SENECA S203TA-D Advanced Three Phase Network Analyzer with Display Instruction Manual
- September 25, 2024
- SENECA
Table of Contents
- S203TA-D Advanced Three Phase Network Analyzer with Display
- Specifications
- Product Usage Instructions
- Installation
- Data Communication Setup
- Analog Output Configuration
- Q: Can the S203TA-D measure single-phase electrical
- Q: What is the communication protocol supported by the
- Q: How do I ensure accurate measurements with the
S203TA-D Advanced Three Phase Network Analyzer with Display
“`html
Specifications
- Model: S203TA-D
- Communication Port: RS485, USB
- Voltage Input: Up to 600 Vac, frequency 50 or 60 Hz
- Current Input: Rated range 5 A, Max Crest Factor 3
- Network Frequency: 50 or 60 Hz
- Voltmeter Precision: 0.2%
- Amperometer Precision: 0.2%
- Wattmeter Precision: 0.2%
- Analog Output: 0-10 Vdc, 0-5 Vdc, 0-20 mA, 4-20 mA
- Installation Category: III (up to 300 V), II (up to 600 V)
- Temperature Range: 30-90%
- Storage Temperature: International protection
Product Usage Instructions
Installation
1. Ensure the power source meets the requirements specified in
the manual.
2. Connect the voltage and current inputs to the appropriate
terminals with correct polarity.
3. Secure the connections using screw terminals with the
specified pitch.
Data Communication Setup
1. Configure the communication port settings as follows:
- Baud Rate: 1200-115200 baud
- Protocol: Modbus RTU
Analog Output Configuration
1. Set the desired output range (0-10 Vdc, 0-5 Vdc, 0-20 mA, or
4-20 mA) based on your requirements.
2. Ensure the load resistance is within the specified limits for
accurate output.
Frequently Asked Questions
Q: Can the S203TA-D measure single-phase electrical
quantities?
A: Yes, the instrument can measure single-phase electrical
quantities in addition to three-phase measurements.
Q: What is the communication protocol supported by the
device?
A: The device supports Modbus RTU protocol over RS485
communication port.
Q: How do I ensure accurate measurements with the
S203TA-D?
A: Make sure the cable length is compatible with the current
transformer and that the total resistance meets the specified
criteria.
“`
S SENECA
SSeerriiee ZZ–PPCC
EN
SS220033TTAA–DD
Advanced Three-phase
Network Analyzer with display
Installation Manual
CCoonntteennttss:: — GGeenneerraall Ssppeecciiffiiccaattiioonnss —
TTeecchhnniiccaall Sfepaetucirfeicsations — IFnusntacltliaotnioinngRules —
EElleeccttrriiccaall cqounannetictiteiosns — MEloedcbtruicsacl
ocnonnencetciotinonrsules — DLEIPD-sswsiitgcnhaelslinsgesttings —
DSiegriitaall iinntpeurftasce — LCeadsseSaingdnaslclirnegws terminal numbers —
FFarocntotrpyaSneetltings – Display programming
SENECA s.r.l. Via Austria, 26 35127 PADOVA ITALY Tel. +39.049.8705355 – 8705359 – Fax +39.049.8706287 For manual and configuration softwares, please see: www.seneca.it
This document is property of SENECA srl. Duplication and reproduction are forbidden, if not authorized. Contents of the present documentation refers to products and technologies described in it. All technical data contained in the document may be modified without prior notice Content of this documentation is subject to periodical revision.
MI002898-E
ENGLISH 1/8
GENERAL SPECIFICATIONS
Model S203TA-D is a complete three-phase network analyzer, with display,
suited for u s e with up to 600Vac voltage range, and max current equal to 5A
connected to the inputs.The instrument provides all the following electrical
measurable quantities: Vrms, Irms, Watt,
VAR, VA, Frequency, Cos and Active Energy. All measurements given above
(except frequency) are available both single-phase and three-
phase.Measurements are read through serial communication both in floating
point and normalized format (except Frequency and Active Energy).It is
possible the analog retransmission of any Vrms, Irms,
Watt and Cos quantity either single phase or three-phase, or any phase chosen
(by specific display or MODBUS registry). The module is also distinguished by:
Communication configurability through software. RS485 serial communication
with MODBUS-RTU protocol, maximum 32 nodes. Easy-wiring of power supply and
serial bus by means of the bus housed in the DIN rail. High precision: 0,2 %
class. Protection against ESD discharge up to 4 kV. Measure input insulation:
4000 Vac towards all the other circuits. Insulation between communication and
power supply: 1500Vac. Insulation between retransmitted output and power
supply: 1500Vac. Analog output signal settable in voltage or current. Digital
output for energy counter Possibility for connection and management by
external CTs with 5A output. All kind of insertion possible: single phase,
Aron, four wires Possibility to compensate errors caused by frequency change
in places where network
frequency is not stable (frequency changes > 30 mHz).
TECHNICAL FEATURES
Communication port
RS485
Baud rate: 1200..115200 baud. Protocol: Modbus RTU
USB
Voltage input Current input
Class/Base Precision (1)
Max Resistance of each CT’s secondary wire :
Mini-USB, for programming (software Easy)
Input
Up to 600 Vac, frequency 50 or 60 Hz Rated range :5 A Max Crest Factor: 3.
Continuous Max Current: 15 A
Network Frequency: 50 or 60 Hz.Voltmeter : 0,2 %. Amperometer : 0,2 %.
Wattmeter : 0,2 %.
To ensure the accuracy on nominal measure, cable lenght must be compatible
with the current transformer. If Rtotal=sum of the resistance of the wire
going (from CT to S203TA-D) and back (from S203TA-D to CT), then Rtotal*I2<
(CT nominal power)
(1) Precisions are given in the following range: Vrms: 40..600 Vac; Cos
(without error due to external CT)
Irms: 0,4-100% Iprimary of TA
Digital output for energy counter
Type
Passive (it has to be powered on), no protection for short circuit
Range
50 mA / 28 V
MI002898-E
ENGLISH 2/8
Voltage Output Current Output Transmission error Response time Thermal
stability
Voltage Consumption
Installation category
Analog Output
0..10 Vdc, 0..5 Vdc, Min. load resistance: 2 k 0..20 mA, 4..20 mA, Max load
resistance: 500 0,1 % (max range). 0,4 s (10%..90%) 100 ppm / K
Other Specifications
11 ..40 VDC or 19 ..28 VAC @ 50 ..60 Hz
Max 2,5 W
Installation
III (up to 300 V), II (up to 600 V)
Temperature Humidity
Environmental conditions
-10 ..+65°C
30 ..90%
Storage temperature
International protection
-20 ..+85°C IP20
Connections
Connections
Screw terminals, 5,08 / 7,5 pitch
Dimensions / case / display
Dimensions Case Display
105 x 89 x 60 mm Plastic UL 94 VO, grey color. Front LCD 2 lines x 16 characters alphanumeric (backlighted)
Isolations
Insulation voltage
4000 Vac between the input and all the other circuits. 1500 Vac between power
supply and communication. 1500 Vac between power supply and analog output.
Standards
Reference standards :
EN61000-6-4 (electromagnetic emission, industrial environment).
EN61000-6-2 (electromagnetic immunity, industrial environment).
EN61010-1 (safety)
MI002898-E
ENGLISH 3/8
OPERATING LOGIC
The module measures the following electrical quantities: Vrms, Irms, Watt,
VAR, VA, Frequency, Cos and Active Energy, and provides the values in the
corresponding MODBUS registers. In three-phase environments, measurements
given above corresponding to any phase are available, other than the three-
phase value (except the frequency). These measurements are rendered in both
floating point and normalized format (except Frequency and Active energy)
between 0..+10000 (-10000 ..+10000 for VAR e Cos). Active energy value is
stored in memory and when the instrument is switched off, the last value
before switching is kept in memory. The module output can transmit one of the
following quantities: Vrms, Irms, Watt, cos as either a current or voltage
value. If the instrument is set for three-phase measurements, it transmits
automatically the three-phase value of the selected measurement. However, via
MODBUS register, the user can choose to transmit the measurement corresponding
to any phase: A, B, C. The user can set through MODBUS the values MIN and MAX
of the measurement to transmit corresponding to 0% and 100% of the analog
output. For example, if the signal is transmitted as current 4..20 mA and the
quantity to transmit is voltage Vrms in the 10..300 V range, (therefore
MIN=10, MAX=300), then if Vrms measured is 10V, analog output will be 4mA,
while if Vrms=300V output will be 20mA. In the intermediate points the
behaviour is linear. The analog output values saturate at approximately 11 V
for voltage output and at 22mA for current output (analog output clamped at
110 %). If network frequency oscillates more than 30 mHz from rated values (50
o 60 Hz), it’s possibile to compensate errors on measurements of Power and
Energy caused by these variations. This option is selectable via MODBUS
register. Vrms and Irms measurements are not influenced by these variations.
When the module is switched on, the appropriate setting coefficients are
measured (depending on the choice of 50 or 60 Hz frequency). All the settings
made will be automatically loaded when the module is reset.
NOTE: without load connected to the S203TA-D, only the (displayed) voltage and
frequency assume a corrected value.
MI002898-E
ENGLISH 4/8
ELECTRICAL QUANTITIES
Measured quantity of S203TA-D
ELECTRICAL QUANTITY
SYMBOLS MEASURED CALCULATED
USED
VALUES
VALUES
Root-mean squared voltage (Vrms) VA, VB, VC
EQUATION
Mean three phase voltage
V
(VA+VB+VC)/3
Root-mean squared current (Irms) IA, IB, IC
Mean three phase current
I
Active power (phase) Total three phase active power
PA, PB, PC P
Reactive power (phase)
QA, QB, QC
(IA+IB+IC)/3
PA+PB+PC
(SA,B,C)2-(PA,B,C)2
Total three phase reactive power
Q
QA+QB+QC
Apparent power (phase)
SA, SB, SC
Total three phase apparent power
S
cos(phase)
cosfiA, cosfiB, cosfiC
Total three-phase cos
cosfi
V *I A,B,C A,B,C
SA+SB+SC
P / S A,B,C
A,B,C
P / S
Frequency
Hz
Active Energy (phase) Total three-phase active energy
EA, EB, EC E
EA+EB+EC
Retransmission range
Electrical Quantity V rms
I rms Active Power Reactive Power
Apparent Power Cos
Frequency
Measurement Range 0..600 Vac
0..I primary of CT (0..I primary of CT600)W
(0..I primary of CT600)VAR (0..I primary of CT*600)VA
0..1 40..70 Hz
MI002898-E
ENGLISH 5/8
ELECTRIC CONNECTIONS
POWER SUPPLY
26 25
11 ÷ 40 VDC 19 ÷ 28 VAC
2.5 W
RS 485
33
B
32
A
31
GND
There is no insulation between RS485 and the analog output
13 14 15 16 17 18 19 20 21 22
SINGLE PHASE INPUT
VG
A N
TA ZL
13 14 15 16 17 18 19 20 21 22
ARON Three-Phase without Neutral
A VG B
C
TA
ZL
TA 13 14 15 16 17 18 19 20 21 22
3 WIRES Three-Phase without Neutral
A
VG B NC
TA
TA
ZL
TA
13 14 15 16 17 18 19 20 21 22
4 WIRES Three-Phase
A VG B
TA TA
ZL
with Neutral
NC
TA
Note: You can’t connect the secondary of any CTs to the Earth. Terminals 14, 16 18 and 22 are internally connected. 19 20 21 22 18 17 16 15 14 13
SINGLE PHASE WITHOUT CT
A VG
N
5 Arms Max
ZL
Note: PAY ATTENTION to the different terminals position from the other schematics
MI002898-E
ENGLISH 6/8
ANALOG OUTPUT
The module provides a programmable, analog output in voltage (0..10 Vdc) or active and
passive current (0..20 mA). We recommend using shielded cables for the electric
connections.
External power supply
Voltage
35
Active current (1) 36
current (2) 36
V
A
34
35
34
There is no insulation between RS485 and the analog output.
DIGITAL OUTPUT The module has a digital output: each pulse corresponds to a
given number of increments about to the energy counter. Imax=V/R=50 mA,
Vmax=28V. For more informations, see the S203TA-D display settings manual.
I V
R
29 Digital output
30
SegnalaLziEoDnes tsriagmnaitlelinLgEsD
LED PWR
ERR TX RX
STATUS
ON (GREEN)
ON (YELLOW)
Blinking (RED)
Blinking (RED)
LEDs signallings The module is power on
At least one of the active phases’ voltage is less than 40 Vac Data are being
transmitted through the RS485 comm. port Data are being received through the
RS485 comm. port
SERIAL INTERFACE
For detailed information on RS485 serial interface, consult the documentation
provided by the website www.seneca.it, in the section Prodotti/Serie
Z-PC/MODBUS TUTORIAL.
SegnalaziPornoegrtraammmitiengLED
The communication parameters have the following default values::
baudrate=38400, no parity, bit number=8, bit stop=1. These values can be
modified by display or Modbus protocol. To program the device, download the
free software Easy Setup from the website www.seneca.it.
MI002898-E
ENGLISH 7/8
CASE AND SCREW TERMINAL NUMBERS
36 35 34 33 32 31 30 29 28
26 25 22 21 20 19
For communication debugging, remove the terminals cover to see the internal LEDs.
S SENECA S203TA-D
TX ERR
RX PWR
S203TA-D
FRONT PANEL
10 11 12 13 14 15 16 17 18
A)MEASURE CONFIG
ESC
OK MENÙ
DISPLAY PROGRAMMING
For detailed information on display programming, consult the documentation
provided by the website www.seneca.it.
Disposal of Electrical & Electronic Equipment (Applicable throughout the
European Union and other European countries with separate collections
programs). This symbol, found on your producr or on its packaging, indicates
that this product should not be treated as household waste when you wish to
dispose of it. Instead, it should be handed over to an applicable collection
point for the recycling of electrical & electronic equipment. By ensuring this
product is didposed of correctly, you will help prevent potential negative
consequences to the environment and human health, which could otherwise be
caused by inappropriate disposal of this product. The recycling of materials
will help to conserve natural resources. For more detailed information about
the recycling of the product, please contact your local city office, waste
disposal service of the retail store where you purchased this product.
MI002898-E