The RHC21 Condensate Kit contains the following:REZNOR-RHC21-4000-Gas-
Fired-Heating-Modules-FIG- \(1\)

To Fit The Kit

  1. Attach silicone hose to condensate outlet on RHC unit and secure with wire kit
  2. Cut the tubing to the required length; route the tubing around obstacles using Barbed Elbows as required
  3. Create Hole Ø46 in the vestibule outer panel (If Fitted) ensuring the hole created is lower than the condensed outlet from the collector box. Fit Grommet to the hole and feed the tubing through.

Notes on Condensate Disposal

FOLLOW LOCAL REGULATIONS FOR THE CORRECT DISPOSAL OF CONDENSATE.

  • All RHC21 gas-fired heating modules are designed with a built-in drain connection. A PVC condensate discharge pipe should be run by the installer to connect the drain from the unit to the nearest foul drainage point. A trap should be fitted in the line and filled prior to use.
  • A condensate disposal system that relies on gravity should be satisfactory for most installations. If a gravity system is not possible, a condensate pump must be installed. There are a number of commercially available pumps made for this purpose. If using a condensate pump, follow the pump manufacturer’s installation recommendations.
  • Condensate drainpipe connections must be glued, to prevent condensation water from dripping from the drainpipe. The condensate water coming from the unit heater has a pH level of approximately 4.6 and can affect materials made from zinc and/or copper, hence it is strongly advised against letting the condensation water flow off through the gutter.
  • To ensure the condensation water does not freeze, it is recommended to mount the drainpipe inside the building. If there is no other choice but to mount it outside, it is strongly recommended to equip it with frost-proof insulation. For external units, it may be necessary to fit trace heating to the condensation pipe to prevent freezing.

NORTEK GLOBAL HVAC (UK) LTD
Fens Pool Avenue Brierley Hill
West Midlands DY5 1QA United Kingdom
Tel +44 (0)1384 489700
Fax +44 (0)1384 489707
Email: reznorsales@nortek.com.
Website: www.reznor.eu

Current full Part No.

Installation Instruction
RHC21 Condensate Kit
EN September 2021 D301415 Issue 0.

Nortek Global HVAC is a registered trademark of Nortek Global HVAC Limited. Because of the continuous product innovation, Nortek Global HVAC reserves the right to change product specifications without due notice.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals