Veris HHX06 Adjustable Current Switch Installation Guide

July 25, 2024
VERIS

Current Monitoring
Current Switches: Adjustable Trip Point, N.C. Output

HHX06 Adjustable Current Switch

HX06 SERIES
Detect Belt Loss, Coupling Shear, and Mechanical Failure Hawkeye x06 Series solid- and split-core current switches provide accurate, reliable, and maintenance-free fan and pump status indication where an NC output is needed.

Adjustable trip point
Versatility with four available amperage ranges
No tubing needed
Easier to install than differential pressure switches
100% solid-state
No moving parts to fail
Status LEDs
Output status LEDs for fast set up
Easy placement
Adjustable mounting bracket on the solid-core housing
Self-gripping iris
Self-gripping iris on split-core housings for easy installation

APPLICATIONS

  • Monitoring fans, pumps, motors, and other electrical  loads for proper operation
  • Detecting belt loss and motor failure…ideal for fan and pump status
  • Verifying lighting circuit loads
  • Monitoring critical motors (compressor, fuel, etc.)
  • Monitoring industrial process equipment status (OEM)

SPECIFICATIONS

Sensor Power 5 to 30 Vdc
Insulation Class 600 Vac RMS (UL), 300 Vac RMS (CE)
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH non-condensing
Hysteresis 10% Typical
Off State Leakage 34 μA @ 5 Vdc, 200 µA @ 30 Vdc
On State Voltage Drop 1.9 Vdc max@ 0.1 A
Terminal Block Wire Size H300: 22 to 16 AWG (0.3 to 1.3 mm 2)

Others: 24 to 14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque| H300: 7 in-lbs (0.8 N-m)
Others: 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

WARRANTY

Limited Warranty 5 years

AGENCY APPROVALS

Agency Approvals| UL 508 open device listing; CE: EN61010-1, CAT III, Pollution Degree 2, basic insulation
---|---

DETECTS BELT LOSS/COUPLING SHEAR!DETECTS BELT LOSS/COUPLING SHEAR! Now you can easily detect when drive belts slip, break, or pump couplings shear.
In fact, a typical HVAC motor that loses its load has a reduction of current draw of up to 50%. That’s why our sensors are the industry standard for status.
Note: Do not use the LED status indicators as evidence of applied voltage. (a) VFD systems generate fields that can disrupt electrical devices. Ensure that these fields are minimized and are not affecting the sensor.

H606
Dimensional Drawing H806
Dimensional Drawing
H706
Dimensional Drawing * Terminal block may extend up to 1/8” over the height dimensions shown.
** Slide switch may extend up to 1/4” over the height dimensions shown.

MONITORING FAN/PUMP MOTORS FOR POSITIVE PROOF OF FLOW (H606 & H806)

Wiring Diagram MONITORING FAN/PUMP MOTORS FOR POSITIVE PROOF OF FLOW (H706)
Wiring Diagram

ORDERING INFORMATION

MODEL| AMPERAGE
RANGE| STATUS OUTPUT
(MAX.)| MIN. TRIP
POINT| HOUSING| STATUS LED| UL| CE
---|---|---|---|---|---|---|---
H606| 1.25 to 50 A| N.C. 0.1 A @ 30 Vdc| 1.25 A or less| Split-Core| •| •| •
I-1706| 1 to 135 A| 1.0 A or less| Solid-Core| •| •| •
I-1806| 0.75 to 50 A| 0.75 A or less| Solid-Core| •| •| •

1. Listed for use on 75°C insulated conductors.

HQ0001756.H 0324
800.354.8556
+1 503.598.4564
sales@veris.com
intl@veris.com
veris.com

Documents / Resources

| Veris HHX06 Adjustable Current Switch [pdf] Installation Guide
HHX06 Adjustable Current Switch, HHX06, Adjustable Current Switch, Current Switch, Switch
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals