REZNOR CK Series Gas Fired Low Intensity Radiant Tube Heaters Installation Guide
- September 11, 2024
- Reznor
Table of Contents
REZNOR CK Series Gas Fired Low Intensity Radiant Tube Heaters
Specifications
- Product Name: Suspension Kit for Gas-Fired Low-Intensity Radiant Tube Heaters
- Model Options: CK53, CK54, CK55, CK56
- Material: Steel hanger kit, Stainless steel hanger kit, Steel turnbuckle kit, Stainless steel turnbuckle kit
- Components: Refer to Table 1 for detailed components
Product Usage Instructions
- Installation should be done by a qualified service agency following the provided instructions to avoid property damage or injury.
- Note: Use turnbuckles with a hanger kit for leveling the system during heater suspension.
- Before installation, ensure all components listed in Table 1 are available.
FAQ
- Q: Can the heater suspension points be adjusted?
- A: Yes, the tube suspension points can be adjusted slightly to adapt to the structure.
- Q: How many suspension points are required for different tube configurations?
- A: Each straight tube must have at least one suspension point. Straight tubes downstream and adjacent to an L-tube or U-tube require two suspension points.
SUSPENSION KIT INSTALLATION FOR GAS-FIRED LOW-INTENSITY RADIANT TUBE HEATERS
OPTIONS CK53, CK54, CK55, AND CK56 FOR MODELS VZ AND VZH
GENERAL INFORMATION
DANGER
These kits are to be installed by a qualified service agency by these
instructions and in compliance with all codes and requirements of authorities
having jurisdiction. Improper installation, adjustment, alteration, service,
and/or maintenance can cause property damage, injury, or death. The qualified
agency performing this work assumes responsibility for this installation.
NOTE: For heater suspension, the use of turnbuckles with a hanger kit is
recommended for convenience in leveling the system. Refer to these
instructions along with the installation manual provided with the heater for
complete heater suspension instructions.
- Refer to the installation manual provided with the unit for important safety information.
KIT COMPONENTS
- When installing the hanger kit and/or turnbuckle kit, ensure that all components listed in Table 1 are available before beginning installation.
Table 1. Suspension Kits
Option| Description| PN
CK53| Steel hanger kit| 270725
CK54| Stainless steel hanger kit| 270717
CK55| Steel turnbuckle kit| 1047421
CK56| Stainless steel turnbuckle kit| 1047422
NOTE: Hanger kits include eleven (11) S-hooks and 50 feet of chain. Turnbuckle kits include two (2) turnbuckles and two (2) hex nuts. Refer to Table 2 for the minimum number of kits needed (may vary depending on the length of the suspension hardware).
Table 2. Kit Quantities
Heater Configuration| Turnbuckle Kit| Hanger Kit
Minimum Number of Kits Needed
10-foot straight tube| 1| ****
1
20-foot straight tube| 2
30-foot straight tube or 20-foot L- or U-tube| 3
40-foot straight tube or 30-foot L- or U-tube| 4
50-foot straight tube or 40-foot L- or U-tube| 5
60-foot straight tube or 50-foot L- or U-tube| 6| 2
70-foot straight tube| 7
DO NOT DESTROY. PLEASE READ CAREFULLY. KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
INSTALLATION
DANGER
The installer is responsible for installing the field-supplied structure
suspension point hardware and for adequately supporting the weight of the
heater.
WARNING
The heaters are designed so that the tube suspension points can be adjusted
slightly to adapt to the structure. Each straight tube must have at least one
suspension point. Straight tubes downstream and adjacent to an L-tube or
U-tube require two suspension points.
CAUTION
A minimum of 12 inches (305 mm)—the total length of chain, S-hook, and/or
turnbuckle—is required between the tubes and the structure suspension points.
-
Suspend heater under installation manual provided with heater using S-hooks, chain, and turnbuckles (as necessary) at all suspension points.
-
To install turnbuckles:
-
Remove the right-hand thread eyebolt from the turnbuckle (see Figure 1) and install the hex nut on the eyebolt with the nut’s teeth away from the eye.
CAUTION -
DO NOT tighten (lock) the hex nuts against the turnbuckles until the system is leveled. Locking the hex nuts against the turnbuckles is required to prevent the turnbuckles from turning when the system expands.
-
Thread eyebolt back into turnbuckle. DO NOT tighten (lock) the hex nut against the turnbuckle at this point.
-
Level the heater and THEN tighten (lock) the hex nut against each turnbuckle.
-
CONTACT
- Specifications and illustrations are subject to change without notice or incurring obligations.
- The latest version of this manual is available at www.reznorhvac.com.
- ©2024 Nortek Global HVAC LLC, O’Fallon, MO. All rights reserved.