Lochinvar Amicus AquaStore Heat Pump Water Heater Owner’s Manual

June 9, 2024
Lochinvar

Lochinvar - logo Amicus AquaStore
HEAT PUMP
WATER HEATER

KEY FEATURES

  • 8kW output: The UK’s largest heat pump water heater
  • Plug & Play: Quick and easy to install with space saving design
  • Touch screen display for custom settings and status reports
  • Monoblock construction
  • 65˚C output in heat pump mode
  • Up to 350 l/hr at a 50˚ temperature rise with immersion
  • Built in redundancy – up to 12kW immersion available for backup

Lochinvar Amicus AquaStore Heat Pump Water Heater

Amicus AquaStore is a packaged heat pump water heater designed to provide DHW only and can work at temperatures up to 65°C without immersion heater support. There are 3 models in the range all with an 8kW heat pump but with different sized immersion back-up available up to 12 kW. They can provide hot water recovery rates of 350 litres per hour based on a temperature rise of 50˚C. Suitable for a range of small to medium sized commercial applications they provide hot water with zero on site emissions: as such they are fully BREEAM compliant.

ErP / EcoDesign certified product
The range has been tested and certified in accordance with the EcoDesign directive, providing peace of mind for specifiers, contractors and end users.
Insulated and jacketed storage vessel
With a storage vessel construction from enamelled steel, Amicus AquaStore water heaters are capable of operating at working pressures of up to 8bar.
An integral magnesium anode provides cathodic protection.
The storage vessel is insulated with 50mm polyurethane foam and encased in an enamelled grey jacket.
Designed for ease of maintenance
Access to refrigeration lines and compressor is provided from the front of the Amicus AquaStore water heater.

Lochinvar Amicus AquaStore Heat Pump Water Heater -
maintenance

BREEAM and zero on-site emissions
BREEAM is the world’s longest established method of assessing, rating, and certifying the sustainability of buildings. It aims to help construction professionals and building owners to manage and mitigate risk through demonstrating sustainability performance during planning, design, construction, operation, or refurbishment. It is also designed to help lower running costs, maximise returns through market value, attract, and retain tenants with desirable places to live and work. Amicus AquaStore water heaters do not have any on-site carbon or NOx emissions making them particularly suitable for BREEAM projects.
breeam

Water heater connections

Description

1| T&P valve connection
2| Hot outlet
3| Drain
4| Cold inlet
5| Touch screen display
6| Electrical cable entry point

Lochinvar Amicus AquaStore Heat Pump Water Heater - Water
heater

Technical specifications

**Model| ****LAAS 8-455-6| ****LAAS 8-455-9| ****LAAS 8-455-12
---|---|---|---
General data**
Input power heat pump operation| kW| 2.22| 2.22| 2.22
Heating capacity heat pump (EN 16147- A15)| kW| 8| 8| 8
Efficiency COP| | 3.2| 3.2| 3.2
Heating capacity electric elements| kW| 6| 9| 12
Power supply| | 400Vac/3N| 400Vac/3N| 400Vac/3N
Total heating capacity| kW| 14| 17| 20
Flow rate @50°c Peak Hour (Heat pump only)| Ltr| 350| 350| 360
Flow rate @50°c Peak Hour (Heat pump + immersion)| Ltr| 460| 480| 490
Continuous @50°C (Heat pump only)| Ltr| 200| 220| 250
Continuous @50°C (Heat pump + immersion)| Ltr| 250| 300| 350
Peak current (= L2)| A| 16.9| 22.5| 30
Maximum current (L1)- heat pump| A| 9.6| 9.6| 9.6
Maximum input (L2)- back up element 1 + controls + fans| A| 16.9| 22.5| 30
Maximum current (L3)- back up element 2| A| 13| 18.7| 26.1
Refrigerant (weight.CO2 equivalent)| (kg/ton)| R134 (1.85/2.646)| R134 (1.85/2.646)| R134 (1.85/2.646)
Tank volume| Ltr| 455| 455| 455
Max Water Temperature Efficiency or Hybrid mode| °C| 65| 65| 65
Max Water Temperature Immersion heaters only| °C| 82| 82| 82
Operating range| °C| -7- 43| -7- 43| -7- 43
Shipping weight| kg| 250| 250| 250
Weight when full| kg| 684| 684| 684
Noise| dB| 59| 59| 59

ErP Data

**Model| ****LAAS 8-455-6| ****LAAS 8-455-9| ****LAAS 8-455-12
---|---|---|---
General data**
Load profile| –| XL| XL| XL
Energy efficiency class| –| A+| A+| A+
Energy efficiency (average climate)| %| 132| 132| 132
Energy efficiency (cold climate)| %| 132| 132| 132
Energy efficiency (hot climate)| %| 132| 132| 132
Daily electricity consumption (average climate)| kWh| 6.01| 6.01| 6.01
Daily electricity consumption (cold climate)| kWh| 6.01| 6.01| 6.01
Daily electricity consumption (hot climate)| kWh| 6.01| 6.01| 6.01
Annual electricity consumption (average climate)| kWh/year| 1272| 1272| 1272
Annual electricity consumption (cold climate)| kWh/year| 1272| 1272| 1272
Annual electricity consumption (hot climate)| kWh/year| 1272| 1272| 1272
Daily fuel consumption (average climate)| GJ/year| 0| 0| 0
Daily fuel consumption (cold climate)| GJ/year| 0| 0| 0
Daily fuel consumption (hot climate)| GJ/year| 0| 0| 0
Annual fuel consumption (average climate)| kWh GCV| 0| 0| 0
Annual fuel consumption (cold climate)| kWh GCV| 0| 0| 0
Annual fuel consumption (hot climate)| kWh GCV| 0| 0| 0
Mixed water 40°C (acc. to V40)| ltr.| 526| 526| 526
Other load profile| –| N/A| N/A| N/A
---|---|---|---|---
Smart controls| –| –| –| –
---|---|---|---|---
Work only during off peak hours| –| –| –| –
Default value setpoint| °C| 50| 50| 50
Noise level Lwa (inside)| dB(A)| 59| 59| 59

Installation

The Amicus AquaStore should be sited in an area which:

  • Can bear the weight of the unit
  • Has enough space around the unit to allow maintenance, see clearances
  • Does not present a noise nuisance to users of the building and neighbours
  • Has enough ventilation
  • Frost free
  • Has an air humidity of max 93% RH at 25˚C

Dimensions

Description LAAS 8-455-6 LAAS 8-455-9 LAAS 8-455-12
A Device height mm 1770
D Device width mm 785
E Device depth mm 995
M Height cold water supply connection mm 165
B Height hot water outlet connection mm 1470
R Height drain valve connection mm 165
S Height T&P-valve connection mm 1470
W Height condensate drain connectioon mm 15
1 Cold water supply connection (female) NPT 3/4″
2 Hot water outlet connection (female) NPT 3/4″
4 Drain valve connection (female) NPT 3/4″
5 T&P-valve connection (female) NPT 3/4″

Lochinvar Amicus AquaStore Heat Pump Water Heater -
Sizing

Operational limits
Amicus AquaStore can provide domestic hot water at temperatures up to 65°C when in Hybrid mode and over 82˚C when in power mode using the electrical elements only, for example for pasteurisation.
Sizing
When sizing the AquaStore heat pump careful consideration needs to be taken of the hot water load and peak demand period. Lochinvar can help with sizing your project, contact your local area sales manager or email info@lochinvar.ltd.uk

Positioning on site
Amicus AquaStore must only be installed in a plantroom it is not suitable for external installation, the plantroom must be large enough to prevent the plantroom from cooling down too much whilst the unit is in operation. The size of the plantroom required will depend on the usage patterns of the heat pump, the larger the peak the larger the plantroom will need to be. The largest plantroom size required will be 90m³ . If the plantroom size is too small ventilation louvres will need to be fitted to allow both air in and exhaust air out to avoid pressurising the plantroom. Ventilation should ideally be supplied via a heated space to prevent the plantroom from being overcooled risking frost damage to the AquaStore and general plant area.
Clearances
Amicus AquaStore require minimum clearances around them to enable maintenance of the unit
Lochinvar Amicus AquaStore Heat Pump Water Heater -
ClearancesThe front of the unit must maintain a clearance of at least 1000mm to ensure the exhaust fans are not restricted which will cause operational issues.
Airflow
Amicus AquaStore require a constant air flow when in operation of 2275 m3/h across the evaporator, this will result in a gradual cooling of the plantroom air. The unit should not cool the room by more than 8˚C, if it does this indicates that there is insufficient air within the plantroom. The amount of ventilation required will depend on the usage pattern of the water heater and can be calculated by Lochinvar Limited.

Lochinvar Amicus AquaStore Heat Pump Water Heater -
Airflow

Positioning multiple units
When positioning multiple units’ minimum distances must be observed, airflow requirements will also be larger. please contact Lochinvar technical support for further help and guidance.
Ancillary items available
WH9 Destratification pump
To improve stratification within the vessel it may be a site requirement to install a de-stratification pump, this is available from Lochinvar as an ancillary extra.
The WH9 de-stratification kit consists of:

  • 1no LM900139A Bronze pump
  • 2no 28mm gate valves
  • 1no 28mm NRV

DRIVE

Pump type| | Potable
Motor| | Electric with integrated motor protection
Electrical requirements| | 230V /1Ph/ 50hz
Enclosure rating| | IP44
Thermal class| | F
Temperature class| | TF 110
Enclosure class| | IP44
Bearings| | Product lubricated special plain bearing
Operating modes| | 3 fixed speed levels
GENERAL DATA
Pump housing| | Stainless steel
Impellor| | Composite PES/PP
Connection type| | Screw end
Connection size| inch| R1½
Maximum pressure| bar| 10
Maximum temperature| °C| 110
Weight| kg| 2,9
Power consumption speed 1/2/3| W| 35/45/50
Current draw speed 1/2/3| A| 0.16/0.2/0.23
Approvals| | CE,WEEE,WRAS
DIMENSIONS
Port to port length| mm| 130

Lochinvar Amicus AquaStore Heat Pump Water Heater -
DRIVE

Unvented Installation

When installing AquaStore on an unvented system a suitable kit of components is available from Lochinvar as an ancillary extra.
The WH15A-RF unvented kit includes all components required and includes:

  • 22mm Monoblock incorporating a pressure reducing valve, non-return valve and 6 bar pressure relief valve
  • ¾” temperature and pressure relief valve
  • 22mm tundish
  • 25 litre flow through expansion vessel

Lochinvar Amicus AquaStore Heat Pump Water Heater -
Unvented

Amicus AquaStore can be installed as a single unit or in multiples depending upon the load, if there is a larger peak load than the unit can supply and then a prolonged period with limited demand (such as a football training ground), AquaStore can be matched with a suitable sized buffer vessel. This will reduce capital cost whilst allowing an efficient method of producing hot water without using extra immersion heaters

Lochinvar Amicus AquaStore Heat Pump Water Heater -
Unvented1

Lochinvar Amicus AquaStore Heat Pump Water Heater -
Unvented2

Electrical Connections

All models require a 3-phase supply with standard electrical requirements as per technical specifications. Provision should be made for local isolation with a lockable isolator fitted on or very close to the heat pump. A single 230v plug socket should also be fitted close to the unit to aid commissioning and future maintenance.

Lochinvar Amicus AquaStore Heat Pump Water Heater -
Connections

|
---|---

Energy label, product fiche and ErP data table are available at www.lochinvar.ltd.uk
For further information on the Amicus AquaStore heat pump water heaters, including ICM & user instructions and our full warranty terms and conditions, please visit our website: www.lochinvar.ltd.uk

Lochinvar - logo8 Lombard Way, The MXL Centre, Banbury, Oxon, OX16 4TJ
Tel: +44(0) 1295 269 981, Fax: +44(0) 1295 271 640, Email: info@lochinvar.ltd.uk
www.lochinvar.ltd.uk
Lochinvar Ltd reserves the right to change specifications without prior notice
LOC_23_0001 | LAAS | February 2023

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Lochinvar User Manuals

Related Manuals