HEW Economy Series wall-mount humidity transmitters offer high performance in easy-to-install housing at an affordable price. The thin-film capacitive sensor element provides high accuracy and performance, great long-term stability, and full recovery from saturation. Temperature sensing options are also available. The wall housing was created using sophisticated thermal analysis techniques for optimum airflow. It is ideal for schools and other applications requiring exceptional durability and a discrete appearance. All Economy models come with a standard one-year warranty.

SPECIFICATIONS

INPUT POWER

Voltage Model Class 2; 12 to 24 Vdc or 24 Vac
mA Model Class 2; 12 to 24 Vdc
AC Voltage Tolerance ±10%
AC Frequency 50/60 Hz
Max. Inrush Current after 1 msec (mA version) 25 mA

OUTPUT POWER

mA Output 4 to 20mA, 2-wire, not polarity sensitive
mA Max. Loop Resistance 500 Ω at 24 Vdc input voltage; 250 Ω at 12 Vdc input

voltage
Voltage Output| 0 to 5 V or 0 to 10 V (jumper selectable)
Voltage Min. Load Resistance| 5 kΩ
Voltage Min. Sinking Current| 0.2 mA

RH TRANSMITTER

RH Element Digitally profiled thin-film capacitive, non-removable
Accuracy* ±2%, 3%, or 5% (10 to 90% RH, 20 to 30 °C)
Temperature Effect (Outside 20° to 30°C) ≤0.1% RH per °C

Response Time

(to 90% change at 20°C)

| 110 sec
Annual Drift| ≤1%
Output Scaling| 0 to 100% RH

TEMPERATURE TRANSMITTER OPTION

Active Output Accuracy ±0.5 °C (±.9 °F)
Active Output Temp Scaling 10 to 35 °C (50 to 95 °F)

Self-Heating Error

(Resistive temperature only)

| ≤±0.5 °C at 20 to 30 °C (68 to 86 °F);

≤±0.75 °C outside of 20 to 30 °C (68 to 86 °F)

OPERATING ENVIRONMENT

Operating Temperature 0 to 50 °C (32 to 122 °F)
Operating Humidity 0 to 100% RH non-condensing (Unit will recover from

saturation)

HOUSING

Material ABS plastic with UL V-0 5VB Flame Class
Mounting Holes US and European junction box
Mounting Location For indoor use only. Not suitable for wet locations.

WARRANTY

Limited Warranty 1 year

COMPLIANCE INFORMATION

Agency Approvals| EMC Conformance: Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU
---|---

  • Humidity sensor measurement uncertainty should include accuracy, hysteresis, temperature coefficient, and stability.

0-5V/0-10V MODELS, TEMPERATURE TRANSMITTER

4-20 mA MODELS, TEMPERATURE TRANSMITTER

4-20 mA MODELS, THERMISTOR

ORDERING INFORMATION

Veris-HEW3MSTA-Wall-Humidity-Sensor-FIG-6

DIMENSIONAL DRAWING

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals