Veris Industries CD2 Series Duct Mount All In One RH Temp VOC and PM Sensing Owner’s Manual

June 14, 2024
VERIS INDUSTRIES

Veris Industries CD2 Series Duct Mount All In One RH Temp VOC and PM Sensing Owner’s Manual
Series Duct Mount All In One RH Temp VOC and PM
Sensing

CD2 SERIES

Duct Mount All-in-One CO2 , RH, Temp, VOC and PM Sensing

CD2 Series Air Quality Sensors are duct mount all-in-one sensors for monitoring air quality. The device combines CO2, temperature, humidity, VOC and particulate matter (PM) sensing into a single unit to ensure a building’s optimum air quality and energy efficiency.

Each device is an active sensor that converts a measurement into one of the following output options:

  • Analog output: 4-20 mA, 0 to 5 Vdc or 0 to 10 Vdc
  • Protocol output : BACnet MS/TP, Modbus RTU

Different models are available based on application requirements for lower- cost installations.

CD2 is available with an LCD display option on selected models. See Ordering Information for details

BACnet & Modbus

Embedded BACnet and Modbus communication protocols for easy systems integration

Self-calibrating

Innovative self-calibration algorithm…easy to maintain

Dual-beam NDIR CO2 sensor

Dual-beam, non-dispersive infrared technology (NDIR) repeatable to ±20 ppm ±1% of measured value… high accuracy measurement

APPLICATIONS

  • HVAC systems
  • Indoor air quality monitoring
  • Life sciences applications

Easy to install

Latch-on sensor cover and screwless terminal block wiring with spring actuator

Field selectable

Field-selectable outputs for operation flexibility

Field replaceable

Replace RH element and temp transmitter in the field… maintain accuracy and minimize downtime and cost

  • Key component for the LEED green building program and WELL Building Standard*

Leadership in Energy and Environmental Design (LEED) is a registered trademark of the US Green Building Council. The WELL Building Standard is a trademark of the International WELL Building Institute in the United States and other countries..

SPECIFICATIONS

OPERATING & STORAGE ENVIRONMENT 

Operating Temp. Range 0 to 50 °C (32 to 122 °F)
Operating Humidity Range 0 to 95% RH (non-condensing)
Storage Temp. Range -25 to 70 °C (-13 to 158 °F)
Storage Humidity Range 0 to 95% RH (non-condensing)
Power Supply 3-wire volt mode: 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
Output Analog: selectable 4 to 20 mA, 0 to 5 Vdc, 0 to 10 Vdc Protocol:

BACnet MS/TP, Modbus RTU
Power Consumption| See Maximum Power Consumption table, next page
Tube Length| 200 mm
Medium| Neutral gas, air
Housing Material| Polycarbonate; flammability rating UL 94 V0
Mounting Location| For indoor use only. Not suitable for wet locations.
IP Rating| IP 65
Protection Class| Class III

CO2 SENSOR

Sensor Type Non-dispersive infrared (NDIR), diffusion sampling
Output Range Analog models: 0 to 2000/5000 ppm (selectable) Protocol models:

0 to 5000 ppm
Accuracy| ±30 ppm ±3% of measured value
Repeatability| ±20 ppm ±1% of measured value
Response Time| <60 seconds for 90% step change
Calibration| Field calibration support

VOC SENSOR OPTION

Sensor Type Solid state
Output Range 0 to 100% AQI for VOC
Accuracy ±15% sensor-to-sensor variation
LEVEL VENTILATION RECOMMENDATION
AQI Table >61%
20 to 61% Significantly increased
10 to 20% Slightly increased
5 to 10% Average
0 to 5% Target value

RH SENSOR OPTION

HS Sensor Thin-film capacitive, replaceable
Accuracy* ±2% from 10 to 80% RH @ 25 °C (77 °F)±1%, ±2% replaceable models
Hysteresis 1.5% typical
Linearity Included in accuracy specification
Stability ±1% @ 20°C (68 °F) annually for 2 years
Output Range 0 to 100% RH
Temperature Coefficient ±0.1% RH/°C above or below 25 °C (77 °F) typical

TEMPERATURE SENSOR OPTION

User configuration °C or °F
Sensor Type Solid state, integrated circuit
Temp. Sensing Element** See Ordering Information on page 2 for available

temp. sensing elements
Time Constant| Air velocity 1.5 m/s. approx. 72 s; Air velocity 3.0 m/s. approx. 52 s
Accuracy***| ±0.2 °C (±0.4 °F) typical at 25 °C
Resolution| 0.1 °C (0.1 °F)
Range| 0 to 50 °C (32 to 131 °F)

PM SENSOR OPTION

Sensor Type Laser-scatter
Particulate Size PM1.0, PM2.5, PM4.0, PM10
Resolution ±1 μg/m³
Mass Concentra- tion Range ±1 μg/m³
Accuracy PM 1 and PM 2.5: ±10 μg/m³ (0 to 100 μg/m³),±10% (100 to

1000 μg/m³)PM 4 and PM 10: ±25 μg/m³ (0 to 100 μg/m³),±25% (100 to 1000 μg/m³)

DISPLAY MODELS

LCD Type Positive display with backlight
Measurement Values Displayed CO2: ppm, Temp: °C or °F, Humidity: % RH, VOC: %

AQI, PM: μg/m³
Display Resolution| CO2: 1 ppm, Temp: 0.1 °C or °F, Humidity: 0.1% RH VOC: 1% AQI, PM: 1 μg/m³

WIRING TERMINALS

Terminal Blocks Screwless terminal block with spring actuator, 16-24 AWG

WARRANTY

Limited Warranty 5 years

COMPLIANCE INFORMATION

Agency Approvals| UL 916 European conformance CE:
EN61000-6-2, EN61000-6-3, EN61000 Series, immunity,
EN 61326-1FCC Part 15 Class AREACH, RoHS, RoHS 2 (China),RCM (Australia), ICES-003
(Canada), UKCA (UK)
---|---

  • Humidity sensor measurement uncertainty should include: accuracy, hysteresis, temperature coefficient and stability.
  • **See thermistor table Z202030 for accuracy.
  • ***±0.5 °C over full operating range.
  • ****Sensor-to-sensor variation.

DIMENSIONAL DRAWING

Dimension

WIRING DIAGRAM

See installation guide for wiring information.

MAXIMUM POWER CONSUMPTION

SERIES LCD CO2/VOC PM TEMP/RH MAX. POWER
**** CD2 Analog Yes Yes Yes Yes 9VA @ 24VAC
Yes Yes No Yes 8VA @ 24VAC
Yes No Yes Yes 7VA @ 24VAC
No Yes No Yes 6VA @ 24VAC
No Yes No No 4VA @ 24VAC
**** CD2 Protocol Yes Yes Yes Yes 4VA @ 24VAC
Yes Yes No Yes 3VA @ 24VAC
No Yes Yes Yes 2VA @ 24VAC
Yes Yes No Yes 1.5VA @ 24VAC

ORDERING INFORMATION

CD2LAXAVP X Temp Transmitter X X X
CD2LAXAVX X Temp Transmitter X X
CD2LAXAXP X Temp Transmitter X
CD2XA2AVX X Temp Transmitter X X
CD2XA2BCX X 100 PT RTD X
CD2XA2CCX X 1000 PT RTD X
CD2XA2DCX X 10K T2 X
CD2XA2HCX X 10K T3 X
CD2XA2KCX X 10K Curve G/11K X
CD2XA2MCX X 20K NTC X
CD2XA2NCX X 1.8K X
CD2XAXAVX Temp Transmitter X X
CD2XAXBCX 100 PT RTD X
CD2XAXCCX 1000 PT RTD X
CD2XAXDCX 10K T2 X
CD2XAXHCX 10K T3 X
CD2XAXKCX 10K Curve G/11K X
CD2XAXMCX 20K NTC X
CD2XAXNCX 1.8K X

Protocol Models

CD2LP2AVP X X Temp Transmitter X X X
CD2LP2AVX X X Temp Transmitter X X
CD2LPXAVP X Temp Transmitter X X X
CD2LPXAVX X Temp Transmitter X X
CD2XP2AVP X Temp Transmitter X X X
CD2XP2AVX X Temp Transmitter X X
CD2XPXAVP Temp Transmitter X X X
CD2XPXAVX Temp Transmitter X X

Note: Replaceable RH and temperature modules available to be ordered separately per table below.

REPLACEABLE RH ELEMENTS & TEMPERATURE AND HUMIDITY CALIBRATION MODULES

MODEL DESCRIPTION
HS1N Replaceable RH Sensor, 1% with NIST certificate
HS2N Replaceable RH sensor, 2% with NIST certificate
HS2X Replaceable RH sensor, 2%
TS2* Replaceable temperature module with 2-point calibrationcertificate
THS2* Replaceable temperature and humidity module with 2-pointcalibration

certificate

*For temperature transmitter models only.

Replaceable RH and Temperature Module

800.354.8556
+1 503.598.4564
[email protected] 
[email protected] 
veris.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

VERIS INDUSTRIES User Manuals

Related Manuals