VERIS CW2 Series Air Quality Sensor Installation Guide
- September 26, 2024
- VERIS
Table of Contents
CW2 Series Air Quality Sensor
“`html
Specifications
-
Operating Environment: IP Rating IP 30,
suitable for indoor use only, not suitable for wet locations -
Mounting Location: Surface mount on Single
Gang J-Box, British Standard, and CE60 wall boxes -
CO2 Transmitter:
-
Sensor Type: Non-dispersive infrared (NDIR),
diffusion sampling -
Output Range: 0 to 2000/5000 ppm
(selectable) -
Response Time:
-
0 to 5%: Target value (0 to 50)
-
5 to 10%: Average (50 to 100)
-
10 to 20%: Slightly increased (100 to 200)
-
20 to 61%: Significantly increased (200 to 610)
-
Greater than 61%: Greatly increased (greater than 610)
-
-
RH Transmitter Option:
-
HS Sensor: Solid state capacitive,
replaceable -
Hysteresis: 1.5% typical
-
-
Temperature Transmitter Option:
- Sensor Type: Solid state, integrated
circuit
- Sensor Type: Solid state, integrated
-
Display Models:
-
Touchscreen: 61 mm (2.4 in), color, backlit,
capacitive, 240×300 px -
LCD: 52mm (2.05 in), segmented with 3
buttons
-
-
Setpoints:
-
Humidity Setpoint: 0 to 10V output, scale: 0
to 100% RH -
Fan Speed Setpoint: 0 to 10V output (Off 0V,
Auto 1.5V, Low 3.3V, Med. 6.7V, High 10.0V)
-
Product Usage Instructions
Installation
1. Ensure the device is mounted in an indoor location with IP
Rating IP30.
2. Mount the device on a Single Gang J-Box, British Standard, or
CE60 wall box.
Connecting Sensors
1. Connect the appropriate sensors based on the model type (CO2,
VOC, RH, temperature).
User Interface Options
1. Select the desired user interface option: touchscreen
(CW2Txxxx), LCD with three buttons (CW2Lxxxx), or blank
(CW2Xxxxx).
Setting Setpoints
1. Adjust the setpoints for humidity and fan speed as needed
using the specified output range.
Frequently Asked Questions (FAQ)
Q: Can I use the CW2 Series sensors in wet locations?
A: No, the CW2 Series sensors are suitable for indoor use only
and not recommended for wet locations due to their IP Rating of
IP30.
“`
Installation Guide Air Quality
CW2 Analog Series
CW2Txxxx
CW2Lxxxx
CW2Xxxxx
Veris Industries Stratford Park 5 Telford TF3 3BL United Kingdom
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
· Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E or CSA Z462. ·This equipment must only
be installed and serviced by qualified electrical personnel. · Turn off all
power supplying this equipment before working on or inside equipment. · Always
use a properly rated voltage sensing device to confirm power is off. · Replace
all devices, doors and covers before turning on power to this equipment.
Failure to follow these instructions can result in death, serious injury or
equipment damage.
This product is intended for use in HVAC and building environmental control
applications. It is not intended for direct medical monitoring of patients.
Read and understand these instructions before installing this product. The
installer is responsible for all applicable codes. If this product is used in
a manner not specified by the manufacturer, the protection provided by the
product may be impaired. No responsibility is assumed by the manufacturer for
any consequences arising out of the use of this material.
Wall Mount Air Quality Sensors
Product Overview
The CW2 Series of air quality sensors for living space is a flexible multi-
sensor platform for use with BAS controllers designed to accept 4 to 20mA, 0
to 5Vdc or 0 to 10Vdc outputs. CW2 Series sensors are available with three
user interface options: touchscreen, LCD with three buttons and blank. CO2 and
temperature sensors are included with all CW2 Series air quality sensors.
Models with VOC sensors and relative humidity sensors are also available.
Product Identification
User Interface CW2
Output
RH Accuracy¹ Temperature
VOC Sensor
T = Color touchscreen A = Analog output 2 = 2%
L = 3-button LCD display
X = None 2
X = None 2
A = Transmitter
V = NDIR CO2/VOC
C = 1000 PT RTD
= None
D = 10K T2 thermistor
G = 10K CPC thermistor 3
H = 10K T3 thermistor
K = 10K curve G/11K shunt
M = 20K NTC thermistor
N = 1.8K TAC thermistor
1. Replaceable RH module available to be ordered separately per table below. 2. For analog non-display, non-RH, models with RTD/thermistor order from CWE2 line. 3. Available in CW2LAXG only. 4. VOC only availble with temperature transmitter option.
Replaceable RH Elements
Model HS1N HS2N HS2X
RH Accuracy ±1% ±2% ±2%
Calibration Certificate X X
Description Replaceable RH sensor, 1% with NIST certification Replaceable RH sensor, 2% with NIST certification Replaceable RH sensor, 2%
Specifications
OPERATING ENVIRONMENT
Input Power Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz Analog Output
Selectable 4 to 20 mA, 0 to 5 V, 0 to 10 V Operating Temp. Range 0 to 50 °C
(32 to 122 °F) Operating Humidity Range 0 to 95% RH non-condensing Housing
Material High-impact ABS plastic Terminal Block Torque 0.5 to 0.6 N-m (0.37 to
0.44 in-lbf)
IP Rating IP 30 Mounting Location For indoor use only. Not suitable for wet
locations.
Surface Mount The device can be surface mounted on Single Gang J-Box, British
Standard and CE60 wall boxes
Z207931-0K
Page 1 of 11
©2024 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
0424
CW2 Analog Series Installation Guide
Specifications (cont.)
CO2 TRANSMITTER
Sensor Type Non-dispersive infrared (NDIR), diffusion sampling
Output Range 0 to 2000/5000 ppm (selectable)
Accuracy ±30 ppm ±3% of measured value Repeatability ±20 ppm ±1% of measured value
Response Time <60 seconds for 90% step change
VOC TRANSMITTER OPTION
Sensor Type Solid state Output Range 0 to 100% AQI for VOC
Accuracy ±15% of measured value
Output Scale 0 to 1,000 ppb of total VOC (TVOC)
Level Ventilation Recommendation TVOC (ppb)
AQI Table* >61% Greatly increased 20 to 61% Significantly increased
610 200 to 610
10 to 20% Slightly increased
100 to 200
5 to 10% Average
50 to 100
0 to 5% Target value
0 to 50
RH TRANSMITTER OPTION
HS Sensor Solid state capacitive, replaceable
Accuracy ±3.8% RH from 10 to 60% RH @ 25°C (77 °F) (Includes Hysteresis)**
±4.8% RH from 60 to 80% RH @ 25°C (77 °F)
±5.8% RH from 80 to 100% RH @ 25°C (77 °F)
Hysteresis 1.5% typical
Stability ±1% @ 20°C (68 °F) annually for 2 years Output Range 0 to 100% RH
Temperature Coefficient ±0.1% RH/°C above or below 25 °C (77 °F) typical
TEMPERATURE TRANSMITTER OPTION
Sensor Type Solid state, integrated circuit
Accuracy ±0.2 °C (±0.4 °F) typical Resolution 0.1 °C (0.1 °F)
Range 0 to 50 °C (32 to 122 °F)
DISPLAY MODELS
Touchscreen
61 mm (2.4 in), color, backlit, capacitive, 240×300 px Setpoint: 0-10Vdc. Temperature, humidity or fan speed selectable Timeout override: Display timeout Lockout override: Touchscreen/button lockout
LCD 52mm (2.05 in), segmented with 3 buttons Setpoint: 0-10Vdc. Temperature, humidity or fan speed selectable Timeout override: Display timeout Lockout override: Touchscreen/button lockout
SETPOINTS****
Temperature Setpoint 0 to 10V output Scale: 10 to 35 °C (50 to 95 °F) / 0 to 50 °C (32 to 122 °F)
Humidity Setpoint 0 to 10V output Scale: 0 to 100% RH
Fan Speed Setpoint 0 to 10V output Off 0V, Auto 1.5V, Low 3.3V, Med. 6.7V, High 10.0V
Z207931-0K
Page 2 of 11
©2024 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
0424
CW2 Analog Series Installation Guide
Specifications (cont.)
