Klima 825201 Intelligent Control Wi-Fi Underfloor Heating Thermostat User Manual

September 21, 2024
klima

825201 Intelligent Control Wi-Fi Underfloor Heating Thermostat

“`html

Product Information:

Specifications:

  • Supply voltage: 85-265 VAC 50/60 Hz
  • Load: max.16 A (resistive load)
  • Setpoint range: Temperature range
  • Cover: Approvals
  • Floor sensor type

Product Usage Instructions:

Installation:

  1. Check if the power is off.

  2. Remove the display frame by pushing a non-sharp instrument in
    the square hole underneath the thermostat.

  3. Remove the display frame and cover frame.

  4. Position the thermostat and install it onto the back box (not
    supplied).

  5. Place the display frame back into position by pushing it
    softly.

Operation and LED:

Instructions on system operation, standard or custom settings,
sensor fault, and more.

Start up wizard:

  1. Follow the steps to set up the thermostat using the start-up
    wizard.

  2. Adjust settings as needed for your preferences.

Mode Selection:

  1. Automatic mode: Thermostat adjusts temperature based on weekly
    program.

  2. Temporary temperature: Override automatic program until next
    event.

  3. Manual mode: Thermostat runs continuously at set
    temperature.

  4. OFF: Turn off all functions, reactivate by selecting mode.

  5. Timer: Set off period for holidays, return to standard settings
    after.

  6. Slow heating: Gradually raise floor temperature over 20 days
    for new floors.

Frequently Asked Questions (FAQ):

Q: Can I replace the outer frame of the thermostat?

A: Yes, according to user preference, the circular and square
outer frame can be replaced. Ensure to use compatible frames.

Q: How do I stop or restart the slow start-up mode?

A: To stop or restart the slow start-up mode, press the left
button on the thermostat.

“`

USER MANUAL
USER MMoAdNelU: MAILC2+ WIFI
Installation
1.Check if the power is off. Remove the display frame by pushing a non sharp instrument (for example the point of a ballpoint pen) carefully in the square hole underneath the thermostat.
2.$POOFDUJPOTDIFEVMF: L/N lead : Connect the power cord using the terminal block. L1/N1 lead : Use a terminal block to connect the load line(Max 16A). S1/COM/ : Connect the floor sensor. Pilot : Connect the pilot to L when the pilot wire function needs to be enabled. WARNINGS: 1Disconnect the main power supply before wiring. Installation needs to be done by a qualified electrician in accordance with all current wiring and building regulations. 2.Electric floor heating cable/ mat must be in accordance with the supply voltage.The terminals are designed to handle a cross-section of wire measuring 12-22AWG.
3.The display frame and the cover frame can be removed. Position the thermostat and install onto the back box (not supplied). Place the display frame back into position by pushing it softly.

POWER

01

02

04

03

Note: According to user preference, the circular and square outer frame can be replaced.
05

Supply voltage:
Load:
Setpoint range: Temperature range: Cover: Approvals: Floor sensor type:

85-265 VAC 50/60 Hz
max.16 A (resistive load)
+5 to +40°C / +41 to +104°F +5 to +45°C / +41 to +113°F IP21 CE/UKCA NTC B=3740 12k

Operation and LED
,FZTPQFSBUJPO
.JEEMFCVUUPOT “EKVTUNFOUVQBOEEPXOPS
5PTDSPMMUISPVHITFUUJOHT

º

-FGUCVUUPO 1VTISJHIUCVUUPOJONBJOTDSFFOUPHPTUSBJHIUUP.FOVTFUUJOHT
$POGJSNJOHBDIPJDF 4FMFDUBOPQUJPO

3JHIUCVUUPO 1VTIMFGUCVUUPOJONBJOTDSFFOUPHPTUSB JHIUUP.PEFGVODUJPOT
5PHFUCBDLUPMBTUTDSFFOPSNBJOTDSFFO ºPS9
“MXBZTHPCBDLUPUIFNBJOTDSFFOBGUFSNBLJOHDIBOHFT

&YQMBOBUJPOPG-&%DPMPVSTTJHOBMT

3FE

Heating

(SFFO

System operationstandard or Costum)

