Klima SF300 Digital Thermostat Instruction Manual

June 3, 2024
klima

Klima SF300 Digital Thermostat

Read this manual carefully and keep it with other warranty documents. Connection must be carried out by a qualified installer in accordance with local regulations. Before installing or disassembling the thermostat, always switch off the electricity in the meter cupboard. This thermostat can be installed in a single flush- mounting box 50 mm deep, according to standard DIN formats

Technical details

  • Power 90-240Vac 60/60Hz
  • Max. Load 16A/250V
  • Floor sensor type 10k NTC 1%
  • Temp. range 5oC-35oC
  • Accuracy 0.5oC
  • Cover IP21
  • Warranty 2 years

Wiring diagram

  • 1 Power supply (Line)
  • 2 Power supply (Neutral)
  • 3 Heating cable wire 1*
  • 4 Heating cable wire 2*
  • 5 N/A
  • 6-7 Floor sensor connection

Order Heating wire 1 and 2 does not apply.
EARTH : Connect the earth of the heating cable and the earth of the power supply outside the thermostat

Display icon explainantion

Klima-SF300-Digital-Thermostat-FIG-
\(3\)

Time setting

(Thermostat on) Long press o to enter options

  • Press▲, choose 0101 and press o to enter
  • Press▼or▲to set minutes
  • Press to confirm and enter hour setting
  • Press▼or▲to set hours
  • Press to confirm
  • Press▼or▲to set week day (Monday = 1, Sunday = 7)
  • Press to confirm

Choose mode
Press to switch between Auto Mode or Manual mode.

Programming

(Auto Mode)

(Thermostat on) Long press to enter options

  • press▲, choose 0202 and then  to enter programming
  • Press  to choose hours, min. and temp. (with▼or▲and )

There are 3 periods (6 setpoints) per day. See standard scedule for reference:

Klima-SF300-Digital-Thermostat-FIG- \(4\)

Holiday Mode

(Thermostat on) Long press o to enter options

  • Press▲, choose 0303 and press  to enter
  • Press▼or▲to set days
  • Press  to confirm and enter temperature setting
  • Press▼or▲to set temperature
  • Press  to confirm

Sensor error

When an “E1” or “E2” code is shown the sensor is wrongly connected or broken. The thermostat will stop heating until the sensor is connected correctly or replaced.

Advanced settings

WARNING : Changing advanced settings may cause undesired results. Please consult your installer before entering this menu!

  • Press the on/off button once, long press  to enter Advanced menu A.
  • Press  to choose between A1 to AE. Press▼or▲to adjust
    No.| Item| Parameters| Default
    ---|---|---|---
    A1| Measured temp. calibration| -9oC to +9oC| 0.5oC
    A2| Differential| 0.5oC to 2.5oC| 1oC
    A3| Key lock| 0: Half lock

1: Full lock

| 0
A4| Power with memory function| 0: Power with memory function

1: Shutdown power after power off 2: Shutdown power after power on

| 0
A5| Backlight time| 5 to 30 seconds| 10 sec
A6| Programmable| 0: 5+2 (Week 1-5 and weekend 6-7)

1: 6+1 (Week 1-6 and sunday 7)

2: 7 (Week 1-7)

| 0
A7| Lowest temp. setting| 1 – 10oC| 5oC
A8| Highest temp.setting| 20-70oC| 35oC
A9| Low temp.protection| 1: 1oC – 10oC

Function off: > 10oC Display (—- )

| 5oC
AA| High temp.protection| 1: 35oC-70oC

2: Function off: < 35oC Display (—- )

| 45oC
AB| High temp. protection differential| 1-9| 2
AC| Running temp. of open window function| 1: 10 – 20oC,

2: Function off: < 10oC Display (—- )

| 15oC
AD| Running time of open window function| 10 – 20 min| 10
AE| Reset to factory settings| Long press o until display goes blank| –

www.klima.co.uk