**** WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
- Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E or CSA Z462.
- This equipment must only be installed and serviced by qualified electrical personnel.
- Turn off all power supplying this equipment before working on or inside equipment.
- Always use a properly rated voltage sensing device to confirm power is off.
- Replace all devices, doors and covers before turning on power to this equipment.
Failure to follow these instructions can result in death, serious injury or
equipment damage.
This product is intended for use in HVAC and building environmental control
applications.
It is not intended for direct medical monitoring of patients.
Read and understand these instructions before installing this product.
The installer is responsible for all applicable codes.
If this product is used in a manner not specified by the manufacturer, the
protection provided by the product may be impaired. No responsibility is
assumed by the manufacturer for any consequences arising out of the use of
this material.
Product Overview
HD2 Protocol Series Humidity Sensors provide an ideal solution for measuring
relative humidity in a wide range of conditions. All models are equipped with
a thin-film capacitive humidity sensor that is easy to replace in the field. A
solid state temperature sensor provides high-accuracy measurements.
HD2 is an all-in-one device combining humidity and temperature sensing.
Intended for duct mount applications, the device ensures a building’s optimum
temperature and humidity levels, resulting in greater energy efficiency.
Each device is an active sensor that converts a humidity or temperature
measurement into a BACnet MS/TP or Modbus RTU output.
Different models are available based on application requirements for lower-
cost installations.
HD2 is available with an LCD display option on select models (see Product
Identification section below).
Product Identification
Note: Replaceable RH and temperature modules available to be ordered
separately per table below.
Replaceable RH Elements & Temperature and Humidity Calibration Modules
Model
|
Description
---|---
HS1N| Replaceable RH sensor, 1% with NIST certificate
HS2N| Replaceable RH sensor, 2% with NIST certificate
HS2X| Replaceable RH sensor, 2%
TS2| Replaceable temperature module with 2-point calibration certificate
THS2| Replaceable temperature and humidity module with 2-point calibration
certificate
*For temperature transmitter models only.
Note: For instructions on installing replaceable elements, see Z207941,
Replacement Humidity and Temperature Sensors Installation Guide.
Specifications
OPERATING / STORAGE ENVIRONMENT
Operating Temp. Range| -35 to 60 °C (-31 to 140 °F)
Operating Humidity Range| 0 to 95% RH (non-condensing)
Storage Temp. Range| -35 to 70 °C (-31 to 158 °F)*
Storage Humidity Range| 0 to 95% RH (non-condensing)
Power Supply| 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
Output| BACnet MS/TP, Modbus RTU
Power Consumption| See Maximum Power Consumption table, page 8
Tube Length| 200 mm
Medium| Neutral gas, air
---|---
Housing Material| Polycarbonate; flammability rating UL 94 V0
Mouting Location| For indoor use only. Not suitable for wet locations.
IP Rating| IP65
Protection Class| Class III
RH SENSOR
HS Sensor| Thin-film capacitive, replaceable
Accuracy**| ±2% from 10 to 80% RH @ 25 °C (77 °F)
±1%, ±2% NIST and 2% replaceable option
Hysteresis| 1.5% typical
Linearity| Included in accuracy specification
Stability| ±1% @ 20°C (68 °F) annually for 2 years
Output Range| 0 to 100% RH
Temperature Coefficient| ±0.1% RH/°C above or below 25 °C (77 °F) typical
TEMPERATURE SENSOR
User Configuration| °C or °F
Sensor Type| Solid state, integrated circuit
Time Constant| Air velocity 1.5 m/s. approx. 72 s; Air velocity 3.0 m/s.
approx. 52 s
Accuracy**| ±0.2 °C (±0.4 °F) typical typical at 25 °C
Resolution| 0.1 °C (0.1 °F)
Range| -35 to 60 °C (-31 to 140 °F)
DISPLAY MODELS
LCD Type| Positive display with backlight
Measurement Values
Displayed
| Temperature: °C or °F Humidity: % RH
Display Resolution| Temperature: 0.1 °C or °F Humidity: 0.1% RH
WIRING TERMINALS
Terminal Blocks| Screwless terminal block with spring actuator, 16-24 AWG
WARRANTY
Limited Warranty| 5 years
COMPLIANCE INFORMATION
Agency Approvals| UL 916
European conformance CE: EN61000-6-2, EN61000-6-3, EN61000
Series immunity, EN 61326-1 FCC Part 15 Class A
Green Premium (REACH, RoHS), RoHS 2 (China), RCM (Australia), ICES-003
(Canada), UKCA (UK)
- Duct mount model with temperature and humidity only. LCD operation from -10 to 60 °C (14 to 140 °F).
** Humidity sensor measurement uncertainty should include: accuracy, hysteresis, temperature coefficient and stability.
*** ±0.5 °C over full operating range.
Dimensions mm (in.)
Installation
-
Prepare the duct for installation by drilling holes to accommodate the probe tube. Ensure the gasket on the back is depressed to prevent leakage between the product and the duct. Do not over-tighten the screws.
-
Ensure the probes are installed in the direction of the air flow. Install the probe in the middle of the duct and away from any restrictions to allow proper air flow.
-
Release the latch on the lid to access the DIP switches and terminal block.
-
Wire the connections per the diagram in the Wiring section below. This device features spring terminals for screwless termination. Open the terminal point by inserting a screwdriver, then insert the wire above. Release the screwdriver to hold the wire in place. Details on wiring and configuration are contained in the next sections of this document.
-
Secure the latch-on cover in the closed position and remove the clear protective mask on the front label of the device.
Wiring **
**
NOTICE
PRODUCT DAMAGE DUE TO ELECTRO-STATIC DISCHARGE
Circuit boards and components can be damaged by static electricity or electro-
static discharge (ESD). Observe the following electro-static precautions when
handling this product and cables and components connected to the product.
- Keep static-producing material such as plastic, upholstery, carpeting, etc. out of the immediate work area
- Store the product in ESD-protective packaging when it is not installed in the panel
- When handling the product or a conductive cable/ESD-sensitive component connected to the product, wear a conductive wrist strap connected to ground through a minimum of 1 MΩ resistance
- Do not touch exposed conductors and component leads with skin or clothing
Failure to follow these instructions can result in equipment damage.
NOTICE
INACCURATE READINGS
- Do not run wiring in the same conduit as AC power wiring. Close proximity to AC power may influence accuracy.
Failure to follow these instructions can result in reduced accuracy.
Wiring Diagram
Configuration
Address Configuration
Each device on a single network must have a unique address. Set the DIP switch
labeled “ADDRESS” to assign a unique address before the device is connected to
the network. If an address is selected that conflicts with another device,
neither device will be able to communicate.
Address the device as any whole number between and including 1 to 127. Note
that zero is not a valid address for Modbus; zero is a valid address for
BACnet. Positions 1 through 7 of the “ADDRESS” DIP switch designate the
address. Position 8 toggles between the Modbus and BACnet communication
protocols, as shown in the diagram below. This is the right bank of DIP
switches on the sensor.![VERIS HD2 Protocol Series Duct Mount Humidity Sensors
-
Wiring Diagram 1](https://manuals.plus/wp-content/uploads/2023/12/VERIS-HD2 -Protocol-Series-Duct-Mount-Humidity-Sensors-Wiring-Diagram-1.jpg)To set an address using the DIP switch, simply add the values of any switches that are in the ON position. For example, an address of 73 is set as shown in the diagram below.Position number 1 has an ON value of 1, position number 4 has an ON value of 8 and position number 7 has an ON value of 64 (1 + 8 + 64 = 73).
Communications Configuration
See the Installation section, Step 3 for the location of the DIP switches. The following parameters are configurable:- Parity (Modbus only): None, Odd, None1 (one stop bit), Even
- Baud rate: 9600, 19200, 38400, 57600 (Modbus), 76800 (BACnet)
Example: No Parity, 19200 Baud
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
---|---|---|---|---|---|---|---|
off | off | on | off | off | off | off | off |
None | 19200 Baud | Unused |
Modbus Point Map
Function Codes:
Function Code | Function |
---|---|
03 | Read holding (RW) registers |
04 | Read input (RO) registers |
06 | Write single register* |
16 | Write multiple registers |
01 | Read coils |
05 | Write single coil |
15 | Write multiple coils |
* Not supported.