3FEMJHIUGMBTIJOHPOBOEPGGSensor fault

%BUF
.FBTVSFE5FNQ .PEF
.PEFHFUCBDL

5JNF
.FOV .FOV$POGJSN -&%

6Q%PXO4DSPMM

Start up wizard

1

-BOHVBHF

2 6OJUT

NBLFZPVSMBOHVBHFDIPJDF 5IJTJTUIFGJSTURVFTUJPOJOUIF TUBSUVQNFOV

$MPDL DIPPTFPSIPVSDMPDL UJNF BNQN

5FNQFSBUVSF DIPPTF°$PS°’TDBMF

3

%BUF

ZFBS QSPHSBNUIFDVSSFOUZFBS

NPOUI QSPHSBNUIFDVSSFOUNPOUI

EBZOVNCFS QSPHSBNUIFDVSSFOUEBZ

4

5JNF

QSPHSBNUJNF QSPHSBNUIFBDUVBMDMPDLUJNF

5 *OUFMMJHFODF
5IJTGVODUJPOFOBCMFTUIF UIFSNPTUBUUPDBMDVMBUFXIFO JUOFFETUPTXJUDIPOTPUIBU UIFSFRVJSFEUFNQFSBUVSFJT SFBDIFEBUUIFTFUUJNF

6 )FBUJOHTZTUFN
‘MPPSIFBUJOHPSEJGGFSFOU IFBUJOHTZTUFN*GZPVDIPPTF BEJGGFSFOUIFBUJOHTZTUFNUIF RVFTUJPOXJMMCFXhFUIFSUIF TZTUFNOFFETUPGVODUJPOPO UIFJOUFSOBMSPPNTFOTPSPS FYUFSOBMTFOTPS

7 4VSGBDFNBUFSJBM
GZPVDIPPTFGMPPSIFBUJOH 8PPEPSPUIFSGZPVDIPPTF PUIFS
UIFRVFTUJPOJTBTLFEJG UIFSFJTBGMPPSTFOTPSJOTUBMMFE

8 5FNQUPDPOUSPM
‘MPPSPSSPPNTFOTPS *GZPVDIPPTFGMPPSIFBUJOH
XFBEWJTFZPVUPDPOUSPMUIF GMPPSUFNQFSBUVSFCZVTJOH UIFGMPPSTFOTPS

9

4VNNBSZ

$POUBJOJOHUIFDVSSFOU TFUUJOHT

10 5FNQFSBUVSF
1SPHSBNUIFDPNGPSUUFNQ FSBUVSFPGZPVSDIPJDFGPSB IFBUJOHQFSJPE4UBOEBSE UFNQFSBUVSFGPSBoEJGGFSFOU IFBUJOHTZTUFNJTQSPHSBN NFEBUEFHSFF$FMTJVTBOE EFHSFF$FMDJVTGPSBGMPPS IFBUJOHTZTUFN

11 0WFSWJFXXJ[BSE
$POUBJOJOHUIFTFMFDUFE IFBUJOHQFSJPETBDDPSEJOHUIF TUBOEBSEQSPHSBN

12 4MPXIFBUJOH
*UJTQPTTJCMFUPDIPPTFUIJT PQUJPO 3FG.PEFTFMFDUJPO QPJOUTMPXTUBSUVQ

Mode selection
1.Automatic mode:
According to the weekly program, the thermostat automatically adjusts the set temperature operation.

2.Temporary temperature:
To temporarily override the temperature in the automatic program. The override will operate until the next automatic event.
3.Manual mode:
The thermostat runs continuously according to the set temperature.
4.OFF: Manually turn off all functions of the thermostat When you want to reactivate the thermostat, just select the mode you want.
5.Anti-frost mode: Range is set from 41°F to 59°F(5°C -15°C in this mode. This mode is used when you want to keep your room at a lower temperature when you are on vacation.
6.Timer:
Use this mode when you are on holidays etc.The thermostat will be off for the chosen period. After this period, the thermostat will return to the standard or the custom time settings.
7.Slow heating: To be used for new floors only. The thermostat will slowly raise the temperature of the floor over a 20 day period. After this period the thermostat automatically starts the standard or the custom time programme. If you need to stop or restart the slow start up mode, press the left button.

Menu selection
1.Temperature settings: You can change the programmed temperature (comfort or set back ). Attention: In the case of floor heating, it is not necessary to program the setback temperature.The setback temperature is controlled by the thermostat automatically.

2.Programming: The comfort temperature and times can be changed in this menu. Standard program:

.POEBZ4VOEBZ

1FSJPE 1FSJPE

¥ ¥

Custom week program: Push the button to confirm the function program’. You enter the screen with the standard settings schedule. Press button,standard’ appears on the display. Press button,standard’ is selected. Press button selectcustom’. confirm this with button. Press / button return to the screen of programmed times. Now you can confirm the symbol by pushing the right button. You can adjust one or two periods a day. If you want to program the same time periods on different days, use the easy copy and paste function.

3.Consumption: The thermostat calculates the average time it has been switched on allowing you to monitor your energy consumption. The total switched on time is by percentage (%) shown over the last 30 and 365 days. Calculate consumption: 30 days: 24 hours x 30 days x total installed power x % = energy consumption 365 days: 24 hours x 365 days x total installed power x % = energy consumption Example: The thermostat gives a percentage of 26% over 30days. The power installed in the floor is 700 Watt. 24 hours x 30 days = 720 hours. 720 hours x 0.7 kW = 504 kWh 26% of 504 kWh = 131 kWh.
4.Child lock: The thermostat is locked with this function.Mode and menu settings cannot be used.To switch the child lock function on or off, push the right key and hold it for a few seconds. When the child lock is switched on, a padlock appears on the display.

5.Information: Gives information about the current software and hardware version of the thermostat.

6.Settings:
With this function you can change settings related with the operating of the thermostat.The following options can be changed: – Date and time: Thermostat will change summer and winter clock change
automatically. – Language: English. – Contrast: Display contrast: 0-20. – Brightness: Display brightness: 0-10. – Back light delay: Can be adjusted from 0 till 250 seconds. (0 =always on) – LED info: When it is switched on, it indicates the current heating period.. – Temp unit:Choose Celsius or Fahrenheit.
7.Advanced functions: The thermostat provides advanced settings to suit a range of special situations which are normally set by a technician during initial installation. – Heating system.
1. Type of heating system (floor heating or other heating) 2. Surface material: wood or other 3. Temp.to control: floor or room These settings can also be changed using the start up wizard. – Calibration. A correction can be made here on the temperature in the display and the measured room temperature. Consult your supplier before changing calibration setting.Setpoint range: ±5°C. – Intelligence. Switch the intelligent function on or off. The thermostat has a self thinking and adaptive system. This function enables the thermostat to calculate when it needs to switch on so that the required temperature is reached at the set time. (i.e. if the set time is 08:00, the thermostat will switch on earlier so that the set temperature is reached at 08:00). – Difference. Example: Set the value to 1°C. The difference between switch on and off period during heating time. The thermostat starts when the room temperature is 1°C lower than set temperature and stops when the room temperature is 1°C higher than the set temperature. – Pilot wire. Can be used to operate the thermostat through an external source.This can be a central source or a smart home system. This function can be turned on or off. – Sensor type. Gives the possibility to adjust the sensor value. This is not required in a standard situation. Consult your supplier before changing sensor type. – Open window. This function only works when room sensor or both sensors is selected. The thermostat with this function will shut off automatically for 15 min when the window opens, as it can detect that the room temp plummets. – Factory defaults. All parameters are restored to default value.You need to right-click and hold down for 5 seconds to perform this operation

Wifi Connections
Download the app Compatible with IOS and Android.
Connection method

1
4DBOUIF23DPEFPS EPXOMPBEGSPN “11TUPSF (PPHMF1MBZ

2
3FHJTUFSBOEMPHJOXJUI NPCJMFOVNCFSFNBJM
BEESFTTJOUIF”11

3
$MJDLm”EE%FWJDFnPS mnPOUIFUPQSJHIUUP
BEEEFWJDF

“UUFOUJPO1MFBTFSFBEBOE BHSFFm1SJWBDZ1PMJDZBOE4FSWJDF BHSFFNFOUnCFGPSFSFHJTUSBUJPO

If you are in the process of networking, the device cannot be discovered. You can press “+” and “-” buttons on the thermostat at the same time to switch the wifi connection mode. When the following interface appears, press “set” to switch between the two modes. If the device is connected to wifi, use this setting to disconnect the device as well.
Smart wifi WiFi icon on thermostat is blinking rapidly. AP wifi WiFi icon on thermostat is blinking slowly.

Explanation of text / Symbols
Comfort period Limited floor temperature achieved (28 ºC) Child lock activated Electrical use for heating

4
$MJDLm8J’JUIFSNPTUBU

5
0QFSBUFUIFSNPTUBU *GUIF8J’JJDPOGMBTIFT
RVJDLMZ
DMJDL m1SFTTUPDPOOFDUn

14:22

ET-5A

6
&OUFS8JGJQBTTXPSE
BOEDMJDLm$POGJSNn

Set back: standard set back temperature (pilot wire)

Set back: anti frost + 7 degree Celsius( pilot wire)
Set back mode The setback mode is when the thermostat sets back’ to a lower temperature during the off time periods. This is the most economical and efficient way to achieve the best energy consumption. Floor temperature limiter Some floor coverings must be limited at a certain maximum temperature (for example wooden floors). When the optionWooden’ is selected (in the start up wizard), the floor will not exceed 28ºC.

7
*GUIFEFWJDFJTBEEFE TVDDFTTGVMMZ
ZPVDBO
DIBOHFUIFEFWJDF OBNFBOETFUSFHJPO
5IFO
DMJDLm%POFn

8
:PVDBODIFDLUIF BDUVBMUFNQFSBUVSF BOETFUUFNQFSBUVSF FUDPOUIFDPOUSPM
JOUFSGBDF

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals