Lochinvar EcoCharger Range Flue User Guide

June 6, 2024
Lochinvar

Lochinvar logo

Lochinvar EcoCharger Range Flue

Models covered:

  • ECH32-220GCE
  • ECH33-370GCE
  • ECH52-370GCE
  • ECH87-480GCE
  • ECH106-480GCE
  • ECH129-480GCE

DOCUMENT CONTROL

Article Language Version Modified by
EcoCharger flue guide English V1.0 October 2021 S Addis

GENERAL

CERTIFIED FLUE SYSTEMS

Lochinvar Water Heaters are certified for use on the following flue categories:

Installation type Category Description

B23

|

Open flue

| An appliance intended to be connected to a flue that evacuates the products of combustion to the outside of the room containing the appliance. The combustion air is drawn directly from the room.
C13| Closed Flue| An appliance connected to either a concentric or twin- pipe flue system with a Horizontal flue terminal. Both the air inlet and flue exhaust must be in the same pressure zone.
C33| Closed Flue| An appliance connected to either a concentric or twin- pipe flue system with a Vertical flue terminal. Both the air inlet and flue exhaust must be in the same pressure zone.

C43

|

Closed Flue

| An appliance connected to a common air inlet and flue exhaust system, which is designed for more than one appliance. This common system has a single air inlet and flue exhaust and is part of the building not the appliance.
C53| Closed Flue| An appliance connected to a twin-pipe flue system with a Horizontal or Vertical flue terminal. Both air inlet and flue exhaust may be in different pressure zones.

C63

|

Closed Flue

| An appliance intended to be connected to a separately approved and marketed system for the supply of combustion air and discharge of combustion products (i.e. other than that supplied by the water heater manufacturer).

All installations should comply with the requirements of:

  1. For appliances up to 70kW net input- BS5440-1:2008- Flueing and ventilation for gas appliances of rated input not exceeding 70 kW net (1st, 2nd and 3rd family gases). Specification for installation of gas appliances to chimneys and for maintenance of chimneys.
  2. Refer to drawing 1 and table 1 for details of terminal locations.
  3. For appliances over 70kW net input- IGEM/UP/10 Edition 4 +A: 2016 – Installation of flued gas appliances in industrial and commercial premises, specific attention should be paid to the following sections.
  4. Refer to drawing 1 and table 1 for details of terminal locations.
  5. Horizontal terminations shall be located according to the minimum distances given in table 1, and subject to the risk assessment criteria shown in table 2.
  6. Horizontal flue terminations (other than for fan dilution systems) must not be installed for any single appliance or group of appliances with a total nett input exceeding 333kW net heat input.
  7. For any single appliance or group of appliances with a total net heat input exceeding 333 kW, the general requirements of IGEM/UP/10 Edition 4 +A: 2016 shall apply and approval must be sought from the Local Authority prior to commencement of the installation.
  8. The Clean Air Act for installations exceeding 333kW nett input.

DRAWING 1 WATER HEATER TERMINAL LOCATIONSLochinvar EcoCharger Range
Flue fig1

TABLE 1 WATER HEATER TERMINAL LOCATIONS

Location| Description| | ECH32-220GCE| ECH33-370GCE| ECH52-370GCE| ECH63-370GCE| ECH87-480GCE| ECH106-480GCE| ECH129-480GCE
---|---|---|---|---|---|---|---|---|---
| Water heater nett input| kW| 29.4| 30.5| 47.8| 57.9| 79.3| 96.6| 117.9
A| Directly below an opening, air brick, opening windows etc.#| mm| 300| 300| 300| 300| 2500| 2500| 2500
B| Above an opening, air brick, opening windows etc.| mm| 300| 300| 300| 300| 1092| 1294| 1294
C| Horizontally to an opening, air brick, opening windows etc.#| mm| 300| 300| 300| 300| 667| 792| 946
D| Below a gutter or sanitary pipework| mm| 75| 75| 75| 75| 200| 200| 200
E| Below the eaves| mm| 200| 200| 200| 200| 200| 200| 200
F| Below a balcony or car port roof| mm| 200| 200| 200| 200| Not reccomended see UP10 risk assesment
G| From a vertical drain or soil pipe| mm| 144| 144| 144| 144| 150| 150| 150
H| From an internal or external corner| mm| 300| 300| 300| 300| 1215| 1615| 2108
I| Above ground, roof or balcony level| mm| 300| 300| 300| 300| 300| 300| 300
J| From a surface facing the terminal| mm| 600| 600| 600| 600| 1215| 1615| 2108
K| From a terminal facing the terminal| mm| 1200| 1200| 1200| 1200| 2180| 2514| 2925
L| From an opening in the car port (e.g. door, window) into the dwelling| mm| 1200| 1200| 1200| 1200| Not reccomended see UP10 risk assesment
M| Vertically from a terminal on the same wall| mm| 1500| 1500| 1500| 1500| 2500| 2500| 2500
N| Horizontally from a terminal on the same wall| mm| 300| 300| 300| 300| 667| 792| 946
P| From a vertical structure on the roof| mm| 300| 300| 300| 300| 1500| 1500| 1500
Q| Above intersection with the roof| mm| 150| 150| 150| 150| 325| 371| 428

distances shown ensure the Water Heaters will operate without problems under most conditions, these distances can be reduced in certain circumstances contact Lochinvar Technical support for assistance if required.

multiple Water Heater installation above 333kW nett input are covered by the clean air act and must comply with its requirements

see UP10 figure 7 for full clarification

TABLE 2 RISK ASSESMENT
The table below is an excerpt from IGEMUP10 and should be used in conjunction with that document

Further to the requirements in IGEM/UP/10 Edition 4 +A: 2016 Section 8 under clause 8.7.3.3 and Figure 7 the following risk assessment gives guidance for the positioning of horizontal flues. This form should be completed before work commences and undertaken by a person who is competent to undertake the risk assessment.

Type C appliances with net heat input exceeding 70 kW and not exceeding 333 kW low level flue discharge risk assessment (including net heat input for groups of appliances)

No.| Regarding the flue position| No| Yes

1

| Is the proposed flue termination within the distance in Figure K of a road, path, track, thoroughfare, walkway, property boundary or area, which is used for general

public access other than for maintenance purposes?

|

No

|

Yes

2| Is the proposed flue termination within the distance in Figure K to a playground, school, yard, seating area, or area where there may be a public gathering| No| Yes
3| If the proposed flue termination enclosed on more than two sides then does it comply with the requirements of Figure 11B?| No| Yes

4

| Is the proposed flue termination within the distance in Figure K of a surface or building element that may be affected by corrosion or deterioration from plume

condensate?

|

No

|

Yes

5| Is the proposed flue position in an area where vehicles could be parked within distances from Figure 12 Line G to the flue?| No| Yes
6| Are there shrubs or trees within minimum distances shown on Figure K of the proposed terminal position?| No| Yes
7| Is the proposed flue termination within a light well?| No| Yes

8

| Are the products of combustion from the proposed flue position likely to build up under unfavourable atmospheric conditions, due to poor cross flow of air caused by enclosures or adjacent structures and/or likely to cause nuisance?|

No

|

Yes

9| Is the flue termination position likely to cause a nuisance to adjoining properties?| No| Yes
Building Regulations part J
10| Is the proposed flue termination less than 300 mm from the boundary of the property, as measured from the side of the terminal to the boundary?| No| Yes
Regarding the Clean Air Act
11| Is the total output of the individual, or group of flue terminals (if within 5U (see A3.7)), greater than 333 kW net heat input?| No| Yes
General
12| Are there any other considerations that are required for this risk assessment, see separate sheet.| No| Yes
13| Comments:| |
| | | | | | | | |
If all answers are Blue then the flue position should be suitable
If any answer is Orange then the flue position is unsuitable, consider revising the position or type of flue outlet or contact the local Environmental Health officer for assistance and/or approval

CONCENTRIC FLUE SYSTEMS

STANDARD CONCENTRIC HORIZONTAL AND VERTICAL FLUE

LV302504 CONCENTRIC HORIZONTAL FLUE ASSEMBLY

MODELS – ECH32-220,ECH33-370,ECH52-370 ECH63-370


COMPONENTS INCLUDED
Item No.| Description| Included
LV302505| CONCENTRIC HORIZONTAL TERMINAL Ø100/150 ALU| 1
LV302499| CONCENTRIC EXTENSION Ø100/150 (500mm) ALU CUT TO LENGTH| 1
LV302502| CONCENTRIC BEND 90⁰ Ø100/150 ALU| 1

Lochinvar EcoCharger Range Flue fig2

LV311465 CONCENTRIC HORIZONTAL FLUE ASSEMBLY

MODELS – ECH87-480,ECH106-480,ECH129-480


COMPONENTS INCLUDED
Item No.| Description| Included
LV302313| CONCENTRIC HORIZONTAL TERMINAL Ø130/200 ALU| 1
LV302301| CONCENTRIC EXTENSION Ø130/200 (500mm) ALU CUT TO LENGTH| 1
LV311456| CONCENTRIC BEND 90⁰ Ø130/200 ALU| 1

| ECH32-220| ECH33-370 to ECH63-370| ECH87-480 to ECH129-480
---|---|---|---
V| 550| 550| 640
W| 725| 790| 940
X| 1535| 2075| 2230
Y| 1460| 1480| 1620

LV311463 CONCENTRIC VERTICAL FLUE ASSEMBLY

MODELS – ECH32-220,ECH33-370,ECH52-370,ECH63-370


COMPONENTS INCLUDED
Item No.| Description| Included
LV311458| CONCENTRIC VERTICAL TERMINAL Ø100/150 ALU| 1
LV311450| CONCENTRIC EXTENSION Ø100/150mm (1000mm) ALU CUT TO LENGTH| 1
LV302509| ROOF FLASHING (170mm) ALU| 1

LV311464 CONCENTRIC VERTICAL FLUE ASSEMBLY

MODELS – ECH87-480,ECH106-480,ECH129-480


COMPONENTS INCLUDED
Item No.| Description| Included
LV306390| CONCENTRIC VERTICAL TERMINAL Ø130/200 ALU| 1
LV302301| CONCENTRIC EXTENSION Ø130/200 (500mm) ALU CUT TO LENGTH| 1
LV302328| FLAT ROOF FLASHING (210mm) ALU| 1

| ECH32-220| ECH33-370 to ECH63-370| ECH87-480 to ECH129-480
---|---|---|---
V| 1500| 1500| 1730
W| 1035| 1035| 940
X| 2965| 3325| 3620
Y| 1415| 1560| 1560
| ECH32-220 to ECH63-370| ECH87-480 to ECH129-480
---|---|---
Maximum flue length| Maximum length 40 metres| Maximum length 15 metres
Maximum no of bends| 7| 4
Even if using less than the maximum number of bends, the maximum pipe length may not be exceeded. Even if using less than the

maximum pipe length, the maximum number of bends may not be exceeded.

Additional Concentric flue items available to complete the installation

Additional Flue Ancillary Items MODELS – ECH32-220,ECH33-370,ECH52-370,ECH63-370

Item No.| Description
LV303854| CONCENTRIC TEST POINT Ø100/150 ALU
LV302499| CONCENTRIC EXTENSION Ø100/150 (500mm) ALU CUT TO LENGTH
LV311450| CONCENTRIC EXTENSION Ø100/150mm (1000mm) ALU CUT TO LENGTH
LV311451| CONCENTRIC EXTENSION Ø100/150mm (1500mm) ALU CUT TO LENGTH
LV302502| CONCENTRIC BEND 90⁰ Ø100/150 ALU ( A=223mm B=208mm)
LV311454| CONCENTRIC BEND 45⁰ Ø100/150mm ALU (A=128mm B=128mm)
M87196| WALL CLAMP Ø150

Lochinvar EcoCharger Range Flue fig4

Additional Flue Ancillary Items MODELS – MODELS – ECH87-480,ECH106-480,ECH129-480

Item No.| Description
LV303855| CONCENTRIC TEST POINT Ø130/200 ALU
LV302301| CONCENTRIC EXTENSION Ø130/200 (500mm) ALU CUT TO LENGTH
LV311452| CONCENTRIC EXTENSION Ø130/200mm (1000mm) ALU CUT TO LENGTH
LV311453| CONCENTRIC FLUE EXTENSION Ø130/200mm X (1500mm) Cutable
LV311456| CONCENTRIC BEND 90⁰ Ø130/200 ALU (A=223mm B=208mm)
LV311455| CONCENTRIC BEND 45⁰ Ø130/200mm ALU (A=128mm B=223mm)
M87198| WALL CLAMP Ø200

TWIN PIPE HORIZONTAL FLUE

ECPH001 TWIN-PIPE HORIZONTAL FLUE ASSEMBLY WITH CONCENTRIC TERMINAL MODELS ECH32-220,ECH33-370,ECH52-370,ECH63-370

COMPONENTS INCLUDED|
Item No.| Description| Included
LV302505| CONCENTRIC HORIZONTAL TERMINAL Ø100/150 ALU| 1
LV307142| TWIN PIPE TO CONCENTRIC ADAPTOR Ø100/100mm TO Ø100/150mm ALU| 1
LV307161| EXTENSION Ø100mm(1000mm) ALU CUT TO LENGTH| 2
LV307164| BEND 90° Ø100mm ALU| 2
LV304204| CONCENTRIC TO TWIN PIPE ADAPTOR Ø100/150mm TO Ø100/100mm ALU| 1

Lochinvar EcoCharger Range Flue fig6

ECPH002 TWIN-PIPE HORIZONTAL FLUE ASSEMBLY WITH CONCENTRIC TERMINAL MODELS ECH87-480,ECH106-480,ECH129-480

COMPONENTS INCLUDED
Item No.| Description| Included
LV306803| CONCENTRIC HORIZONTAL TERMINAL Ø130/200mm ALU| 1
LV306801| TWIN PIPE TO CONCENTRIC ADAPTOR Ø130/130mm TO Ø130/200mm ALU| 1
LV306804| EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH| 2
LV306805| BEND 90° Ø130mm ALU| 2
LV309605| CONCENTRIC TO TWIN PIPE ADAPTOR Ø130/200mm TO Ø130/130mm ALU| 1

ECPH003 TWIN-PIPE HORIZONTAL FLUE ASSEMBLY MODELS ECH32-220,ECH33-370,ECH52-370,ECH63-370

COMPONENTS INCLUDED|
Item No.| Description| Included
LV302505| CONCENTRIC HORIZONTAL TERMINAL Ø100/150 ALU| 1
LV307161| EXTENSION Ø100mm(1000mm) ALU CUT TO LENGTH| 2
LV305039| HORIZONTAL TERMINAL Ø100mm ALU| 1
LV307164| BEND 90° Ø100mm ALU| 2
LV304204| CONCENTRIC TO TWIN PIPE ADAPTOR Ø100/150mm TO Ø100/100mm ALU| 1

Lochinvar EcoCharger Range Flue fig7

ECPH004 TWIN-PIPE HORIZONTAL FLUE ASSEMBLY MODELS ECH87-480,ECH106-480,ECH129-480

COMPONENTS INCLUDED
Item No.| Description| Included
LV302313| CONCENTRIC HORIZONTAL TERMINAL Ø130/200 ALU| 1
LV306804| EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH| 2
LV307178| HORIZONTAL TERMINAL Ø130mm ALU| 1
LV306805| BEND 90° Ø130mm ALU| 2
LV309605| CONCENTRIC TO TWIN PIPE ADAPTOR Ø130/200mm TO Ø130/130mm ALU| 1

| ECH32-220 to ECH63-370| ECH87-480 to ECH129-480
---|---|---
Maximum flue length| 55| 65
Equivalent length 90 bend| 4.6| 2.4
Equivalent length 45 bend| 1.2| 1.4

TWIN PIPE VERTICAL FLUE

ECPV001 TWIN-PIPE VERTICAL FLUE ASSEMBLY WITH CONCENTRIC TERMINAL MODELS ECH32-220,ECH33-370,ECH52-370,ECH63-370

COMPONENTS INCLUDED
Item No.| Description| Included
LV311458| CONCENTRIC VERTICAL TERMINAL Ø100/150 ALU| 1
LV307142| TWIN PIPE TO CONCENTRIC ADAPTOR Ø100/100mm TO Ø100/150mm ALU| 1
LV307160| EXTENSION Ø100mm(500mm) ALU CUT TO LENGTH| 2
LV304204| CONCENTRIC TO TWIN PIPE ADAPTOR Ø100/150mm TO Ø100/100mm ALU| 1

ECPV002 TWIN-PIPE VERTICAL FLUE ASSEMBLY WITH CONCENTRIC TERMINAL MODELS ECH87-480,ECH106-480,ECH129-480

COMPONENTS INCLUDED
Item No.| Description| Included
LV306800| CONCENTRIC VERTICAL TERMINAL Ø130/200 ALU| 1
LV306801| TWIN PIPE TO CONCENTRIC ADAPTOR Ø130/130mm TO Ø130/200mm ALU| 1
LV306804| EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH| 2
LV309605| CONCENTRIC TO TWIN PIPE ADAPTOR Ø130/200mm TO Ø130/130mm ALU| 1

ECPV003 TWIN-PIPE VERTICAL FLUE ASSEMBLY MODELS ECH32-220,ECH33-370,ECH52-370,ECH63-370

COMPONENTS INCLUDED
Item No.| Description| Included
LV305040| VERTICAL TERMINAL Ø100mm ALU| 1
LV305039| HORIZONTAL TERMINAL Ø100mm ALU| 1
LV307160| EXTENSION Ø100mm(500mm) ALU CUT TO LENGTH| 2
LV307164| BEND 90° Ø100mm ALU A=115mm,B=115mm| 1
LV310197| BEND 45° Ø100mm ALU A=100mm,B=100mm| 1
LV304204| CONCENTRIC TO TWIN PIPE ADAPTOR Ø100/150mm TO Ø100/100mm ALU| 1

ECPV004 TWIN-PIPE VERTICAL FLUE ASSEMBLY MODELS ECH87-480,ECH106-480,ECH129-480

COMPONENTS INCLUDED
Item No.| Description| Included
LV307175| VERTICAL TERMINAL Ø130mm ALU| 1
LV306804| EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH| 2
LV307178| HORIZONTAL AIR INLET Ø130mm ALU| 1
LV306805| BEND 90° Ø130mm ALU| 1
LV309605| CONCENTRIC TO TWIN PIPE ADAPTOR Ø130/200mm TO Ø130/130mm ALU| 1

| ECH32-220 to ECH63-370| ECH87-480 to ECH129-480
---|---|---
Maximum flue length| 55| 65
Equivalent length 90 bend| 4.6| 2.4
Equivalent length 45 bend| 1.2| 1.4

Additional Twin-pipe flue items available to complete the installation

Additional Flue Ancillary Items MODELS – ECH32-220,ECH33-370,ECH52-370,ECH63-370

Item No.| Description
LV307160| EXTENSION Ø100mm(500mm) ALU CUT TO LENGTH
LV307161| EXTENSION Ø100mm(1000mm) ALU CUT TO LENGTH
LV307164| BEND 90° Ø100mm ALU (A=115mm,B=115mm)
LV310197| BEND 45° Ø100mm ALU (A=100mm,B=100mm)
LV302520| ROOF FLASHING (140mm) ALU
M87193| WALL CLAMP Ø100mm
Additional Flue Ancillary Items MODELS – MODELS – ECH87-480,ECH106-480,ECH129-480
Item No.| Description
LV306804| EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH
LV306802| EXTENSION Ø130mm(1000mm) ALU CUT TO LENGTH
LV306805| BEND 90° Ø130mm ALU (A=160mm,B=160mm)
LV308026| BEND 45° Ø130mm ALU (A=100mm,B=100mm)
LV302520| ROOF FLASHING (140mm) ALU
M87195| WALL CLAMP Ø130mm

CONVENTIONAL (EXHAUST ONLY) FLUE SYSTEMS

ECCV001 CONVENTIONAL (EXHAUST ONLY) FLUE ASSEMBLY MODELS ECH32-220,ECH33-370,ECH52-370,ECH63-370

COMPONENTS INCLUDED|
Item No.| Description| Included
LV305040| VERTICAL TERMINAL Ø100mm ALU| 1
LV307160| EXTENSION Ø100mm(500mm) ALU CUT TO LENGTH| 2
LV304872| APPLIANCE AIR INTAKE GUARD Ø100| 1
ECCV002 CONVENTIONAL (EXHAUST ONLY) FLUE ASSEMBLY MODELS ECH87-480,ECH106-480,ECH129-480
COMPONENTS INCLUDED|
Item No.| Description| Included
LV307175| VERTICAL TERMINAL Ø130mm ALU| 1
LV306804| EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH| 2
LV307176| APPLIANCE AIR INTAKE GUARD Ø130mm ALU| 1

| ECH32-220 to ECH63-370| ECH87-480 to ECH129-480
---|---|---
Maximum flue length| 55| 65
Equivalent length 90 bend| 4.6| 2.4
Equivalent length 45 bend| 1.2| 1.4

Additional Exhaust only flue items available to complete the installation

Additional Flue Ancillary Items MODELS – ECH32-220,ECH33-370,ECH52-370,ECH63-370

Item No.| Description
LV307160| EXTENSION Ø100mm(500mm) ALU CUT TO LENGTH
LV307161| EXTENSION Ø100mm(1000mm) ALU CUT TO LENGTH
LV307164| BEND 90° Ø100mm ALU (A=115mm,B=115mm)
LV310197| BEND 45° Ø100mm ALU (A=100mm,B=100mm)
LV302520| ROOF FLASHING (140mm) ALU
M87193| WALL CLAMP Ø100mm
Additional Flue Ancillary Items MODELS – MODELS – ECH87-480,ECH106-480,ECH129-480
Item No.| Description
LV306804| EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH
LV306802| EXTENSION Ø130mm(1000mm) ALU CUT TO LENGTH
LV306805| BEND 90° Ø130mm ALU (A=160mm,B=160mm)
LV308026| BEND 45° Ø130mm ALU (A=100mm,B=100mm)
LV302520| ROOF FLASHING (140mm) ALU
M87195| WALL CLAMP Ø130mm

COMMON FLUE SYSTEMS

Any installations using flue type C63 must be designed and installed in compliance with any local Building or planning regulations, but as these systems use a flue system not supplied by Lochinvar, Lochinvar cannot comment / advise or provide support on the design of this type of flue system. To design such a flue system, the installer/contractor must consult a specialist flue supplier who will be responsible for the design and installation of the separate flue system. When designing the type C63 flue system, the instructions in the Installation Manual, provided with the water heater, must be taken into account. Lochinvar will provide pressure loss figures for the specific units, but other than that, Lochinvar cannot provide support on Common Flue requests because flue certification is limited to the certified categories in the table on page 2. Lochinvar cannot accept any responsibility for Flue system design.

Pressure Loss Figures

Maximum pressure Flue gas rate

Model

| Inlet only| Outlet only| Inlet + Outlet| Gas type
P inlet| P outlet| P inlet| P outlet| P inlet| P outlet| G20| G31
Pa| Pa| Pa| Pa| Pa| Pa| kg/h| kg/h
ECH32-220| -55| 0| 0| 52| -26| 26| 51.7| 53.6
ECH33-370| -66| 0| 0| 62| -32| 32| 53.5| 54.4
ECH52-370| -142| 0| 0| 133| -69| 69| 84.6| 85.6
ECH63-370| -184| 0| 0| 173| -90| 90| 103.7| 103.8
ECH87-480| -90| 0| 0| 88| -47| 47| 141.9| 149.1
ECH106-480| -129| 0| 0| 126| -67| 67| 172.9| 181.6
ECH129-480| -184| 0| 0| 180| -96| 96| 213.3| 221.7

ORDER FORM AND NOTES

Lochinvar EcoCharger Range Flue fig11

Contact Lochinvar customer service to order additional flue items on 01295 269981

Lochinvar Limited 7 Lombard way, The MXL centre, Banbury
OX16 4TJ
01296 269981 www.lochinvar.ltd.uk