Veris Industries CD2 Series Duct Mount All In One RH Temp VOC and PM Sensing Owner’s Manual
- June 14, 2024
- VERIS INDUSTRIES
Table of Contents
- CD2 SERIES
- BACnet & Modbus
- Self-calibrating
- Dual-beam NDIR CO2 sensor
- APPLICATIONS
- Easy to install
- Field selectable
- Field replaceable
- SPECIFICATIONS
- DIMENSIONAL DRAWING
- WIRING DIAGRAM
- MAXIMUM POWER CONSUMPTION
- ORDERING INFORMATION
- REPLACEABLE RH ELEMENTS & TEMPERATURE AND HUMIDITY CALIBRATION MODULES
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Veris Industries CD2 Series Duct Mount All In One RH Temp VOC and PM
Sensing Owner’s Manual
CD2 SERIES
Duct Mount All-in-One CO2 , RH, Temp, VOC and PM Sensing
CD2 Series Air Quality Sensors are duct mount all-in-one sensors for monitoring air quality. The device combines CO2, temperature, humidity, VOC and particulate matter (PM) sensing into a single unit to ensure a building’s optimum air quality and energy efficiency.
Each device is an active sensor that converts a measurement into one of the following output options:
- Analog output: 4-20 mA, 0 to 5 Vdc or 0 to 10 Vdc
- Protocol output : BACnet MS/TP, Modbus RTU
Different models are available based on application requirements for lower- cost installations.
CD2 is available with an LCD display option on selected models. See Ordering Information for details
BACnet & Modbus
Embedded BACnet and Modbus communication protocols for easy systems integration
Self-calibrating
Innovative self-calibration algorithm…easy to maintain
Dual-beam NDIR CO2 sensor
Dual-beam, non-dispersive infrared technology (NDIR) repeatable to ±20 ppm ±1% of measured value… high accuracy measurement
APPLICATIONS
- HVAC systems
- Indoor air quality monitoring
- Life sciences applications
Easy to install
Latch-on sensor cover and screwless terminal block wiring with spring actuator
Field selectable
Field-selectable outputs for operation flexibility
Field replaceable
Replace RH element and temp transmitter in the field… maintain accuracy and minimize downtime and cost
- Key component for the LEED green building program and WELL Building Standard*
Leadership in Energy and Environmental Design (LEED) is a registered trademark of the US Green Building Council. The WELL Building Standard is a trademark of the International WELL Building Institute in the United States and other countries..
SPECIFICATIONS
OPERATING & STORAGE ENVIRONMENT
Operating Temp. Range | 0 to 50 °C (32 to 122 °F) |
---|---|
Operating Humidity Range | 0 to 95% RH (non-condensing) |
Storage Temp. Range | -25 to 70 °C (-13 to 158 °F) |
Storage Humidity Range | 0 to 95% RH (non-condensing) |
Power Supply | 3-wire volt mode: 20 to 30 Vdc, 24 Vac, 50 to 60 Hz |
Output | Analog: selectable 4 to 20 mA, 0 to 5 Vdc, 0 to 10 Vdc Protocol: |
BACnet MS/TP, Modbus RTU
Power Consumption| See Maximum Power Consumption table, next page
Tube Length| 200 mm
Medium| Neutral gas, air
Housing Material| Polycarbonate; flammability rating UL 94 V0
Mounting Location| For indoor use only. Not suitable for wet locations.
IP Rating| IP 65
Protection Class| Class III
CO2 SENSOR
Sensor Type | Non-dispersive infrared (NDIR), diffusion sampling |
---|---|
Output Range | Analog models: 0 to 2000/5000 ppm (selectable) Protocol models: |
0 to 5000 ppm
Accuracy| ±30 ppm ±3% of measured value
Repeatability| ±20 ppm ±1% of measured value
Response Time| <60 seconds for 90% step change
Calibration| Field calibration support
VOC SENSOR OPTION
Sensor Type | Solid state |
---|---|
Output Range | 0 to 100% AQI for VOC |
Accuracy | ±15% sensor-to-sensor variation |
LEVEL | VENTILATION RECOMMENDATION |
AQI Table | >61% |
20 to 61% | Significantly increased |
10 to 20% | Slightly increased |
5 to 10% | Average |
0 to 5% | Target value |
RH SENSOR OPTION
HS Sensor | Thin-film capacitive, replaceable |
---|---|
Accuracy* | ±2% from 10 to 80% RH @ 25 °C (77 °F)±1%, ±2% replaceable models |
Hysteresis | 1.5% typical |
Linearity | Included in accuracy specification |
Stability | ±1% @ 20°C (68 °F) annually for 2 years |
Output Range | 0 to 100% RH |
Temperature Coefficient | ±0.1% RH/°C above or below 25 °C (77 °F) typical |
TEMPERATURE SENSOR OPTION
User configuration | °C or °F |
---|---|
Sensor Type | Solid state, integrated circuit |
Temp. Sensing Element** | See Ordering Information on page 2 for available |
temp. sensing elements
Time Constant| Air velocity 1.5 m/s. approx. 72 s; Air velocity 3.0 m/s.
