VERIS HD2 Protocol Series Duct Mount Humidity Sensors Installation Guide

June 15, 2024
VERIS

Installation Guide
Humidity

HD2 Protocol Series Duct Mount Humidity Sensors

HD2 Protocol Series
Duct Mount Humidity SensorsVERIS HD2 Protocol Series Duct Mount
Humidity Sensors - icon 1 Veris Industries
Stratford Park 5
Telford TF3 3BL
United Kingdom

**** WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E or CSA Z462.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Replace all devices, doors and covers before turning on power to this equipment.

Failure to follow these instructions can result in death, serious injury or equipment damage.
This product is intended for use in HVAC and building environmental control applications.
It is not intended for direct medical monitoring of patients.
Read and understand these instructions before installing this product.
The installer is responsible for all applicable codes.
If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired. No responsibility is assumed by the manufacturer for any consequences arising out of the use of this material.

Product Overview

HD2 Protocol Series Humidity Sensors provide an ideal solution for measuring relative humidity in a wide range of conditions. All models are equipped with a thin-film capacitive humidity sensor that is easy to replace in the field. A solid state temperature sensor provides high-accuracy measurements.
HD2 is an all-in-one device combining humidity and temperature sensing. Intended for duct mount applications, the device ensures a building’s optimum temperature and humidity levels, resulting in greater energy efficiency.
Each device is an active sensor that converts a humidity or temperature measurement into a BACnet MS/TP or Modbus RTU output.
Different models are available based on application requirements for lower- cost installations.
HD2 is available with an LCD display option on select models (see Product Identification section below).

Product Identification

VERIS HD2 Protocol Series Duct Mount Humidity Sensors - Product
Identification Note: Replaceable RH and temperature modules available to be ordered separately per table below.
Replaceable RH Elements & Temperature and Humidity Calibration Modules

Model

|

Description

---|---
HS1N| Replaceable RH sensor, 1% with NIST certificate
HS2N| Replaceable RH sensor, 2% with NIST certificate
HS2X| Replaceable RH sensor, 2%
TS2| Replaceable temperature module with 2-point calibration certificate
THS2
| Replaceable temperature and humidity module with 2-point calibration certificate

*For temperature transmitter models only.
Note: For instructions on installing replaceable elements, see Z207941, Replacement Humidity and Temperature Sensors Installation Guide.

Specifications

OPERATING / STORAGE ENVIRONMENT


Operating Temp. Range| -35 to 60 °C (-31 to 140 °F)
Operating Humidity Range| 0 to 95% RH (non-condensing)

Storage Temp. Range| -35 to 70 °C (-31 to 158 °F)*
Storage Humidity Range| 0 to 95% RH (non-condensing)
Power Supply| 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
Output| BACnet MS/TP, Modbus RTU
Power Consumption| See Maximum Power Consumption table, page 8
Tube Length| 200 mm
Medium| Neutral gas, air
---|---
Housing Material| Polycarbonate; flammability rating UL 94 V0
Mouting Location| For indoor use only. Not suitable for wet locations.
IP Rating| IP65
Protection Class| Class III

RH SENSOR

HS Sensor| Thin-film capacitive, replaceable
Accuracy**| ±2% from 10 to 80% RH @ 25 °C (77 °F)

±1%, ±2% NIST and 2% replaceable option

Hysteresis| 1.5% typical
Linearity| Included in accuracy specification
Stability| ±1% @ 20°C (68 °F) annually for 2 years
Output Range| 0 to 100% RH
Temperature Coefficient| ±0.1% RH/°C above or below 25 °C (77 °F) typical

TEMPERATURE SENSOR

User Configuration| °C or °F
Sensor Type| Solid state, integrated circuit
Time Constant| Air velocity 1.5 m/s. approx. 72 s; Air velocity 3.0 m/s. approx. 52 s
Accuracy**| ±0.2 °C (±0.4 °F) typical typical at 25 °C
Resolution| 0.1 °C (0.1 °F)
Range| -35 to 60 °C (-31 to 140 °F)

DISPLAY MODELS

LCD Type| Positive display with backlight
Measurement Values

Displayed

| Temperature: °C or °F Humidity: % RH
Display Resolution| Temperature: 0.1 °C or °F Humidity: 0.1% RH

WIRING TERMINALS

Terminal Blocks| Screwless terminal block with spring actuator, 16-24 AWG

WARRANTY

Limited Warranty| 5 years

COMPLIANCE INFORMATION

Agency Approvals| UL 916
European conformance CE: EN61000-6-2, EN61000-6-3, EN61000
Series immunity, EN 61326-1 FCC Part 15 Class A
Green Premium (REACH, RoHS), RoHS 2 (China), RCM (Australia), ICES-003 (Canada), UKCA (UK)

  • Duct mount model with temperature and humidity only. LCD operation from -10 to 60 °C (14 to 140 °F).
    ** Humidity sensor measurement uncertainty should include: accuracy, hysteresis, temperature coefficient and stability.
    *** ±0.5 °C over full operating range.

Dimensions mm (in.)

VERIS HD2 Protocol Series Duct Mount Humidity Sensors -
Dimensions

Installation

  1. Prepare the duct for installation by drilling holes to accommodate the probe tube. Ensure the gasket on the back is depressed to prevent leakage between the product and the duct. Do not over-tighten the screws.    VERIS HD2 Protocol Series Duct Mount Humidity Sensors - Dimensions 1

  2. Ensure the probes are installed in the direction of the air flow. Install the probe in the middle of the duct and away from any restrictions to allow proper air flow.
    VERIS HD2 Protocol Series Duct Mount Humidity Sensors - Dimensions
2

  3. Release the latch on the lid to access the DIP switches and terminal block.
    VERIS HD2 Protocol Series Duct Mount Humidity Sensors - Dimensions
3

  4. Wire the connections per the diagram in the Wiring section below. This device features spring terminals for screwless termination. Open the terminal point by inserting a screwdriver, then insert the wire above. Release the screwdriver to hold the wire in place. Details on wiring and configuration are contained in the next sections of this document.
    VERIS HD2 Protocol Series Duct Mount Humidity Sensors - Dimensions
4

  5. Secure the latch-on cover in the closed position and remove the clear protective mask on the front label of the device.
    VERIS HD2 Protocol Series Duct Mount Humidity Sensors - Dimensions
5

Wiring **

**

NOTICE
PRODUCT DAMAGE DUE TO ELECTRO-STATIC DISCHARGE
Circuit boards and components can be damaged by static electricity or electro- static discharge (ESD). Observe the following electro-static precautions when handling this product and cables and components connected to the product.

  • Keep static-producing material such as plastic, upholstery, carpeting, etc. out of the immediate work area
  • Store the product in ESD-protective packaging when it is not installed in the panel
  • When handling the product or a conductive cable/ESD-sensitive component connected to the product, wear a conductive wrist strap connected to ground through a minimum of 1 MΩ resistance
  • Do not touch exposed conductors and component leads with skin or clothing

Failure to follow these instructions can result in equipment damage.
NOTICE
INACCURATE READINGS

  • Do not run wiring in the same conduit as AC power wiring. Close proximity to AC power may influence accuracy.

Failure to follow these instructions can result in reduced accuracy.
Wiring DiagramVERIS HD2 Protocol Series Duct Mount Humidity Sensors -
Wiring Diagram

Configuration

Address Configuration
Each device on a single network must have a unique address. Set the DIP switch labeled “ADDRESS” to assign a unique address before the device is connected to the network. If an address is selected that conflicts with another device, neither device will be able to communicate.
Address the device as any whole number between and including 1 to 127. Note that zero is not a valid address for Modbus; zero is a valid address for BACnet. Positions 1 through 7 of the “ADDRESS” DIP switch designate the address. Position 8 toggles between the Modbus and BACnet communication protocols, as shown in the diagram below. This is the right bank of DIP switches on the sensor.![VERIS HD2 Protocol Series Duct Mount Humidity Sensors

  • Wiring Diagram 1](https://manuals.plus/wp-content/uploads/2023/12/VERIS-HD2 -Protocol-Series-Duct-Mount-Humidity-Sensors-Wiring-Diagram-1.jpg)To set an address using the DIP switch, simply add the values of any switches that are in the ON position. For example, an address of 73 is set as shown in the diagram below.VERIS HD2 Protocol Series Duct Mount Humidity Sensors - Wiring
Diagram 2Position number 1 has an ON value of 1, position number 4 has an ON value of 8 and position number 7 has an ON value of 64 (1 + 8 + 64 = 73).
    Communications Configuration
    See the Installation section, Step 3 for the location of the DIP switches. The following parameters are configurable:

    • Parity (Modbus only): None, Odd, None1 (one stop bit), Even
    • Baud rate: 9600, 19200, 38400, 57600 (Modbus), 76800 (BACnet)VERIS HD2 Protocol Series Duct Mount Humidity Sensors - Wiring Diagram 3

Example: No Parity, 19200 Baud

1 2 3 4 5 6 7 8
off off on off off off off off
None 19200 Baud Unused

Modbus Point Map
Function Codes:

Function Code Function
03 Read holding (RW) registers
04 Read input (RO) registers
06 Write single register*
16 Write multiple registers
01 Read coils
05 Write single coil
15 Write multiple coils

* Not supported.
All of these values correspond to BACnet objects with the same name. See the BACnet Conformance Statement on page 8 for their definitions.
Note that an attempt to write to “read only” holding registers will give an error and the entire write command will not be executed even if writing to read/write locations were also requested. Exception code 2 is given in this case. “Preserved” means the values is maintained through power outages.
32-Bit Input Registers (Read Only):

Register Description
1 Temperature reading in IEEE 32-bit floating point (°C)
3 Humidity reading in IEEE 32-bit floating point
9-41 Model (numeric representation of ASCII characters)
42-45 Serial number (numeric representation of ASCII characters)

32-Bit Holding Registers (Read/Write):

Register Description
7* Device name (numeric representation of ASCII characters)

*Preserved during power outages.
Coils (Read/Write):

Register Description
5* Temperature (°C)

*Preserved during power outages.

BACnet Descriptions

Note: In the tables below, all properties are read-only unless otherwise noted. “Preserved” means the value is maintained through power outages.
Present_Value Range Restrictions:

Object Name Minimum Value Maximum Value
DEV – Object_Name 1 Character 65 Characters
Device_Instance 0 4,194,302

Standard Object Types Supported:

Object Type Supported Optional Properties Writable Properties
Analog Input – AI Reliability None
Binary Value – BV None Present Value
Device – DEV Max Info Frames Max_Master APDU_Timeout Max_Master Object_Name

Objects Table:

Object Name Object Identifier Object Property
Room Temperature AI 1 Temperature in Room (°C)
Room Humidity AI 2 Humidity in Room
Temperature Units* BV4 ACTIVE displays temperature in Fahrenhiet INACTIVE

displays temperature in Celsius

  • Preserved during power outages. Applicable to LCD models only.
    Device Objects Table:

Object Name| Object Identifier| Object Property| Description
---|---|---|---
Plant Room Units XXXXXXXX| Vendor_ID + nnn| Object _Identifer (R/W)| Unique value where nnn initially is the MS/TP address

BACnet Protocol Implementation Conformance Statement
Vendor Name: Veris Industries
Product Name: Plant Room Humidity and Temperature Unit
Product Model: HD2XPXXXX
BACnet Protocol Version: 1
BACnet Protocol Revision: 16
Product Description: Environmental Sensor
BACnet Standardized Device Profile (AnnexL): BACnet Application Specific Controller (B-ASC)

LCD Operation

The screen displays sensor values for RH, temperature and Celsius/Fahrenheit.

Maximum Power Consumption

Series LCD Temp/RH Max. Power

HD2 Protocol

| Yes| Yes| 1.5VA @24VAC
No| Yes| 0.8VA @24VAC

China RoHS Compliance Information

Environment-Friendly Use Period (EFUP) Tableb

– Hazardous Substances

Part Name|  (Pb)| ➴ (Hg)| (Cd)|  (Cr (VI))| (PBB)| (PBDE)
Electronic| X| O| O| O| O| O

This table is made according to SJ/T 11364.
O: indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below the limit as stipulated in GB/T 26572.
X: indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part is above the limit as stipulated in GB/T 26572

GEX55253-00
Page 8 of 8
©2023 Veris Industries USA 800.354.8556 or +1.503.598.4564 /support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’
logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Documents / Resources

| VERIS HD2 Protocol Series Duct Mount Humidity Sensors [pdf] Installation Guide
HD2P2AL, HD2P2AX, HD2P2AP, HD2 Protocol Series, HD2 Protocol Series Duct Mount Humidity Sensors, Duct Mount Humidity Sensors, Mount Humidity Sensors, Humidity Sensors, Sensors
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals