Lochinvar 60 – 119 Storage Tank 119 gal Instruction Manual
- September 19, 2024
- Lochinvar
Table of Contents
60 – 119 Storage Tank 119 gal
Product Information
Specifications
- Model Numbers: SJS060, SJS080, SJS119
- Hot Water Outlet Temperature: See table below
- Recirculation Tappings: 1-1/2 NPT and 2 NPT
- Sensor Well: Included
Product Usage Instructions
General Information
This manual covers installation, operation, and maintenance
procedures for the Lochinvar SJS Storage Tank. It is essential to
follow the instructions carefully to ensure safe and efficient use
of the product.
Operating Restrictions
Do not install the storage tank in any location where gasoline
or flammable vapors are likely to be present. Failure to comply may
result in fire or explosion.
Installation
-
Consult a qualified professional installer or service
technician for proper installation procedures. -
Ensure that a Temperature & Pressure (T&P) relief valve
is installed to protect against excessive temperature and
pressure. -
Refer to the provided diagram for proper installation
positioning and connections.
FAQ
Q: What should I do if I smell gas?
A: If you smell gas, do not operate the storage
tank. Contact a professional immediately to address the issue.
Q: Why is it important to install a Temperature & Pressure
relief valve?
A: The relief valve is crucial in preventing
scalding injuries and ensuring safe operation of the storage tank
by regulating temperature and pressure levels.
100161703_2000017219 Rev E
WARNING: If the information in this
manual is not followed exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
— This storage tank MUST NOT be installed in any location where gasoline or
flammable vapors are likely to be present.
— WHAT TO DO IF YOU SMELL GAS
·Do not try to light any appliance. ·Do not touch any electric switch; do not
use any phone in your building. ·Immediately call your gas supplier from a
near by phone. Follow the gas supplier’s instructions. · If you cannot reach
your gas supplier, call the fire department. ·Installation and service must be
performed by a qualified installer, service agency, or the gas supplier.
Installation & Operation Manual Models: 60 – 119
LOW LEAD CONTENT
WARNING
The information contained in this manual is intended for use by qualified professional installers, or service technicians. Consult your local expert for proper installation or service procedures.
Save this manual for future reference.
Contents
CONTENTS…………………………………………………………….. 2 HAZARD DEFINITIONS…………………………………………… 2 1.
GENERAL INFORMATION ………………………………. 3-4
Operating Restrictions ………………………………………….. 4 2. INSTALLATION
………………………………………………….. 5
Pre-Installation …………………………………………………….. 5 Transporting and unpacking the unit
………………………. 5 Examining the unit ………………………………………………. 5 Anchoring the
unit………………………………………………… 5 Recommended service clearances ……………………….. 5
Connecting the hot water source……………………………. 6 Hot water outlet
…………………………………………………… 6
Mixing valve ………………………………………………………… 6 Aquastat / bulbwell ………………………………………………. 6 Piping the relief valve ……………………………………………. 7 Drain ………………………………………………………………….. 7 Completing the installation ……………………………………. 7 3. OPERATION ………………………………………………………. 8 Startup procedure …………………………………………………. 8 Shutdown procedure……………………………………………… 8 4. INSPECTION ……………………………………………………… 9 5. MAINTENANCE………………………………………………… 10 Flushing the tank ……………………………………………….. 10 Revision Notes ………………………………………….. Back Cover
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels
or to important information concerning the life of the product.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTICE
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
Hot Water Can Scald!
· Water heated to temperatures for clothes washing, dish washing, and other
sanitizing needs can scald and cause permanent injury.
· Children, elderly, and infirm or physically handicapped persons are more
likely to be permanently injured by hot water. Never leave them unattended in
a bathtub or shower. Never allow small children to use a hot water tap or draw
their own bath.
· If anyone using hot water in the building fits the above description, or if
state laws or local codes require certain water temperatures at hot water
taps, you must take special precautions: · Use lowest possible temperature
setting. · Install some type of tempering device, such as an automatic mixing
valve, at hot water tap or water heater. Automatic mixing valve must be
selected and installed according to valve manufacturer’s recommendations and
instructions.
· Water passing out of drain valves may be extremely hot. To avoid injury: ·
Make sure all connections are tight. · Direct water flow away from any person.
Protection Must Be Taken Against Excessive Temperature and Pressure!
–Installation of a Temperature & Pressure (T&P) relief valve is required.
2
1 General information
WARNING
· Before using product, understand instructions.
read
and
· Save these instructions for future reference.
· All work must be performed by qualified personnel trained in the proper application, installation, and maintenance of the water systems in accordance with all applicable codes and ordinances.
· To prevent serious burns, wear heat resistant gloves when handling hot equipment.
Failure to follow this warning could cause property damage, personal injury, or death.
Installation and Operation Manual
Table 1A details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.
Table 1A Approximate Time / Temperature Scald Chart
APPROXIMATE TIME / TEMPERATURE RELATIONSHIPS IN SCALDS
120°F 125°F 130°F 135°F 140°F 145°F 150°F 155°F
More than 5 minutes 1 1/2 to 2 minutes About 30 seconds About 10 seconds
Less than 5 seconds Less than 3 seconds About 1 1/2 seconds
About 1 second
Figure 1-1 Lochinvar SJS Series Storage Tank
HOT WATER OUTLET F
23° 23°
MODEL NUMBER
A
SJS060
36
SJS080
69.5
SJS119
68.3
A B
C
B
28 61.75 60.12
C
14.25 14.25 14.5
SENSOR WELL
FROM WATER HEATER
TO WATER HEATER DRAIN VALVE (SHIPPED LOOSE)
E D
D
E
9.25
9
9.25
9
9.5
9
IMG00542
F
RECIRCULATION TAPPINGS
OUTLET
28
1-1/2″ NPT
1-1/2″ NPT
24
2″ NPT
1-1/2″ NPT
28
2″ NPT
1-1/2″ NPT
3
Installation and Operation Manual
1 General information
This manual is intended to cover installation, operation, and maintenance
procedures for Lochinvar’s SJS Storage Tank. Instructions may not be specific
to every system.
If questions are not answered by this manual, or if specific installation,
operation, and/or maintenance procedures are not clearly understood, contact
Lochinvar for clarification before proceeding.
Storage Tanks are designed for indoor use only. It should be located on a
level surface (no more than one-half degree of slope), capable of supporting
the total weight of the unit when filled to capacity.
The unit should be mounted to the floor following applicable architectural and
local code requirements for the specific installation site. NOTE: Tanks do not
come standard with floor tie downs.
For all piping connections, the use and/or type of joint compound or sealer on
the joints should be determined by referring to local codes, accepted
standards, and/or the requirements of the installing contractor.
WARNING Areas of potential danger: 1. All water lines, joints, and valves.
2. If the unit has been in operation, allow the water in the heater and all components and surfaces (tank surface, water piping, etc.,) to cool before starting any maintenance procedures.
3. Assure that all power to associated water heating equipment has been shut off and disconnected before attempting any procedures.
4. Assure that all incoming and outgoing water lines have been shut off at the manual shutoff valves.
WARNING
Heated water presents situations that can be very dangerous due to the fact they are under pressure and at very high temperatures. To avoid possible injury or death, use common sense and follow all accepted and recommended procedures when performing installation, operation, and maintenance procedures.
WARNING
The combination of electricity and water can pose a very dangerous situation. Assure that all power has been shut off / disconnected from any associated water heater equipement before attempting any installation or maintenance procedures.
Tank construction
Storage Tanks are pre-engineered and pre-assembled complete with all fittings.
And like every Lochinvar product, they are thoroughly tested to ensure proper
performance from the moment they are installed.
Gallon Capacities — Lochinvar tanks are available in gallon capacities from 60
to 119 gallons.
Pressure Rating — Lochinvar tanks are available with a maximum 150 psi working
pressure.
Temperature Rating — Lochinvar tanks are available with a maximum temperature
of 210°F.
Tank — Lochinvar tanks are constructed of 316L stainless steel with
Polypropylene/ABS jackets to prevent rusting.
Insulation — Tanks are insulated with a Polyeurethane foam mixture that has an
R value of R-16. These tanks are for indoor installation only.
Relief Valve Tapping — A tapping is provided for the installation of a factory
supplied ASME/ANSI safety relief valve.
Hot Water Recirculation Tappings — Lochinvar storage tanks will have two (2)
tappings on the tank to provide recirculation piping between the tank and a
hot water source.
Hot Water Outlet — A Hot Water Outlet Tapping is positioned on the top of the
tank for connection to the building system.
Drain — A tapping or drain pipe will be connected to a low point on the tank
for drainage.
Aquastat Bulbwell — All Lochinvar tanks are provided with a bulbwell for the
location of control sensors.
4
2 Installation
Pre-Installation
1. The installation must conform to the instructions in this manual and all
applicable local, state, provincial, and national codes, laws, regulations,
and ordinances. Installations in Canada must conform to B149.2 Installation
Code.
2. Be certain the domestic water supply to the tank has physical and chemical characteristics that fall within the limits shown in Table 2A. Where questions exist as to the composition of the water on the job, a qualified water treatment expert should be consulted.
CAUTION
Water with characteristics outside the limits shown in Table 2A may severely shorten the life of the tank due to corrosion. Damage to tanks in such cases is not covered under warranty.
3. Read and understand all installation requirements in this manual.
Table 2A Water Chemistry Requirements
Water used in the tank must have characteristics falling within the following
limits:
Characteristic
Min.
Max.
Ph
6.0
8.0
Chloride (PPM)
—
80
Transporting and unpacking the unit
Each jacketed Lochinvar SJS Storage Tank is cartoned as necessary at the
factory. The carton is designed to provide protection for the unit during
transportation, and to provide a safe means by which to lift and move the unit
with a fork lift or hand truck.
Installation and Operation Manual
Examining the unit
After the unit has been uncartoned and set in place, it should be carefully
examined to assure the tank has not been damaged during shipping. If any
evidence of damage is detected that could affect the safe operation of the
unit, contact Lochinvar , LLC., or your authorized sales representative, to
report the damage and to receive instructions on how to proceed.
After the unit and all components have been inspected for damage, it is
suggested that all optional or independent pressure and temperature control
components be checked to assure that they meet or exceed design
specifications. If any discrepancy is found, contact Lochinvar, LLC., or your
authorized representative, before proceeding with the installation.
Anchoring the unit
The unit should be anchored to the floor, following applicable architectural /
local code requirements, or accepted standards for the specific installation
site. The unit should be installed in a location with sufficient clearance for
service and repair.
Check local codes for Seismic anchoring requirements. If further assistance is
needed, call the Lochinvar Technical Service Department and request a Seismic
Report.
Recommended clearances
The installation location must provide adequate clearances for servicing and
proper operation of the tank. A 12 inch vertical clearance is recommended from
the top of the tank. A zero clearance is allowed for the sides of the tank.
Locating the tank
CAUTION
The appliance MUST be located where leakage from the relief valve, leakage from related piping, or leakage from the tank or connections, will not result in damage to the surrounding areas, or to the lower floors of the building. A hot water storage tank should always be located in an area with a floor drain or installed in a drain pan suitable for water heaters. The manufacturer shall not be held liable for any such water damage.
5
2 Installation
Connecting the hot water source
Before making any connections of water WARNING inlet or outlet to the unit,
assure that all piping is clean and free of foreign material or scale. This
can usually be accomplished by “blowing out” the pipe. Any foreign material or
scale entering the unit can adversely affect operation and performance.
The two (2) tappings on the lower side of the tank shall provide recirculation
between the tank and the water heating source. See example piping diagram
between a storage tank and an indirect gas fired water heater (FIG. 2-1).
NOTICE
See the Water Heater’s Installation and Operation manual for specific piping diagrams that match the inlet / outlet water tappings on the tank to the inlet / outlet water tappings on the water heater. Tapping locations on the water heater may vary by product or manufacturer.
Figure 2-1_Vertical Tank Piping Diagram
COLD WATER SUPPLY
FLOW CHECK VALVE (TYPICAL)
MIXING VALVE THERMOMETER
BUILDING RETURN
EXPANSION TANK
HOT WATER SUPPLY
UNION (TYPICAL)
RELIEF VALVE
BALL VALVE (TYPICAL)
WATER HEATER CIRCULATOR
WATER HEATER
STORAGE TANK
FLOW SWITCH
Y-STRAINER [RECOMMENDED]
IMG00606
NOTICE
For all piping connections, the use and / or type of joint compound or sealer on the joint should be determined by referring to local codes, accepted practices, or the requirements of the installing contractor.