All of these values correspond to BACnet objects with the same name. See the
BACnet Conformance Statement on page 8 for their definitions.
Note that an attempt to write to “read only” holding registers will give an
error and the entire write command will not be executed even if writing to
read/write locations were also requested. Exception code 2 is given in this
case. “Preserved” means the values is maintained through power outages.
32-Bit Input Registers (Read Only):
Register | Description |
---|---|
1 | Temperature reading in IEEE 32-bit floating point (°C) |
3 | Humidity reading in IEEE 32-bit floating point |
9-41 | Model (numeric representation of ASCII characters) |
42-45 | Serial number (numeric representation of ASCII characters) |
32-Bit Holding Registers (Read/Write):
Register | Description |
---|---|
7* | Device name (numeric representation of ASCII characters) |
*Preserved during power outages.
Coils (Read/Write):
Register | Description |
---|---|
5* | Temperature (°C) |
*Preserved during power outages.
BACnet Descriptions
Note: In the tables below, all properties are read-only unless otherwise
noted. “Preserved” means the value is maintained through power outages.
Present_Value Range Restrictions:
Object Name | Minimum Value | Maximum Value |
---|---|---|
DEV – Object_Name | 1 Character | 65 Characters |
Device_Instance | 0 | 4,194,302 |
Standard Object Types Supported:
Object Type | Supported Optional Properties | Writable Properties |
---|---|---|
Analog Input – AI | Reliability | None |
Binary Value – BV | None | Present Value |
Device – DEV | Max Info Frames Max_Master | APDU_Timeout Max_Master Object_Name |
Objects Table:
Object Name | Object Identifier | Object Property |
---|---|---|
Room Temperature | AI 1 | Temperature in Room (°C) |
Room Humidity | AI 2 | Humidity in Room |
Temperature Units* | BV4 | ACTIVE displays temperature in Fahrenhiet INACTIVE |
displays temperature in Celsius
- Preserved during power outages. Applicable to LCD models only.
Device Objects Table:
Object Name| Object Identifier| Object Property|
Description
---|---|---|---
Plant Room Units XXXXXXXX| Vendor_ID + nnn| Object _Identifer (R/W)| Unique
value where nnn initially is the MS/TP address
BACnet Protocol Implementation Conformance Statement
Vendor Name: Veris Industries
Product Name: Plant Room Humidity and Temperature Unit
Product Model: HD2XPXXXX
BACnet Protocol Version: 1
BACnet Protocol Revision: 16
Product Description: Environmental Sensor
BACnet Standardized Device Profile (AnnexL): BACnet Application Specific
Controller (B-ASC)
LCD Operation
The screen displays sensor values for RH, temperature and Celsius/Fahrenheit.
Maximum Power Consumption
Series | LCD | Temp/RH | Max. Power |
---|
HD2 Protocol
| Yes| Yes| 1.5VA @24VAC
No| Yes| 0.8VA @24VAC
China RoHS Compliance Information
Environment-Friendly Use Period (EFUP) Tableb
– Hazardous Substances
Part Name| (Pb)| ➴ (Hg)| (Cd)| (Cr (VI))| (PBB)| (PBDE)
Electronic| X| O| O| O| O| O
This table is made according to SJ/T 11364.
O: indicates that the concentration of hazardous substance in all of the
homogeneous materials for this part is below the limit as stipulated in GB/T
26572.
X: indicates that concentration of hazardous substance in at least one of the
homogeneous materials used for this part is above the limit as stipulated in
GB/T 26572
GEX55253-00
Page 8 of 8
©2023 Veris Industries USA 800.354.8556 or +1.503.598.4564
/support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the
Veris ‘V’
logo are trademarks or registered trademarks of Veris Industries, L.L.C. in
the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their
respective owners.
Documents / Resources
|
VERIS HD2 Protocol Series Duct Mount Humidity
Sensors
[pdf] Installation Guide
HD2P2AL, HD2P2AX, HD2P2AP, HD2 Protocol Series, HD2 Protocol Series Duct Mount
Humidity Sensors, Duct Mount Humidity Sensors, Mount Humidity Sensors,
Humidity Sensors, Sensors
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>