INSTALLATION AND OPERATING INSTRUCTIONS
for all Hydrocarbon
BZ Refrigerator Models
BZ13 Black Merchandiser Series
User Manual for BZ Refrigerators
WELCOME
Thank you for purchasing a Beverage-Air cabinet. This series has passed our
strict quality control inspection and meets the high standards set by
Beverage-Air! You have made a quality investment that with proper maintenance
will give you many years of reliable service! Please read the following
installation and maintenance instructions before installing or using your
unit. If you have any questions, Please call our Technical Service Department
at 800-684-1199. 8:00 AM to 5:00 PM
EST.
Important Information
- PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR USING, IF RECOMMENDED PROCEDURES ARE NOT FOLLOWED, WARRANTY CLAIMS MAY BE DENIED.
- Your warranty registration information is located within this manual. Please complete the card and submit it to Beverage-Air within TEN days of installation. Failure to properly register equipment may limit or void the warranty.
- Beverage-Air reserves the right to change specifications and product design without notice. Such revisions do not entitle the buyer to corresponding changes, improvements, additions, or replacements for previously purchased equipment.
SAFETY
This appliance has been designed with your safety in mind. It has many
features to keep you from being harmed. However, safe operation and
maintenance are your responsibilities.
CAUTION
Use: When using this unit, please:
- Move it carefully. If on casters be sure the casters do NOT run over the power cord.
- Lock the casters when in use.
- Seek help. This machine is heavy! Be sure to move with enough help to avoid tipping or dropping the cabinet.
- Prevent children from playing in or on the cabinet. Persons unable to use this product must be prevented access.
- Follow all instructions. There are many safety labels and directions on the unit. Heed them.
- Watch your fingers. There may be pinch points near the door hinges.
CAUTION
Maintenance
Do NOT:
- Clean a frozen evaporator with a sharp object
- Clean a dirty condenser with a sharp object.
- Store gasoline, kerosene or any other flammable material near the cabinet.
Do ALWAYS
- Use a Beverage-Air recommended technician certified to repair R290 equipment.
- Use ONLY Beverage-Air factory service parts. Use of non OEM parts can be dangerous because of the design changes needed to safely use R290.
Important Information to Add
Record the model number, serial number and the date of installation here for
future reference. The model and serial numbers are on the unit’s serial number
dataplate, which is located on the left inside wall.
Model Number|
---|---
Serial Number|
Date of Installation|
Purchased From|
CAUTION
WARNING
Observe the Caution and Warning notices. They are indicators of important
safety information. Keep this manual for future reference.
CAUTION: If it is necessary to move the Refrigerator after removal from
the skid, remove all doors and carefully push the unit at a point of no more
than 36” from the bottom to avoid damage.
IMPORTANT INFORMATION
This unit is intended to be used in a commercial application. That includes
bars and restaurants.
If installed in a residence some commercial service companies may not be able
to service it on site.
The manufacturer has designed and produced this machine with the finest in
materials. The manufacturer assumes no liability for units that have been
altered in any way. Alterations or part substitutions will void the warranty.
Limitations
The machine is designed for use indoors in a controlled environment. It
must be kept dry, not overheated or subjected to excessive cold. May only be
connected to a dedicated electrical circuit. Extension cords are not
permitted.
| Minimum| Maximum
---|---|---
Voltage| 103.5| 126.5
Room Air Temp| 60º F| 80º F
Air Flow
Agency Approvals
These marks appear on the dataplate or serial tag, located in the inside of
the left wall. The dataplate also contains the model and serial numbers as
well as electrical requirements.
PRODUCT INFORMATION
Model| Cabinet Dimensions wx dx h(Inches)| Full Load Amps| Power Cord Plug
(NEMA)| Refrigerant Type / Charge (g) / Charge (oz)
---|---|---|---|---
BZ13HC-1| 30 x 32 3/4 x 54 3/8| 9.1| 5-15P| R-290 / 145 / 5.12
- Exterior finish is heavy duty steel with durable, baked on black or white coating.
- All models will maintain product temperature between 32 and 40 degrees F. at the factory setting of 38 F.
- All models are 115 volts, 60 Hz AC.
- ALWAYS REFERENCE YOUR EQUIPMENT DATA PLATE AMPS, REFRIGERANT AND REFRIGERANT CHARGE FOR THE MOST UP TO DATE AND ACCURATE VALUES.
- There are no access valves on the refrigeration system.
CLEARANCE AND PLACEMENT
Placement
Consider the following when selecting a location for your Refrigerator:
Clearance:
- 6.0in. at the top
- 3.0in.at the rear
- 0.0in. atthe left side
- 0.0in. attheright side
- 0.0inatthe bottom
Floor Load: the floor on which the Refrigerator is located must be even
and level, free from vibrations, and strong enough to support the combined
weights of the unit and maximum product load.
Ventilation: Grille area at front must be free and clear of any object or
wall.
Power Outlet: Dedicated power outlet is located within the length of the
unit’s power cord.
UNPACKING AND SET UP
Carefully inspect the shipping carton for damage. This is the only time that
shipping damage may be claimed. If damage is suspected, open the carton
immediately and, if there is damage, retain the carton and contact the shipper
to make a claim.
Do NOT contact the manufacturer.
Uncrating
Tools Needed: %” box wrench, adjustable wrench, level, flat head screw driver,
and box cutter.
-
Cut the stretch wrap along a corner post and remove the cardboard top capping and the corner posts.
-
Discard stretch wrap and any cardboard that will not be recycled.
Note : additional clear plastic protective wrap is applied directly to any product with a glass door. -
Move unit as close to final position as possible before removing the skid.
Note: The skid must be removed before the casters or legs can be attached.
Do NOT tip unit on its front or sides. If tipped onto the back, unit must not
be started for 3 hours.
Skid Removal and Caster Attachment
Tip the unit forward and remove the skid.
WARNING
Risk of personal injury.
Unit must be securely supported while attaching casters or legs.
- Remove the shipping bolts using the %” box wrench while cabinet is held in one direction. Repeat the process while the cabinet is held in the opposite direction.
- None of the threads on the leg or caster stem should be visible once screwed in.
- Tilt the cabinet in one direction approximately 8″ and block it securely with pieces of 2×4 lumber or other suitable material.
- Thread the stem casters or legs into the % -13 holes in the bottom of the cabinet. Tighten by hand as much as possible.
- Once the caster or leg cannot be turned any further, use a 3/4 inch wrench to tighten the nut in between the mounting plate and the wheel of the caster until snug.
- Repeat this procedure with unit secured in the opposite direction so as to access the remaining legs/ casters
- If plate casters or legs are installed instead of stem casters or legs, then repeat step 3 above and secure the plate with either #14 AB screws, or /%-20 screws, depending upon which are required.
Leveling:
Cabinets must be leveled when installed. Level should be measured on the
headrail.
Note: If no casters, legs or levelers are to be installed, the floor
below the equipment must be level
Failure to level your cabinet may result in door not sealing, closing
correctly, or condensed water draining not draining properly.
For cabinets with legs, rotate the foot of the leg with an adjustable wrench
to achieve desired height for leveling. For cabinets with casters, leveling
can be achieved by placing large washers in between the %’ stud and the holes
located on the bottom of the case.
Do NOT loosen casters to level the cabinet. Casters MUST be tightly secured to
cabinet for full strength.
CAUTION Install or attach any accessories that will be used
Remove any plastic covering the stainless steel.
SHELF INSTALLATION
- Determine the proper location for the shelf clips. The reference numbers on the pilaster can serve as a guide to ensure all clips are properly located.
- Insert the top tab of the shelf clip into the desired hole of the pilaster. The retaining tab MUST be facing up as shown.
- Rotate the clip downwards and insert the bottom tab into the matching hole in the pilaster. The clip may need to be squeezed slightly during installation.
- Install all remaining clips.
- Install shelves onto clips with the product retention bar facing up. Be careful not to dislodge clips during installation.
- Place shelves so that the retaining tab on the clip captures the shelf as shown.
- Confirm that the shelf is resting on ALL 4 clips and that the clips are securely attached to the pilasters.
- Improper shelf clip installation could cause the shelf and/ or the product on it to fall, resulting in damage to the unit and possible bodily injury.
- Do NOT overload the shelves. The unit is designed to use all shelves that are supplied in an equally spaced manner. Contact Beverage-Air customer service if fewer shelves or a different configuration to ensure shelf overloading will not occur.
ELECTRICAL
This is a cord-connected unit, and must be connected to its own dedicated
power supply. Check the dataplate on the machine to confirm the voltage and
per the dataplate use the correct fuses or HACR circuit breakers.
Note: Do not connect to GFI / GFCI outlets. Connection to that type of
outlet can result in product loss due to unsafe cabinet temperature when GFI
device trips from moisture.
Power Cord
This 115 volt model is equipped with a cord and 5-15P plug.
If the power cord becomes damaged, it must be replaced with the identical
cord.
Follow All National and Local Codes
This Unit Must Be Grounded. Do not use extension cords and do not disable or
by-pass ground prong on electrical plug.
Initial Start Up
Plug the power cord into the proper power supply.
The cabinet will soon begin to blow warm air out of the top area, and cool air
will flow from the inside blower.
The cabinet temperature has been set at the factory and should not need
adjustment, however if it was changed, the standard setting is 38°F.
Cautions
Care must be taken whenever moving or servicing the unit. The refrigerant is
contained in a sealed system, but if released it may be flammable.
USING THE UNIT – DANFOSS CONTROLLER
Operation is simple, just keep it connected to the correct power supply and
the refrigerator will maintain the internal temperature it has been set to.
Keep the doors and / or drawers closed as much as possible to avoid
unnecessary run time.
The controller displays the current internal temperature. Adjusting the set
temperature lower will NOT cause the system to lower the temperature faster.
When on, the refrigeration system is always operating at maximum. The
temperature was set at the factory at 38″ F, but you can adjust it to your own
selected temperature. 30 seconds after adjustment, the display automatically
reverts to showing the current temperature.
The Refrigerator will automatically defrost as needed, there is no set time
for defrost. Push and immediately release the “melting” or defrost button for
a manual defrost.
Note: Holding the defrost button in too long will shut the controller
off.
The internal fan will be on when the compressor is on and when the doors are
closed.
The compressor and condenser fan motor will only be on when the controller
senses an increase in internal cabinet temperature passed the set point.
In most cases the only thing displayed will be the cabinet temperature. When something other than normal operation has occurred, a message will be shown.
Message Displayed | Why | What to do |
---|---|---|
Unit is defrosting | Nothing. Normal operation. | |
Cabinet temperature too warm | Confirm doors or drawers are closed. | |
Compressor run time too long | Check doors closed. If yes, call for service. | |
Sensor unplugged or has failed | Call for service. |
SEQUENCE OF OPERATIONS REFRIGERATOR
The refrigerator operates based on the air temperature measured by the probe located at the return air.
| ON| OFF
---|---|---
COMPONENT| OPERATION| CONTROLLER ACTION| OPERATION|
CONTROLLER ACTION
COMPRESSOR| Compressor turns on when the air
temperature at the probe is above the
sum of the set point +2| The Compressor Contact is energized| Compressor turns
off when the air
temperature at probe is equal to or less than
the set point -2| The Compressor Contact is de- energized
(ERC 112 — Terminal #1)| (ERC 112 — Terminal #1)
CONDENSER FAN| The Condenser Fan turns on when the
Compressor is running| The Condenser Fan is wired directly to the
Compressor, not through the controller| The Condenser Fan turns off when the
Compressor is not running| The Condenser Fan is wired directly to the
Compressor, not through the controller
EVAPORATOR FAN| The Evaporator Fan runs continuously in refrigerators. When
the unit is plugged in, the Evaporator Fan will run.| The Evaporator Fan is
connected directly to incoming power, not through the controller.| The
Evaporator Fan runs continuously.
When the unit is plugged in, The Evaporator Fan will run.| The Evaporator Fan
is connected directly to incoming power, not through the controller.
Condition| Compressor| Compressor Fan| Compressor Fan
---|---|---|---
Cabinet Temp > Set point + 2| ON| ON| ON
Cabinet Temperature <= Set point – 2| OFF| OFF| ON
Defrost| OFF| OFF| ON
Electronic Controller
Control Panel Display
| Defrost LED|
| Alarm LED
---|---|---|---
On fixed:| Defrost active| On fixed:| ALARM Present
Off:| Defrost is off| Flashing:| ALARM Silenced
| | Off:| No Alarm
| Fan LED|
| Compressor LED
On fixed:| Fan active| On fixed:| Compressor active
Off:| Fan Off| Flashing:| Delay, protection or activation blocked
| | Off:| No Alarm
NOTE: When switched on, the instrument panel performs alamp test for a
few seconds.
Keyboard Functions
UP
Quick press and release
-
Increases Set Point
Long press and release ; . -
Increases display brightness
DOWN
Quick press and release
-
Decreases Set Point
Long press and release -
Decreases display brightness
DEFROST (ESC)
Quick press and release
-
Activates manual defrost
Long press and release -
Controller enter stand-by mode
SET (ENTER)
Quick press and release
-
No Function
Long press and release -
Toggles display °F/°C
Note: When the controller is in a Standby Mode, a blue dot will be displayed as shown here. To switch out of Standby Mode, push and hold the Defrost button until the display reads ON.
CONTROL PANEL CONNECTIONS
Changing the Set point
The alarm condition is always signaled by the alarm icon .
Press any button to silence the alarm, the relative icon will continue
flashing.
Alarm Code| Trigger| Automatic Clearance| Outputs|
Comments
---|---|---|---|---
“Hi”| Air temperature is higher than “ALA->Hat. for “ALA->Htd”| User
configured| Blink “Hi” with the highest temperature; If configured: cut in
alarm relay, beep the buzzer| High temperature alarm
“Lo”| Air temperature is lower than “LAt” for “Ltd”| User configured| Blink
“Lo” with the lowest temperature. If configured: cut in alarm relay, beep the
buzzer| Low temperature alarm
“Con”| Condenser temperature is too high or too low| User configured| Blink
“Con”. If configured: cut in alarm relay, beep the buzzer| Condenser alarm
“dor”| Door open for more than| Always| Blink “dor”. If configured: cut in
alarm relay, beep the buzzer| Door open alarm
“uHi”| Line voltage is higher than “Cop- >uHi”| Always| Blink “uHi”. If
configured: cut in alarm relay, beep the buzzer| High voltage alarm
“uLi”| Line voltage is higher than “Cop- >uLi”| Always| Blink “uLo”. If
configured: cut in alarm relay, beep the buzzer.| Low voltage alarm
“LEA”| Compressor continuous running for more than “ALA->LEA”| Always| Blink
“LEA”. If configured: cut in alarm relay, beep the buzzer| Leakage alarm
“E01”| “S1” error| Always| Blink “E01”. If configured: cut in alarm relay,
beep the buzzer| “S1” sensor failure (short or open)
“E02”| “S1” error| Always| Blink “E02”. If configured: cut in alarm relay,
beep the”S2″ buzzer| sensor failure (short or open)
“E03”| “S1” error| Always| Blink “E03 “.If configured: cut in alarm relay,
beep the buzzer| “S3” sensor failure (short or open)
“E04”| “S1” error| Always| Blink “E04 “. If configured: cut in alarm relay,
beep the buzzer| “S4” sensor failure (short or open)
How to Acknowledge Alarms:
NOTE: If alarm exclusion times are in progress (ALA folder of the
parameter table), the alarm is not signaled.
- The alarm code flashing alternately th the temperature and the alarm symbol is displayed
- After the acknowledge temperature is displayed and the alarm symbol remains shown
USING THE UNIT – ELIWELL CONTROLLER
Operation is simple, just keep it connected to the correct power supply and
the refrigerator will maintain the internal temperature it has been set to.
Keep the doors and / or drawers closed as much as possible to avoid
unnecessary run time.
The controller displays the current internal temperature.
Adjusting the set temperature lower will NOT cause the system to lower the
temperature faster. When on, the refrigeration system is always operating at
maximum.
The temperature was set at the factory at 35° F, but you can adjust it to your
own selected temperature. 30 seconds after adjustment, the display
automatically reverts to showing the current temperature.
The refrigerator will automatically defrost as needed, there is no set time
for defrost. Push and immediately release the “melting” or defrost button for
a manual defrost. The internal fan will be on when the unit is plugged in. The
compressor and condenser fan motor will only be on when the controller senses
an increase in internal cabinet temperature passed the set point.
In most cases the only thing displayed will be the cabinet temperature. When something other than normal operation has occurred, a message will be shown.
Message Displayed | Why | What to do |
---|---|---|
dEF | Unit is defrosting | Nothing. Normal operation. |
AH1 | Cabinet temperature too warm | Confirm doors or drawers are closed. |
El, E2, E3, E4 | Sensor unplugged or has failed | Call for service. |
SEQUENCE OF OPERATIONS REFRIGERATOR
The refrigerator operates based on the air temperature measured by the probe
located at the return air.
| ON| OFF
---|---|---
COMPONENT| OPERATION| CONTROLLER ACTION| OPERATION|
CONTROLLER ACTION
COMPRESSOR| Compressor turns on when the air temperature at the probe is
above the sum of the set point + 4| The Compressor Contact is energized|
Compressor turns off when the air temperature at probe is equal to or less
than the set point| The Compressor Contact is de-energized
(EW+978 – Terminal #1)| (EW+978 – Terminal #1)
CONDENSER FAN| The Condenser Fan turns on when the Compressor is
running| The Condenser Fan is wired directly to the Compressor, not through
the controller| The Condenser Fan turns off when the Compressor is not
running| The Condenser Fan is wired directly to the Compressor, not through
the controller
EVAP FAN| The Evaporator Fan turns on when the unit is
powered on.
| The Evaporator Fan is wired to constant power| The Evaporator Fan turns off
when the unit is unplugged or put into standby.| The Evaporator Fan is wired
to constant power
Some models will be wired to the fan relay (EW+978 – Terminal #3)| Some models
will be wired to the fan relay (EW+978 – Terminal #3)
Condition| Compressor| Compressor Fan| Compressor Fan
---|---|---|---
Cabinet Temp > Set point + 4| ON| ON| ON
Cabinet Temperature <= Set point – 4| OFF| OFF| ON
Defrost| OFF| OFF| ON
Electronic Controller
Controller Symbols
| Reduced SET / Economy Permanently on: Energy Saving Mode Flashing:
Reduced Set Mode Quick Flashing: Access to level 2 parameters| | AUX
Permanently on: Aux Active Flashing: Deep Cooling Cycle Active
---|---|---|---
| Compressor
Permanently On: Compressor Active Flashing: Delay, protection or blocked
start-up| | Defrost
Permanently on: Defrost Active Flashing: Manual or D.I. activation
| Alarm
Permanently on: Alarm Active Flashing: Alarm Acknowledged| | Fan
Permanently on: Fans Active
| Celsius
Permanently On: C Setting| | Fahrenheit
Permanently on: iF Setting
Controller Buttons
| Up
Press and release
· Scrolls through menu items
· Increases Values
Press for at least 5 seconds
· Activates the manual defrost| | Stand-by
Press and release
· Returns to the previous menu level
· Confirm parameter value
Press for at least 5 seconds
· Activates the stand-by function
---|---|---|---
| Down
Press and release
· Scrolls through menu items
· Decreases values
Press for at least 5 seconds
· No Function| | Set (Enter)
Press and release
· Displays alarms
· Opens the machine status menu
Press for at least 5 seconds
· Opens the programming menu
· Confirms commands
Electronic Controller Alarms
Alarms are always indicated by the buzzer (if present) and the alarm icon. To
switch off the buzzer, press and release any key, the relative icon will
continue to flash.
NOTE: If alarm exclusion times have been set (see AL folder in the
parameters table), the alarm will not be signaled.
Alarm Code| Trigger| Automatic Clearance| Outputs|
Comments
---|---|---|---|---
“AHl”| pm probe HIGH Temperature alarm| User configured| Label A1-11 displayed
alternately with the actual value read by the probe Pb1| High temperature
alarm
“ALl”| Pb1 probe LOW Temperature alarm| User| Label ALl displayed alternately
with the actual value read by the probe Pb1| Low temperature alarm
“OPd”| Door open for more than| Always| Label OPd displayed alternately with
the actual value read by probe PIA.| Door open alarm
“El”| “El” error| Always| Blink “El “. If configured: cut in alarm relay, beep
the buzzer| “PB1” sensor failure (short or open)
“E2”| “E2” error| Always| Blink “E2”. If configured: cut in alarm relay, beep
the buzzer| “PB2” sensor failure (short or open)
“E3”| “E3” error| Always| Blink “E3 “. If configured: cut in alarm relay, beep
the buzzer| “PB3” sensor failure (short or open)
“E4”| “E4” error| Always| Blink “E4 “. If configured: cut in alarm relay, beep
the buzzer| “PB4” sensor failure (short or open)
CLEANING AND MAINTENANCE
Cleaning Schedule:
Cabinet Condenser coil
Daily wipe down Quarterly cleaning
Weekly interior
Gaskets Routine maintenance
Daily inspection, check Annually that hinges are tight to the cabinet.
Daily Exterior Cleaning
It is much easier to clean on a regular basis than to have to remove stains
once they have built up.
- Wash with a clean sponge and a mild detergent that does not contain chlorine.
- Rinse with clean water.
- Dry with a soft cloth.
- Polish with a soft cloth, wiping with the grain.
- Wipe weekly with stainless steel cleaner.
Weekly Interior Cleaning
- Remove all food, food related items and shelves. Store the food at a safe temperature.
- Disconnect power to the unit (unplug it or switch the breaker off).
- Remove all loose food particles from the inside walls, floor, door liner and ceiling.
- Scrub allinterior surfaces and door gaskets with a warm (100°F to 110°F) detergent solution and a soft scrub brush.
- Rinse with clean water and allow to air dry.
- Return the shelves to the unit and secure them.
- Restore power.
- Return food to the unit when it has reached a safe temperature.
CONDENSER CLEANING
Keeping the condenser coil clean is critical to efficient operation.
-
Unplug unit from power supply.
CAUTION
Rotating fan blade can cause personal injury. Unplug unit from power supply before beginning to clean condenser -
Remove the single Phillips head screw at the bottom of the front panel
-
Lift upwards on the front panel to remove
-
Examine condenser surface, if dusty, brush and vacuum the dust and lint from the surface of the coil. Brush up and down to avoid damaging the fins. Use care to not disturb the wires connected to the controller.
Note: If the coil is greasy, the coil will need to be cleaned with coil cleaner and that should be left to an experienced technician. -
To reinstall the front panel line up the keeper screws behind the panel and firmly pull downwards
-
Reinstall the Phillips head screw
-
Return grill to unit.
Note: Air filters are not recommended as they restrict the flow of cooling air.
METHODS FOR CLEANING EXTERIOR BAKED ON FINISH
Cleaning Needed| Cleaning Agent| Method of Application|
Affect on Finish
---|---|---|---
Smears and fingerprints| Areal 20, Lac-O-Nu, Lumin Wash O’Cedar Cream Polish,
Stainless Shine.| Rub with cloth as directed on the package.| Satisfactory for
use on all finishes. Provides barrier film to minimize prints.
Stubborn Spots and Stains, and Other Light Discolorations| Allchem
Concentrated Cleaner.| Apply with damp sponge or cloth. Rub with damp cloth.|
Use in direction of polish lines on No. 4 (polished) finish. May scratch No. 2
(mill) and Nos. 7 and 8 (polished) finishes.
Samae, Twinkle or Cameo Copper Cleaner| Rub with damp cloth.
Grade FFF Italian pumice, whiting, or talc.| Rub with dry cloth.