If the cold water supply to the system is equipped with an in-line check valve or backflow preventer, a suitable expansion tank must be installed in the cold water supply line.
Installation and Operation Manual
Hot water outlet
The next step in the installation process is to connect the hot water system piping to the hot water outlet port. The hot water supply tapping is located on top of the tank.
A manual shutoff valve should be installed downstream on the hot water outlet line as an isolation device in case the unit must be disconnected from the system. The shutoff valve should be in the closed position and remain so until the installation is complete.
Mixing valve
Field supplied. An anti-scald mixing valve is recommended when storing domestic hot water above 115°F.
Aquastat bulbwell
Review the controls for the hot water source equipment. Some equipment or systems designs will require an independent aquastat (field supplied) to control the equipment. The aquastat may be surface mounted onto the jacket of the tank or a nearby surface. The water sensing probe may be installed in the 3/8″ diameter dry bulbwell supplied with all Lochinvar Hot Water Storage Tanks. The equipment may employ a water sensing thermistor. The thermistor would be installed into the dry bulbwell and wired back to the hot water equipment.
NOTICE
When connecting the unit to piping made of a different material, use of a dielectric fitting or a dielectric union conforming to ASSE 1079 is recommended to prevent corrosion and potential subsequent water leaks at or near the connection. Dielectric fittings may be required by local plumbing codes.
6
2 Installation (continued)
Piping the relief valve (Relief valve is field
supplied)
All Lochinvar SJS Storage Tanks are equipped with a relief valve tapping on the tank. The valve should be piped to a discharge line leading to a suitable drain. Piping the pressure relief valve to a suitable drain will prevent both water and heat damage to the unit, as well as reduce the risk of injury from released heated water. The pipe must be of adequate size to properly handle the capacity of the relief valve and discharge line.
Check local codes to assure compliance. If a check valve has
been installed on the inlet water line, thermal expansion may
take place causing build up of excessive pressure when the water
is being heated. This expansion will cause the relief valve to
open, releasing hot water to the discharge line. A properly sized
expansion tank must be installed to protect the system from
water expansion.
WARNING
Do not install a manual shut off valve between the relief valve and the discharge.
Doing so could cause serious injury or death
if the relief valve released and the manual
valve was closed. This would cause excessive
buildup of pressure in the storage tank which
could result in an explosion.
Drain
The tanks’ drain connection must be piped to a suitable floor drain. Brass drain cocks are acceptable. A brass full port ball valve is recommended to improve water flow.
Completing installation
Installation of the Lochinvar Hot Water Storage Tank is now complete. All
documentation supplied with the unit should be passed along to maintenance
personnel for future reference.
Installation and Operation Manual
7
Installation and Operation Manual
3 Operation
After all installation procedures have been completed, and all water piping to
the energy source and power connections have been double checked, the unit is
ready for operation. The following Startup Procedure focuses on the storage
tank. Check the Installation and Operation Manual of the hot water source for
additional startup and shutdown procedures.
Startup procedure
1. Assure that all manual shutoff valves are closed.
2. Slowly open the manual shutoff valve on the cold water supply line and the
valves in the hot water source recirculation piping. Check to assure that
there are not leaks at the valve or any joints. Allow the tank to fill with
water. As the tank is filling, hold the relief valve open to allow air to
bleed out of the tank. Hot water faucets at the highest location in the
building should also be opened. This will speed the filling process. Make sure
the tank is full of water and free of air.
3. Open the manual shutoff valves.
4. Turn on the recirculation pump between the water heater and the tank.
Shutdown procedure
1. Turn off all power to the circulating pump and the hot water source
controls.
2. Close all valves in the system in the following order: · the hot water
outlet line; · the recirculation water piping
3. Relieve the pressure where possible.
4. After the system has cooled, drain the unit by opening the tank drain
valve and holding the relief valve in the open position. This will prevent the
formation of a vacuum and increase the drainage flow.
5. Proceed with the required maintenance or repairs.
6. After performing the required maintenance or repairs, return the unit to
operation by following the Startup Procedure.
After the power to the pump is turned on verify that the
pump is working. If the pump is an oil lubricated unit,
verify proper oiling.
WARNING
Heated can be
water presents very dangerous
situations that because of the
high temperatures and pressures. Use
common sense and follow all accepted
and recommended procedures when
performing installation, operation, and
maintenance procedures to avoid possible
injury or death.
5. Follow the Startup procedure for the water heater to initiate a call for heat. Adjust the operating temperature control to the desired operating temperature and set the safety high limit.
6. As the unit is heating the water, carefully re-inspect water recirculation piping and the tank hot water outlet for signs of leakage.
7. As the unit approaches the desired operating temperature, adjust the temperature controls.
8. After the unit has reached operating temperature, re-inspect all joints for signs of leakage. In addition, check all gauges and controls to verify that the water temperature and pressure are within design specifications.
9. The unit is now ready for normal operation.
8
Installation and Operation Manual
4 Inspection
The following table summarizes the recommended time intervals for inspections
of the tank, components, water piping and power connections.
To Be Inspected
RECOMMENDED INSPECTIONS Time Interval
Per Manufacturer
Specs
Weekly
Monthly
Quarterly
Annually
Circulating Pump
ü
Gauges – Pressure & Temperature
Lines – Inlet, Outlet, & Return
Pressure Relief Valve
ü
Shutoff Valves – Manual
Temperatures – Water & Operating
Thermometer
Interior for Sediment or Scale
Flush tank at six (6) month intervals
ü ü
ü ü
ü ü
ü
9
5 Maintenance
A new tank installation should have a regular inspection program set up. The first inspection should be within the first three months of operation. Once the tendency to accumulate sediment has been established, the inspection program can be modified to suit the water conditions. Typical inspection programs flush the tank at six-month intervals and clean the tank in yearly intervals.
Deliming solvents or acid type flush agents are not
recommended for use. These chemical cleaners are usually
designed for use in non-potable systems such as heating
boilers. These chemicals may be aggressive and cause
damage to the tank.
WARNING
Hot water will be released under pressure. Avoid contact with the hot discharge
water to prevent the risk of severe scald
injury.
Flushing the storage tank
Since mineral accumulation occurs in an un-fired tank it will be in a soft sediment form. This soft sediment can be removed by a regular flushing of the lower portion of the tank.
To flush the tank, follow these steps:
1. Turn off electrical power to the circulating pump and any other tank
accessories.
2. Close the valve on the hot water outlet on top of the storage tank.
3. Ensure that the drain located on the bottom of the tank is routed to a
floor drain with adequate capacity to allow the tank to be flushed.
4. Open the drain valve and allow the incoming cold water to flush the soft
sediment out the bottom of the storage tank. Use extreme caution, as the water
exiting the tank drain may be very hot. Avoid contact with the hot discharge
water to prevent the risk of severe scald injury.
5. Observe the color of the water initially discharged from the tank drain.
This water will generally be milky or slightly discolored by the sediment
discharge. Allow the drain to run until the water runs clear.
6. Close the drain valve on the tank.
7. Open the hot water outlet valve on top of the tank.
8. Open an adjacent hot water tap to purge any air that may have entered the
storage tank during the draining process. Close the hot water tap if no air
discharge is observed.
9. Turn on electric power to the circulating pump and other electrical
components if necessary.
10. Observe tank and piping to ensure all components are functioning
properly.
10
Installation and Operation Manual
Notes
Installation and Operation Manual
11
Revision Notes: Revision A (ECO #C11841) initial release.
Revision B (ECO C11908) reflects the update of chart information in FIG. 1-1
on page 3 for SJS080.
Revision C (ECO #C12382) reflects the addition of the CSA Low Lead Content
logo.
Revision D (ECO C15671) reflects the addition of the “Locating the tank”
caution on page 5.
Revision E (PCP #3000060820 / CN #500046810) reflects the addition of a
dielectric notice on page 6.
100161703_2000017219 Rev E 06/24