Veris HHX06 Adjustable Current Switch Installation Guide
- July 25, 2024
- VERIS
Table of Contents
Current Monitoring
Current Switches: Adjustable Trip Point, N.C. Output
HHX06 Adjustable Current Switch
HX06 SERIES
Detect Belt Loss, Coupling Shear, and Mechanical Failure Hawkeye x06 Series
solid- and split-core current switches provide accurate, reliable, and
maintenance-free fan and pump status indication where an NC output is needed.
Adjustable trip point
Versatility with four available amperage ranges
No tubing needed
Easier to install than differential pressure switches
100% solid-state
No moving parts to fail
Status LEDs
Output status LEDs for fast set up
Easy placement
Adjustable mounting bracket on the solid-core housing
Self-gripping iris
Self-gripping iris on split-core housings for easy installation
APPLICATIONS
- Monitoring fans, pumps, motors, and other electrical loads for proper operation
- Detecting belt loss and motor failure…ideal for fan and pump status
- Verifying lighting circuit loads
- Monitoring critical motors (compressor, fuel, etc.)
- Monitoring industrial process equipment status (OEM)
SPECIFICATIONS
Sensor Power | 5 to 30 Vdc |
---|---|
Insulation Class | 600 Vac RMS (UL), 300 Vac RMS (CE) |
Temperature Range | -15 to 60 °C (5 to 140 °F) |
Humidity Range | 10 to 90% RH non-condensing |
Hysteresis | 10% Typical |
Off State Leakage | 34 μA @ 5 Vdc, 200 µA @ 30 Vdc |
On State Voltage Drop | 1.9 Vdc max@ 0.1 A |
Terminal Block Wire Size | H300: 22 to 16 AWG (0.3 to 1.3 mm 2) |
Others: 24 to 14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque| H300: 7 in-lbs (0.8 N-m)
Others: 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
WARRANTY
Limited Warranty | 5 years |
---|
AGENCY APPROVALS
Agency Approvals| UL 508 open device listing; CE: EN61010-1, CAT III,
Pollution Degree 2, basic insulation
---|---
DETECTS BELT LOSS/COUPLING SHEAR!DETECTS BELT LOSS/COUPLING SHEAR! Now
you can easily detect when drive belts slip, break, or pump couplings shear.
In fact, a typical HVAC motor that loses its load has a reduction of current
draw of up to 50%. That’s why our sensors are the industry standard for
status.
Note: Do not use the LED status indicators as evidence of applied
voltage. (a) VFD systems generate fields that can disrupt electrical devices.
Ensure that these fields are minimized and are not affecting the sensor.
H606
Dimensional Drawing H806
Dimensional Drawing
H706
Dimensional Drawing * Terminal block may extend up to 1/8” over the
height dimensions shown.
** Slide switch may extend up to 1/4” over the height dimensions shown.
MONITORING FAN/PUMP MOTORS FOR POSITIVE PROOF OF FLOW (H606 & H806)
Wiring Diagram MONITORING FAN/PUMP MOTORS FOR POSITIVE PROOF OF FLOW
(H706)
Wiring Diagram
ORDERING INFORMATION
MODEL| AMPERAGE
RANGE| STATUS OUTPUT
(MAX.)| MIN. TRIP
POINT| HOUSING| STATUS LED| UL| CE
---|---|---|---|---|---|---|---
H606| 1.25 to 50 A| N.C. 0.1 A @ 30 Vdc| 1.25 A or less| Split-Core| •| •| •
I-1706| 1 to 135 A| 1.0 A or less| Solid-Core| •| •| •
I-1806| 0.75 to 50 A| 0.75 A or less| Solid-Core| •| •| •
1. Listed for use on 75°C insulated conductors.
HQ0001756.H 0324
800.354.8556
+1 503.598.4564
sales@veris.com
intl@veris.com
veris.com
Documents / Resources
|
Veris HHX06 Adjustable Current
Switch
[pdf] Installation Guide
HHX06 Adjustable Current Switch, HHX06, Adjustable Current Switch, Current
Switch, Switch
---|---