Liquid NuSteel Paste NuSteel or DuBois Temp. Copper’s Stainless Steel Cleaner
Revere Stainless Cleaner Household cleansers, such as Old Dutch, Lighthouse,
Sunrise, Wyandotte, Bab-O, Gold Dust, Sapolio, Bon Ami, Ajax, or Comet Grade F
Italian Pumice, Steel Bright, Lumin Cleaner, Zud, Restore, Sta-Clean, or
Highlite. Penny-Brite or Copper-Brite.| Use small amount of cleaner. Rub with
dry cloth using a small amount of cleaner. Apply with damp sponge or cloth.
Rub with a damp cloth. May contain chlorine bleaches. Rinse thoroughly after
use. Rub with a damp cloth. Rub with a dry cloth using a small amount of
cleaner.
Heat tint or discoloration| Penny-Brite or Copper-Brite. Past NuSteel, DuBois
Temp, or Termite. Revere Stainless Steel Cleaner. Allen Polish, Steel Bright,
Tenacious Deposits, Rusty Discolorations, Industrial Atmospheric Stains
Wyandotte, Bab-O or Zud.| Rub with a dry cloth. Rub with a dry cloth or stain-
less steel wool. Apply with damp sponge or cloth. Rub with a damp cloth.
Grease Fatty Acids, Milk stone (where swabbing or rubbing is not practical)|
Easy-Off, De-Grease-It, 4 to 6% hot solution of such agents as trisodium
phosphate or sodium tripolyphosphate or 5 to 15% caustic soda solution| Apply
generous coating. Allow to stand for 10-15 minutes. Rinse. Repeated
application may be necessary.| Excellent removal, satisfactory for use on all
finishes.
Tenacious Deposits, Rusty Discolorations, Industrial Atmospheric Stains|
Oakite No. 33, Dilac Texo 12, Texo NY, Flash-Klenz, Caddy Cleaner, Turco Scale
4368 or Permag 57.| Swab and soak with clean cloth. Let stand 15 minutes or
more according to directions on package, then rinse and dry.| Satisfactory for
use on all finishes
Hard Water Spots and Scale| Vinegar. 5% oxalic acid, 5% sulfamic acid, 5 to
10% phosphoric acid, or Dilac, Oakite No. 33, Texo 12, Texo N.Y.| Swab or wipe
with cloth. Rinse with water and dry.
Swab or soak with cloth. Let stand 10-15 minutes. Always follow with
neutralizer rinse, and dry.| Satisfactory for all finishes. Satisfactory for
all finishes. Effective on tenacious deposits or where scale has built up.
HELP
Trouble Diagnosis for the User
Malfunction| Possible Cause| Likely Solution
No cooling – unit is silent| Unit not plugged in. Fuse or circuit breaker
tripped. Power cord plug loose in outlet.| Connect to proper voltage circuit
Replace fuse or reset breaker.
Check outlet for loose connection, replace as needed
Unit cools but seems to be on all the time| Dirty condenser| Clean condenser
Space temperature too high| Dirty condenser Evaporator iced over Unit in high
temperature environment| Clean condenser Defrost evaporator Reduce temperature
of room
Space temperature too low| Temperature control| Adjust or replace control
Trouble Diagnosis for the Technician
No cooling – compressor does not hum| Temp control stuck in open position|
Replace temp control.
No cooling – compressor hums but does not start| Low voltage to unit.
Compressor starting system failure| Check voltage, correct as needed. Check
start relay and start capacitor. See next step.
No cooling – compressor starts but shuts off| Compressor start relay failure
Compressor start capacitor failure| Replace relay. Replace capacitor.
No cooling – compressor cycles on and off| Overheating weak overload| Clean
condenser, check fan motor and blade. Check refrigerant charge. Replace
overload.
Unit cools, but is slow to pull cabinet temperature down| Evaporator fan not
turning| Check fan(s), on multiple fan units one fan may be turning slowly and
will need to be replaced.
Unit cools but turns on and off frequently| No product in cabinet. Temperature
control defective Refrigeration issue| Fill cabinet Replace control Have
system checked
Makes excessive noise| Tubing rattle Loose parts Bent or broken fan blade
Noisy fan motor| Check tubing for routing Check for loose components Replace
fan blade Replace fan motor
FOR THE SERVICE TECH – R290
Refrigeration service should only be attempted by a trained trade professional
certified to work on R290 systems.
Here are some critical service items.
This list does not qualify anyone to service the unit. Itis a reminder and
checklist for the service tech. Keep these in mind for R290 service:
- Wire nuts are NOT to be used when changing an electrical part.
- The switches in this product are sealed, only exact replacements may be used.
- The process tubes are to be used for service access.
- Cut out (with tubing cutter) refrigeration components that are to be replaced. Do NOT un-braze.
- Because R290 can be vented into the air during service, the venting MUST be in an area free from flame or spark. It must be near an opened window or door.