approx. 52 s
Accuracy***| ±0.2 °C (±0.4 °F) typical at 25 °C
Resolution| 0.1 °C (0.1 °F)
Range| 0 to 50 °C (32 to 131 °F)
PM SENSOR OPTION
Sensor Type | Laser-scatter |
---|---|
Particulate Size | PM1.0, PM2.5, PM4.0, PM10 |
Resolution | ±1 μg/m³ |
Mass Concentra- tion Range | ±1 μg/m³ |
Accuracy | PM 1 and PM 2.5: ±10 μg/m³ (0 to 100 μg/m³),±10% (100 to |
1000 μg/m³)PM 4 and PM 10: ±25 μg/m³ (0 to 100 μg/m³),±25% (100 to 1000 μg/m³)
DISPLAY MODELS
LCD Type | Positive display with backlight |
---|---|
Measurement Values Displayed | CO2: ppm, Temp: °C or °F, Humidity: % RH, VOC: % |
AQI, PM: μg/m³
Display Resolution| CO2: 1 ppm, Temp: 0.1 °C or °F, Humidity: 0.1% RH VOC: 1%
AQI, PM: 1 μg/m³
WIRING TERMINALS
Terminal Blocks | Screwless terminal block with spring actuator, 16-24 AWG |
---|
WARRANTY
Limited Warranty | 5 years |
---|
COMPLIANCE INFORMATION
Agency Approvals| UL 916 European conformance CE:
EN61000-6-2, EN61000-6-3, EN61000 Series, immunity,
EN 61326-1FCC Part 15 Class AREACH, RoHS, RoHS 2 (China),RCM (Australia),
ICES-003
(Canada), UKCA (UK)
---|---
- Humidity sensor measurement uncertainty should include: accuracy, hysteresis, temperature coefficient and stability.
- **See thermistor table Z202030 for accuracy.
- ***±0.5 °C over full operating range.
- ****Sensor-to-sensor variation.
DIMENSIONAL DRAWING
WIRING DIAGRAM
See installation guide for wiring information.
MAXIMUM POWER CONSUMPTION
SERIES | LCD | CO2/VOC | PM | TEMP/RH | MAX. POWER |
---|---|---|---|---|---|
**** CD2 Analog | Yes | Yes | Yes | Yes | 9VA @ 24VAC |
Yes | Yes | No | Yes | 8VA @ 24VAC | |
Yes | No | Yes | Yes | 7VA @ 24VAC | |
No | Yes | No | Yes | 6VA @ 24VAC | |
No | Yes | No | No | 4VA @ 24VAC | |
**** CD2 Protocol | Yes | Yes | Yes | Yes | 4VA @ 24VAC |
Yes | Yes | No | Yes | 3VA @ 24VAC | |
No | Yes | Yes | Yes | 2VA @ 24VAC | |
Yes | Yes | No | Yes | 1.5VA @ 24VAC |
ORDERING INFORMATION
CD2LAXAVP | X | Temp Transmitter | X | X | X | |
---|---|---|---|---|---|---|
CD2LAXAVX | X | Temp Transmitter | X | X | ||
CD2LAXAXP | X | Temp Transmitter | X | |||
CD2XA2AVX | X | Temp Transmitter | X | X | ||
CD2XA2BCX | X | 100 PT RTD | X | |||
CD2XA2CCX | X | 1000 PT RTD | X | |||
CD2XA2DCX | X | 10K T2 | X | |||
CD2XA2HCX | X | 10K T3 | X | |||
CD2XA2KCX | X | 10K Curve G/11K | X | |||
CD2XA2MCX | X | 20K NTC | X | |||
CD2XA2NCX | X | 1.8K | X | |||
CD2XAXAVX | Temp Transmitter | X | X | |||
CD2XAXBCX | 100 PT RTD | X | ||||
CD2XAXCCX | 1000 PT RTD | X | ||||
CD2XAXDCX | 10K T2 | X | ||||
CD2XAXHCX | 10K T3 | X | ||||
CD2XAXKCX | 10K Curve G/11K | X | ||||
CD2XAXMCX | 20K NTC | X | ||||
CD2XAXNCX | 1.8K | X |
Protocol Models
CD2LP2AVP | X | X | Temp Transmitter | X | X | X |
---|---|---|---|---|---|---|
CD2LP2AVX | X | X | Temp Transmitter | X | X | |
CD2LPXAVP | X | Temp Transmitter | X | X | X | |
CD2LPXAVX | X | Temp Transmitter | X | X | ||
CD2XP2AVP | X | Temp Transmitter | X | X | X | |
CD2XP2AVX | X | Temp Transmitter | X | X | ||
CD2XPXAVP | Temp Transmitter | X | X | X | ||
CD2XPXAVX | Temp Transmitter | X | X |
Note: Replaceable RH and temperature modules available to be ordered separately per table below.
REPLACEABLE RH ELEMENTS & TEMPERATURE AND HUMIDITY CALIBRATION MODULES
MODEL | DESCRIPTION |
---|---|
HS1N | Replaceable RH Sensor, 1% with NIST certificate |
HS2N | Replaceable RH sensor, 2% with NIST certificate |
HS2X | Replaceable RH sensor, 2% |
TS2* | Replaceable temperature module with 2-point calibrationcertificate |
THS2* | Replaceable temperature and humidity module with 2-pointcalibration |
certificate
*For temperature transmitter models only.
Replaceable RH and Temperature Module
800.354.8556
+1 503.598.4564
sales@veris.com
intl@veris.com
veris.com
Read User Manual Online (PDF format)