OVERRIDE
Override Button Display models feature a momentary-to-ground override button
WIRING TERMINALS
Terminal Blocks Screw terminals, 18-24 AWG Screw Terminal Torque 0.2 N-m (2.0 in-lbF) max.
WARRANTY
Limited Warranty 5 years
COMPLIANCE INFORMATION
Agency Approvals
UL 916, European conformance CE: EN61000-6-2, EN61000-6-3, EN61000 Series – industrial immunity, EN 61326-1 FCC Part 15 Class B, REACH, RoHS, RCM (Australia), ICES-003 (Canada), UKCA (UK)
- Air Quality Index for VOC aligns with TVOC levels for IAQ as specified by the WHO (World Health Organization). ** Humidity sensor overall accuracy should include: accuracy, temperature coefficient and stability. Humidity accuracy is shown as an absolute value, so if testing accuracy with a hand-held device, you must check for deviation in its readings instead of calculating the percentual deviation. Additionally, you must consider the overall accuracy of the hand-held device in the comparison. * DIP switch selectable. ** One setpoint type is selectable via DIP switch on display models only.
Dimensions
115 (4.5)
2X .264 [6.7] 2X .142 [3.6]
3.28 83.32
2.374 60.3
Functions
85
24
(3.3)
(0.9)
The CW2 Series sensor measures CO2, VOC (if equipped), RH (if equipped) and temperature in a room and provides analog outputs to a controller.
Z207931-0K
Page 3 of 11
©2024 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
0424
CW2 Analog Series Installation Guide
Installation
1. Remove the cover from the base at the bottom of the device.
2. Position the sensor base vertically on the wall 1.35 m (4.5 ft.) above the
floor with the “UP” arrow facing upward. Locate away from windows, vents and
other sources of draft. If possible, do not mount on an external wall, as this
may cause inaccurate temperature readings.
3. Pull 18 or 22 AWG cable(s) through the hole in the backplate.
4. Mount the backplate onto the wall using the screws provided. Six screw
holes available. Use a minimum of two for secure mounting.
5. Connect the wires to the screw terminals. Do not over-tighten the screws.
Z207931-0K
Page 4 of 11
©2024 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
0424
CW2 Analog Series Installation Guide
Installation (cont.)
Wiring for models with temperature transmitter:.
CONTROL SYSTEM VOC OUT CO2 OUT OVERRIDE* SETPOINT OUT** RH OUT TEMP OUT COMMON
POWER SUPPLY 20-30 Vdc, 24 Vac – COMMON + POWER (+24)
10 9 8 7 6
5432 1
Wiring for models with RTD/thermistor:
CONTROL SYSTEM VOC OUT CO2 OUT OVERRIDE* SETPOINT OUT** RH OUT RTD/THERMISTOR
OUT RTD/THERMISTOR OUT COMMON
POWER SUPPLY 20-30 Vdc, 24 Vac – COMMON + POWER (+24)
10 9 8 7 6
5432 1
- Momentary to ground. ** 0-10V DIP switch selectable for temperature, RH (if equipped) or fan speed (off, 0V, Auto 1.5V, Low 3.3V, Medium 6.7V or high 10V).
Z207931-0K
Page 5 of 11
©2024 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
0424
CW2 Analog Series Installation Guide
Installation (cont.)