- A signnoting service of a system containing propane must be attached to the unit during refrigeration service.
- A combustible gas leak detector must be used to inform anyone in the area when propane is present in the air.
Other Information:
Evacuation: It is critical that a refrigeration system be leak free and
internally dry. A thorough evacuation with a good vacuum pump with a micron
gauge attached is the only way to ensure that the system is dry and ready for
a charge of refrigerant.
Charging: The system is critically charged and the proper type and amount
MUST be weighed in.
Overcharge symptoms: Unit will cool properly but the suction line
temperature will be unusually cold.
Compressor run time will be longer than normal.
Undercharge symptoms : Long run time, poor cooling and a hot compressor
dome are the main symptoms of an undercharge.
FOR THE SERVICE TECH – WIRING DIAGRAM DANFOSS
REPLACEMENT PARTS
| Part #| Description
---|---|---
1| 706-165D-02 (Blue Sign Well) 706-165D-03 (Black Sign Well) 706-165D-18
(White Sign Well) 706-165D-20 (Alum Grey Sign Well)| Top Grille (1)
2| 409-467D- (Last 2 Digits Will Vary)| Sign Insert for Top Grille (1)
3| 403-761D| Pilaster (2)
4| 403-168A| Pilaster Clips (6)
5| 403-749D-01 (White Wire)
403-749D-02 (Black Wire)| Shelves (3)
6| 403-750D-01 (White)
403-750D-02 (Black)| 20 oz. Divider (3)
7| 59D33-032D-01AB (White)| Rear Pilasters (2)
8| 706-166D-01 (Black)
**706-166D-02 (Blue)
706-166D-18 (White)
706-166D-20 (Alum Grey)| Front Grille (1)
9| 305-471D| Condenser Coil (1)
10| 501-192D-03| Condenser Fan (1)
11| 49A51-214D| Capillary Tube (1)
12| 305-172C| Evaporator Coil (1)
13| 501-190D-05| Evaporator Fans (2)
14| 312-213D| Compressor (1)
15| 303-241D| Dryer (1)
16| 317-036B| Start Components (1)
LIMITED WARRANTY
WARRANTY (Warranty valid in USA and Canada)
THREE (3) YEAR PARTS AND LABOR WARRANTY:
Beverage-Air Corporation warrants to the original purchaser of Beverage-Air
branded equipment, including all farts thereof, that such equipmentis free
from defects in material and workmanship, under normal use, proper
maintenance, and service as indicated by Beverage-Air installation and
operation instructions, for a period of three E3) ears from the date of
installation, or thirty-nine (39) months from the data of shipment from the
manufacturer, whichever is earlier.
ADDITIONAL TWO (2) YEAR COMPRESSOR PART WARRANTY”:
In addition to the warranty set forth above, Beverage- Air warrants the
hermetically/semi-hermetically sealed compressor (part only) for an additional
TWO (2) years beyond the first THREE {3) ears warranty period; not to exceed
sixty-three (63) months from the date of shipment from Beverage-Air, provided
upon receipt of the compressor, manufacturer examination shows the sealed
compressor to be defective. This extended warranty does not cover freight for
the replacement compressor or freight for the return of the failed compressor.
- Units shipped after 07/01/2024. Previous warranty applies to units shipped prior. EXCEPTIONS:
- CT96 and CF3 models carry a ONE (1) year parts and labor warranty, limited to fifteen HS) months from date of shipment from Beverage-Air. These are excluded from additional compressor warranty.
- SR/SF (Slate) models carry a TWO (2) year parts and labor warranty, limited to twenty-seven (27) months from date of shipment from Beverage-Air.
- BZ, VM, CDR, DPCR, MT and Blast Chillers carry a THREE (3) year ;arts and labor warranty; additional TWO (2) years compressor part only.
- Units installed in Residential applications will be not covered under this warranty. Units are intended for Commercial use only.
Also, this compressor-part only warranty does NOT apply to any electrical
controls, condenser, evaporator, fan motors, overload switch, starting relay,
capacitors, temperature control, filter/drier, accumulator, recreation tubing,
wiring harness, labor charges, or supplies which are covered by the warranty
above.
Note: 3rd party extended warranties are not covered by this warranty
statement.
Normal wear parts, as deemed by Beverage-Air, such as but not exclusive to,
light bulbs/lamps and gaskets are not covered by this warranty. For the
purpose of this warranty, the original purchaser shall be deemed to mean the
individual or company for who the product was originally installed.
Units that utilize variable speed compressor technology can experience
nuisance tripping on Class A GFCl outlets which have a trip limit of 4 mA to 6
mA. To avoid this issue in a location that requires GFCI circuit protection,
Beverage-Air & Victory recommends using a HUBBELL Model Number GFRST83W 20A
Heavy Duty Hospital Grade Self-Test GFCI Receptacle. Nuisance tripping not
covered under warranty. Our obligation under this warranty shall be limited to
repairing or replacing, including labor, any part of such product, which
proves thus defective. Beverage-Air reserves the right to examine any product
claimed to be defective and request photos of the unit prior to dispatching
service. Moisture or water damage is not covered under warranty. If service is
deemed non- warranty, Beverage-Air reserves the right to bill the end user for
service.
