VERIS INDUSTRIES TW2 Series Wall Mount Temperature Sensors Installation Guide
- June 9, 2024
- VERIS INDUSTRIES
Table of Contents
VERIS INDUSTRIES TW2 Series Wall Mount Temperature Sensors
This product is not intended for life or safety applications.
- Do not install this product in hazardous or classified locations.
- Read and understand the instructions before installing this product.
- Turn of all power supplying equipment before working on it.
- The installer is responsible for conformance to all applicable codes.
If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired. No responsibility is assumed by the manufacturer for any consequences arising out of the use of this material.
Product Overview
The TW2 Series of temperature sensors for living space is a versatile sensor platform for use with BAS controllers designed to accept 4 to 20mA, 0 to 5Vdc or 0 to 10Vdc outputs. TW2 Series sensors are available with three user interface options: touchscreen, LCD with three buttons and blank.
Product Identification
**X **
Specifications
OPERATING ENVIRONMENT
Input Power| Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
Analog Output| Selectable 4 to 20 mA, 0 to 5 V, 0 to 10 V
Operating Temp. Range| 0 to 50 °C (32 to 122 °F)
Operating Humidity Range| 0 to 95% RH non-condensing
Housing Material| High-impact ABS plastic
Terminal Block Torque| 0.5 to 0.6 N-m (0.37 to 0.44 in-lbf)
IP Rating| IP 30
Mounting Location| For indoor use only. Not suitable for wet locations.
Surface Mount| The device can be surface mounted on Single Gang J-Box,
British Standard and CE60 wall boxes
TEMPERATURE TRANSMITTER OPTION
Sensor Type| Solid state, integrated circuit
Accuracy| ±0.2 °C (±0.4 °F) typical
Resolution| 0.1 °C (0.1 °F)
Range| 0 to 50 °C (32 to 122 °F)
DISPLAY MODELS
Touchscreen| 61 mm (2.4 in), color, backlit, capacitive, 240×300 px
Setpoint: 0-10Vdc. Temperature or fan speed selectable Timeout override:
Display timeout*
Lockout override: Touchscreen/button lockout*
LCD| 52mm (2.05 in), segmented with 3 buttons
Setpoint: 0-10Vdc. Temperature or fan speed selectable
Timeout override: Display timeout
Lockout override: Touchscreen/button lockout
_SETPOINTS_**
Temperature Setpoint| 0 to 10V output
Scale: 10 to 35 °C (50 to 95 °F) / 0 to 50 °C (32 to 122 °F)
Fan Speed Setpoint| 0 to 10V output
Off 0V, Auto 1.5V, Low 3.3V, Med. 6.7V, High 10.0V
WIRING TERMINALS
Terminal Blocks| Screw terminals, 18-24 AWG
Screw Terminal Torque| 0.2 N-m (2.0 in-lbF) max.
OVERRIDE
Override Button| Display models feature a momentary-to-ground override
button
WARRANTY
Limited Warranty| 5 years
COMPLIANCE INFORMATION
Agency Approvals| UL 916, European conformance CE: EN61000-6-2,
EN61000-6-3, EN61000 Series – industrial immunity, EN 61326-1
FCC Part 15 Class B, REACH, RoHS, RCM (Australia), ICES-003 (Canada)
*DIP switch selectable.
** One setpoint type is selectable via DIP switch on display models only.
Dimensions
Functions
The TW2 Series sensor measures the temperature in a room and provides analog outputs to a controller
Installation
-
Remove the cover from the base at the bottom of the device.
-
Position the sensor base vertically on the wall 1.35 m (4.5 ft.) above the floor with the “UP” arrow facing upward. Locate away
from windows, vents and other sources of draft. If possible, do not mount on an external wall, as this may cause inaccurate temperature readings -
Pull 18 or 22 AWG cable(s) through the hole in the backplate.
-
Mount the backplate onto the wall using the screws provided
Connect the wires to the screw terminals. Do not over-tighten the screws.
Wiring for models with temperature transmitter (except TW2LAXA):
Wiring for models with temperature transmitter (TW2LAXA only):
Wiring for models with RTD/thermistor:
|
- Momentary to ground.
0-10V DIP switch selectable for temperature, RH or fan speed (off, 0V, Auto 1.5V, Low 3.3V, Medium 6.7V or high 10.0V).
Set the DIP switches.
** Switch| Function| Description
---|---|---
1| Output mode| ON – 4-20mA output mode enabled OFF – Voltage output mode enabled
2| Voltage output range*| ON – 0-5V output range enabled OFF 0-10V output range enabled
3| Unused| Unused
4| Unused| Unused
5| Setpoint output type| ON – Temperature setpoint enabled (temp range selected on DIP switch 6) OFF – Fan Speed setpoint enabled
6| Setpoint output temperature range| Temperature setpoint (must be enabled on DIP switch 5) ON – Temp range 1, 50 to 95 °F (10 to 35 °C) enabled
OFF – Temp range 2, 32 to 122 °F (0 to 50 °C) enabled
7| Display times out and turns off after 6-10 seconds of touchscreen/button
press| ON – Display Timeout enabled OFF – Display Timeout disabled
8| Touchscreen touch functions and buttons are disabled| ON – Touchscreen
touch/button functions disabled OFF – Touchscreen touch/button functions
enabled
5. With sensor base fully installed, align top of cover to mounting tabs on top of sensor base. Swing cover downward until it latches at the bottom.
Touchscreen Operation
=Install locking screw to secure cover in closed position.
Main Screen
The touchscreen user interface displays temperature sensor output values,
setpoint value and menu button
Menu Screen
The menu screen opens when pressing the Menu button on the main screen.
Integrator’s submenu, occupancy/override, Fahrenheit/Celsius, settings and
setpoint submenu (temp or fan, determined by DIP switch settings) are
displayed on the menu screen
Menu Button Functions
Integrator’s Submenu Press this icon to access the Integrator’s menu.|
Submenu Only
Occupied Override Button Press this icon to provide momentary ground output to
the controller| Single Press Only
Signals occupied/override call to controller
Fahrenheit/Celsius Switch Press this icon to display either °C or °F.| Single
Press Only
Changes units to Fahrenheit when pressed.
Changes units to Celsius when presse
Settings
This icon provides the ability to change the color scheme of the display
|
Temp Setpoint Adjustment
Click this icon to access the setpoint change menu. Mutually exclusive with
fan speed, set by DIP switch.
Fan Speed
Click this icon to access the fan speed menu. Mutually exclusive with humidity
and fan speed. Set by DIP switch.
|
LCD Display Operation
Button Functions
Display Icons
The main screen displays sensor values for temperature and Celsius/Fahrenheit
Setpoint Function
A single 0-10V setpoint (temperature or fan speed) can be selected via DIP switch.
Temperature Setpoint Adjustment
Fan Speed Setpoint Adjustment
Changing Celsius and Fahrenheit Scales
Occupied/Override Button
China RoHS Compliance Information
Environment-Friendly Use Period (EFUP) Table
This table is made according to SJ/T 11364.
O: indicates that the concentration of hazardous substance in all of the
homogeneous materials for this part is below the limit as stipulated in GB/T
26572.
X: indicates that concentration of hazardous substance in at least one of
the homogeneous materials used for this part is above the limit as stipulated
in GB/T 26572 Z000057-0B
©2022 Veris Industries USA 800.354.8556 or +1.503.598.4564 /
support@veris.com 0422
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the
Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries,
L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their
respective owners.