6. Set the DIP switches.
ON
12345678
Touch-Button Disable On/Off
Screen Timeout On/Off Temp Range 1 / 2 RH / Fan Setpoint Temp / RH-Fan
Setpoint
ABC On / Off
2000 / 5000ppm
5V / 10V
mA / Voltage
Switch
Function
1
Output mode
2
Voltage output range*
Description
ON – 4-20mA output mode enabled OFF – Voltage output mode enabled
ON – 0-5V output range enabled OFF 0-10V output range enabled
3
CO2 output range
ON – 0-2000 ppm CO2 output range enabled OFF – 0-5000 ppm CO2 output range enabled
4
Automatic Baseline Calibration (ABC) ON – ABC enabled
for CO2
OFF – ABC disabled
5
Setpoint output type
ON – Temperature setpoint enabled (temp range selected on DIP switch 6)
OFF – RH or Fan Speed setpoint enabled (specific setpoint output type to be
selected on DIP switch 6)
Models without RH option select only temp or fan setpoint
6
Setpoint output temperature range or Temperature setpoint (must be enabled on DIP switch 5)
RH/Fan Speed output type
ON – Temp range 1, 50 to 95 °F (10 to 35 °C) enabled
OFF – Temp range 2, 32 to 122 °F (0 to 50 °C) enabled
RH or Fan Speed setpoint (must be enabled on DIP switch 5) ON – RH setpoint enabled OFF – Fan Speed setpoint enabled Models without RH option, set to OFF
7
Display times out and turns off after ON – Display Timeout enabled
6-10 seconds of touchscreen/button OFF – Display Timeout disabled
press
8
Touchscreen touch functions and
buttons are disabled
ON – Touchscreen touch/button functions disabled OFF – Touchscreen touch/button functions enabled
- Only used with voltage output mode enabled. Not applicable to setpoint output. Setpoint is 0-10V fixed.
7. With sensor base fully installed, align top of cover to mounting tabs on top of sensor base. Swing cover downward until it latches at the bottom.
Z207931-0K
Page 6 of 11
©2024 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
0424
CW2 Analog Series Installation Guide
Installation (cont.)
8. Install locking screw to secure cover in closed position.
CO2 Sensor Calibration
There are two methods for CO2 calibration available: 400 ppm baseline
calibration and automatic baseline calibration (ABC).
400 ppm Baseline Calibration
400 ppm baseline calibration allows the sensor to be set at 400 ppm. Push and
hold the calibration button for 3 to 5 seconds. The LED will flash green. Once
the button is released, calibration is complete and the LED switches off.
Calibration button access hole LED
Automatic Baseline Calibration (ABC)
The ABC mode addresses the 400 ppm calibration. It allows turning on or off a
background correction/recovery mode that will minimize any calibration error
that has been caused by shock during handling and transportation or is caused
by a long term shift in measurement. The ABC algorithm constantly keeps track
of the sensor’s lowest reading over a preconfigured time interval and slowly
corrects for any long-term drift detected as compared to the expected fresh
air value of 400 ppm. After initial startup, it is expected that the sensor
reaches specified accuracy after 7 to 21 days.
Touchscreen Operation
Main Screen
The touchscreen user interface displays applicable sensor output values
(temperature, RH, CO2 and VOC), setpoint value, menu button and CO2 stoplight
status (if enabled).
Setpoint value (temperature setpoint shown)
Menu button
VOC AQI value Fahrenheit/Celsius Temperature value
RH value
CO2 value
Menu Screen
The menu screen opens when pressing the Menu button on the main screen.
Integrator’s submenu, occupancy/override, Fahrenheit/Celsius, settings,
setpoint submenu (temp, RH or fan, determined by DIP switch settings) and CO2
stoplight buttons are displayed on the menu screen.
Temperature setpoint DIP switch selected
RH setpoint DIP switch selected
Fan Speed setpoint DIP switch selected
Z207931-0K
Page 7 of 11
©2024 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
0424
CW2 Analog Series Installation Guide
Touchscreen Operation (cont.)
Menu Button Functions
Integrator’s Submenu Press this icon to access the Integrator’s menu.
Submenu Only
Menu Button Functions (cont.)
Occupied Override Button Press this icon to provide momentary ground output to
the controller
Fahrenheit/Celsius Switch Press this icon to display either °C or °F.
Single Press Only Signals occupied/override call to controller.
Single Press Only Changes units to Fahrenheit when pressed. Changes units to
Celsius when pressed.
Settings This icon provides the ability to change the color scheme of the display.
Submenu Only
Temp Setpoint Adjustment
Submenu Only
Click this icon to access the setpoint
change menu. Mutually exclusive
with fan speed, set by DIP switch.
Humidity Setpoint Adjustment Submenu Only Click this icon to access the setpoint change menu. Mutually exclusive with humidity and fan speed. Set by DIP switch.
Fan Speed Click this icon to access the fan speed menu. Mutually exclusive with humidity and fan speed. Set by DIP switch.
Submenu Only
A
Selected
Z207931-0K
Page 8 of 11
©2024 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
0424
CW2 Analog Series Installation Guide
Touchscreen Operation (cont.)
CO Stoplight Menu 2
Click this icon to toggle the CO2 Stoplight feature on and off. With CO
Stoplight turned on,
2
the background color of the main screen changes with CO2 level. This provides
a visual indicator of CO2 levels to the room occupants.
Using the +/- buttons, the thresholds at which the colors change on the main
screen are user configurable, as described in the diagram.
Submenu Only
Feature is ON Feature is OFF
Default1
Default2
Green3 CO2 <1000 ppm
Yellow & Single Flag4
Red & Double Flag4
CO2 = 1000-1499 ppm CO2 = 1500-10,000 ppm
1. Values <400 ppm will be rounded up to the minimum limit of 400 ppm. 2.
Values >10,000 ppm will be rounded down to the maximum limit of 10,000 ppm. 3.
Possible to adjust CO thresholds by changing the yellow and red limits. 4.
User configurable in increments of 10 ppm using the +/- buttons. With a long
press
of these buttons, the number will change more quickly.
LCD Display Operation Button Functions
Change Values Menu Advance Change Values
Display Icons
The main screen displays sensor values for CO2, VOC (if equipped), RH (if
equipped), temperature and Celsius/Fahrenheit.
Temperature Value
Humidity Value (if equipped)
CO2 Value VOC Value (if equipped) Alternates between CO2 and VOC every 6
seconds
Override Press Indicator
Z207931-0K
Page 9 of 11
©2024 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
0424
CW2 Analog Series Installation Guide
Setpoint Function
A single 0-10V setpoint (temperature, RH (if equipped) or fan speed) can be
selected via DIP switch.
Temperature Setpoint Adjustment
Press the Menu Advance button
Adjusts setpoint up Adjusts setpoint down
After adjustment, wait 6 seconds or press the Menu Advance button. Setpoint is accepted and main screen appears.
Note: Numeric information will flash while in Set mode.
RH Setpoint Adjustment
Press the Menu Advance button
Note: Numeric information will flash while in Set mode.
Adjusts setpoint up Adjusts setpoint down
After adjustment, wait 6 seconds or press the Menu Advance button. Setpoint is accepted and main screen appears.
Fan Speed Setpoint Adjustment
Press the Menu Advance button
Adjusts setpoint up
Adjusts setpoint down Note: Fan speed scale flashes when in Set mode. Off setting is default.
Low Medium High Auto
After adjustment, wait 6 seconds or press the Menu Advance button. Setpoint is accepted and the main screen appears.
Changing Celsius and Fahrenheit Scales
Press the Menu
Advance button 2
times
2x
Note: ºF or ºC text will flash while in Set mode.
Adjusts from ºF to ºC Adjusts from ºC to ºF
After adjustment, wait 6 seconds or press the Menu Advance button to return to the main screen.
Occupied/Override Button
Press and hold the Menu Advance button for 1 second
Override Press Indicator illuminates for 6 seconds, indicating a momentary output to ground.
Z207931-0K
Page 10 of 11 ©2024 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
0424
CW2 Analog Series Installation Guide
China RoHS Compliance Information
Environment-Friendly Use Period (EFUP) Table
– Hazardous Substances
Part Name (Pb) (Hg) (Cd) (Cr (VI)) (PBB) (PBDE)
Electronic
X
O
O
O
O
O
SJ/T11364 O: GB/T 26572 X: GB/T 26572
This table is made according to SJ/T 11364. O: indicates that the
concentration of hazardous substance in all of the homogeneous materials for
this part is below the limit as stipulated in GB/T 26572. X: indicates that
concentration of hazardous substance in at least one of the homogeneous
materials used for this part is above the limit as stipulated in GB/T 26572
Z000057-0B
Z207931-0K
Page 11 of 11 ©2024 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com