The labor warranty shall be for self-contained units only and for standard
straight time, which is defined as normal service rate time, for service
performed during normal working hours. All warranty labor will be covered at
standard time. Any service requested outside of a servicer’s normal working
hours including weekends and any additional overtime will be at the
responsibility of the equipment purchaser. Any part or accessory determined to
be defective in the product should be returned to the company within thirty
(30) days under the terms of this warranty and must be accompanied by a record
of the cabinet model, serial number, and identified with a return material
authorization number (RMA#) issued by the manufacturer.
Special installation/applications, including remote locations, are limited in
coverage by this warranty.
Any installation that requires extra work, and/or travel, to gain access to
the unit for service is the sole responsibility of the equipment purchaser.
Improper operation resulting from factors, including but not limited to,
improper or negligent cleaning and maintenance, improper installation, low
voltage conditions, inadequate wiring, outdoor use (unless otherwise
specified) and accidental damage are not manufacturing defects and are
strictly the responsibility of the purchaser.
With the exception of Blast Chillers, the product is designed for maintaining
temperature and not bringing food to a desired temperature and therefore
cannot be held responsible for this function under warranty. Units must be in
a conditioned environment or warranty will be void. Non-standard use of unit
can also be subject to reduced or voided warranty. Condensing coils must be
cleaned at regular intervals as a part of preventative maintenance for optimal
performance. Failure to do so is subject to a voided warranty. Although
cleaning requirements vary in accordance with operation of various products,
Beverage-Air recommends a minimum monthly cleaning.
NO CLAIMS CAN BE MADE AGAINST THIS WARRANTY FOR SPOILAGE OF FOOD, PRODUCTS,
LOSS OF SALES OR CONSEQUENTIAL DAMAGES.
THE FOREGOING WARRANTIES ARE EXPRESSLY GIVEN IN LIEU OF ALL OTHER WARRANTIES,
EXPRESS, IMPLIED, OR STATUTORY, INCLUDING THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE HEREBY
DISCLAIMED, ALL OTHER OBLIGATIONS OR LIABILITIES ON OUR PART, AND WE NEITHER
ASSUME, NOR AUTHORIZE ANY OTHER PERSON TO ASSUME FOR US, ANY OBLIGATION OR
LIABILITY IN CONNECTION WITH THE SALE OF SAID REFRIGERATION UNITS OR ANY PARTS
THERE OF.
This warranty shall not be assignable and shall be honored only in so far as
the original purchaser. This warranty does not apply outside the limits of the
United States of America and Canada, nor does it apply to any part that has
been subject to misuse, neglect, alteration, accident, or to any damage caused
by ga sortation, flood, fire, acts of terrorism, or acts of god.
LIMITATION OF LIABILITY:
Beverage-Air Corporation or their affiliates shall not be liable for any
indirect, incidental, special or consequential damages, or losses of a
commercial nature arising out of malfunction equipment or its parts components
thereof, as a result of defects in material or workmanship.
THE ORIGINAL OWNER’S SOLE AND EXCLUSIVE REMEDY AND BEVERAGE-AIR’S SOLE AND
EXCLUSIVE LIABILITY SHALL BE LIMITED TO THE REPAIR OR REPLACEMENT OF PARTS OR
COMPONENTS CONTAINED IN THE EQUIPMENT IDENTIFIED ABOVE WHICH UNDER NORMAL USE
AND SERVICE MALFUNCTION AS A RESULT OF DEFECTS IN MATERIAL OR WORKMANSHIP,
SUBJECT TO THE APPLICABLE PROVISIONS AND LIMITATIONS STATED ABOVE.
Note: Additional Terms and Conditions of sale may apply.
Notice: Specifications are subject to change without notice. Contact
Beverage-Air for specific model agency approval. All prices are ex-works
Brookville, PA. July 1, 2024
Warranty Registration
Register your product online at beverage:com/parts-service or fill out and mail the form below.
Cabinet Model Number:————————
Date Of Installation:———————
Cabinet Serial Number:———————-
Location Of Product————
Business Name:————-
Business Street:————
Business City:————
State:—————-
Postal Code:———————
Mail to: Beverage-Air, 3779 Champion Blvd, Winston-Salem, NC 27105
Rev. 07/24
3779 CHAMPION BLVD, WINSTON-SALEM, NC 27105
Phone: 888-845-9800
Fax: 800-253-5168
Web: beverage-air.com
809-236A Rev. B. 07/15/2024
BZ13-1-B
SEE BACK COVER FOR
WARRANTY REGISTRATION
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>