REZNOR RHC21-P Air Heater Modules Instruction Manual

June 8, 2024
Reznor

**REZNOR RHC21-P Air Heater Modules

**

INTRODUCTION

This addendum has been produced for the propane fired (RHC21-P) version of the RHC21 4000 and RHC21 8000 Air Heater Module. This addendum highlights the differences between the RHC21-P and the standard RHC21 4000 and RHC21 8000 Air Heater Module.

This addendum must be read in conjunction with the applicable RHC21 4000 or RHC21 8000 Air Heater Module Installation Manual. Particular attention must be paid to the “Important Notice to Installers” and Health and Safety” Sections of the installation manual.

This addendum does not supersede or replace the applicable RHC21 4000 or RHC21 8000 Air Heater Installation Manual in any way.

RHC21-P air heaters are designed to operate on propane gas (G31). Refer to the technical data given on pages 3 to 6 inclusive of this document and to the data plate on the air heater module for details of supply pressures.

Technical Data RHC21 4000 Series

This table replaces “Table 1 – Specifications” given on Page 8 of the RHC21 4000 Installation Manual

Model| 4024-05-P| 4050-06-P| 4060-07-P| 4075-09-P| 4100-12-P
---|---|---|---|---|---
Combustion air & flue type Indoor| B23 / B53 / C13 / C33 / C53
Combustion air & flue type External| Rooftop
Heat Input High Fire (Hs) 1| kW| 28.80| 61.50| 77.60| 91.50| 120.00
Heat Input Low Fire (Hs) 1| kW| 18.60| 16.00| 23.00| 32.00| 37.00
Heat Input High Fire (Hi) 2| kW| 26.42| 56.42| 71.19| 83.94| 110.09
Heat Input Low Fire (Hi) 2| kW| 17.06| 14.68| 21.10| 29.36| 33.94
Heat Output H2 High Fire 4| kW| 24.09| 52.43| 66.22| 78.06| 103.05
Heat Output H2 Low Fire 4| kW| 16.45| 14.58| 20.88| 29.02| 33.59
Gas Consumption High Fire (Hs) G31 3| m³/h| 1.08| 2.31| 2.92| 3.44| 4.51
Gas Consumption Low Fire (Hs) G31 3| m³/h| 0.70| 0.60| 0.87| 1.20| 1.39
Gas Consumption High Fire (Hs) G31 3| l/h| 4.02| 8.58| 10.83| 12.77| 16.75
Gas Consumption Low Fire (Hs) G31 3| l/h| 2.60| 2.23| 3.21| 4.47| 5.16
Gas Consumption High Fire (Hs) G31 3| kg/h| 2.06| 4.40| 5.55| 6.54| 8.58
Gas Consumption Low Fire (Hs) G31 3| kg/h| 1.33| 1.14| 1.64| 2.29| 2.64
Gas Service Connection| 1/2″| 3/4″| 3/4″| 3/4″| 3/4″
Flue & Combustion Air Connection Collars

(Indoor)

| Ø mm| 100| 130| 130| 130| 130
Condensation Connection / Outlet| Ø mm| 22 OD
Minimum V1 Airflow at 15°C with Heat Output H1 6| m³/h| 2500| 3900| 4700| 5700| 7500
kW| TBA| TBA| TBA| TBA| TBA
Temperature Rise at V1 Airflow| K| TBA| TBA| TBA| TBA| TBA
Minimum V2 Airflow at 15°C with Heat Output H2 5| m³/h| 2880| 5950| 7150| 8800| 11700
Temperature Rise at V2 Airflow| K| 25| 26| 28| 26| 26
Electrical Connection| 1 Phase| 230V 1N~50Hz
Total Electric Rating| kW| 0.08| 0.30| 0.30| 0.30| 0.28
Appliance Weight (net)| kg| 31| 90| 100| 120| 149
Protection Grade| IP| 20 (Indoor) / X4D (External)

  1. Refers to gross calorific value of fuel
  2. Refers to net calorific value of fuel
  3. Propane gas: G31 Hs 95.65 MJ/m³ @ 15°C and 1013.25 mbar
  4. Heat output depends on airflow – heat output H2 only for airflows above V2.
  5. H2 = heat output at airflow V2
  6. H1 = heat output at airflow V1.
Technical Data RHC21 8000 Series

This table replaces “Table 1 – Specifications” given on Page 8 of the RHC21 8000 Installation Manual

Model| 8045-09-P| 8075-15-P| 8075-09-P| 8100-12-P| 8150M18-P| 8200M24-P
---|---|---|---|---|---|---
Combustion air & flue type Indoor| B23 / B53 / C13 / C33 / C53
Combustion air & flue type External| Rooftop
Heat Input High Fire (Hs) 1| kW| 56.00| 91.50| 91.50| 120.00| 183.00| 240.00
Heat Input Low Fire (Hs) 1| kW| 16.80| 32.00| 32.00| 37.00| 64.00| 79.00
Heat Input High Fire (Hi) 2| kW| 51.38| 83.94| 83.94| 110.09| 167.89| 220.18
Heat Input Low Fire (Hi) 2| kW| 15.41| 29.36| 29.36| 33.94| 58.72| 72.48
Heat Output H2 High Fire 4| kW| 46.74| 77.04| 78.09| 103.67| 156.73| 204.92
Heat Output H2 Low Fire 4| kW| 15.13| 28.77| 28.94| 33.71| 57.93| 71.61
Gas Consumption High Fire (Hs) G31 3| m³/h| 2.11| 3.44| 3.44| 4.51| 6.88| 9.03
Gas Consumption Low Fire (Hs) G31 3| m³/h| 0.63| 1.20| 1.20| 1.39| 2.41| 2.97
Gas Consumption High Fire (Hs) G31 3| l/h| 7.82| 12.77| 12.77| 16.75| 25.54| 33.50
Gas Consumption Low Fire (Hs) G31 3| l/h| 2.35| 4.47| 4.47| 5.16| 8.93| 11.03
Gas Consumption High Fire (Hs) G31 3| kg/h| 4.00| 6.54| 6.54| 8.58| 13.08| 17.15
Gas Consumption Low Fire (Hs) G31 3| kg/h| 1.20| 2.29| 2.29| 2.64| 4.57| 5.65
Gas Service Connection| 3/4″| 3/4″| 3/4″| 3/4″| 1 1/4″| 1 1/4″
Flue & Combustion Air Connection Collars (Indoor)| Ø mm| 130| 130| 130| 130| 130| 180
Condensation Connection / Outlet| Ø mm| 22 OD
Minimum V1 Airflow at 15°C with Heat Output H1 6| m³/h| 5650| 9300| 9300| 12400| 18200| 23300
kW| TBA| TBA| TBA| TBA| TBA| TBA
Temperature Rise at V1 Airflow| K| TBA| TBA| TBA| TBA| TBA| TBA
Minimum V2 Airflow at 15°C with Heat Output H2 5| m³/h| 6600| 11900| 10790| 14300| 21000| 24000
Temperature Rise at V2 Airflow| K| 21| 19| 22| 22| 22| 25
Electrical Connection| 1 Phase| 230V 1N~50Hz
Total Electric Rating| kW| 0.30| 0.30| 0.30| 0.28| 0.60| 0.56
Appliance Weight (net)| kg| 87| 140| 110| 145| 230| 305
Protection Grade| IP| 20 (Indoor) / X4D (External)

  1. Refers to gross calorific value of fuel
  2. Refers to net calorific value of fuel
  3. Propane gas: G31 Hs 95.65 MJ/m³ @ 15°C and 1013.25 mbar
  4. Heat output depends on airflow – heat output H2 only for airflows above V2.
  5. H2 = heat output at airflow V2
  6. H1 = heat output at airflow V1.
Nominal Combustion Values RHC21 4000 Series

This table replaces “Table 2 – Nominal Combustion Values and Flue Gas Properties” given on Page 9 of the RHC21 4000 Installation Manual

Model| 4024-05-P| 4050-06-P| 4060-07-P| 4075-09-P| 4100-12-P
---|---|---|---|---|---
CO2 at High Fire (Throttle) G31| %| 9.40| 9.40| 9.80| 9.80| 9.80
CO| ppm| < 50 ppm
CO2 at Low Fire (Offset) G31| %| 8.80| 8.80| 9.00| 9.00| 9.00
CO| ppm| < 50 ppm
Flue Gas Temperature High Fire ΔT| °C| 168| 136| 139| 140| 129
Flue Gas Temperature Low Fire ΔT| °C| 67| 17| 24| 24| 26
Mass Flow Rate Flue Gases High

Fire G31

| kg/h| 30.57| 64.67| 71.93| 84.00| 109.10
Flue Pressure at Maximum Flue

Resistance

| Pa| 5| 8| 9| 14| 14
Thermal Efficiency High Fire NCV| %| 91.19| 92.93| 93.02| 92.99| 93.60
Thermal Efficiency Low Fire NCV| %| 96.42| 99.30| 98.95| 98.84| 98.96
Gas Valve Orifice Size| mm| 4.4| 6.0| 6.8| 6.8| 7.4

Nominal Combustion Values RHC21 8000 Series

This table replaces “Table 2 – Nominal Combustion Values and Flue Gas Properties” given on Page 9 of the RHC21 8000 Installation Manual

Model| 8045-09-P| 8075-15-P| 8075-09-P| 8100-12-P| 8150M18-

P

| 8200M24-

P

---|---|---|---|---|---|---
CO2 at High Fire (Throttle) G31| %| 9.40| 9.80| 9.60| 9.70| 9.70| 9.70
CO| ppm| < 50 ppm
CO2 at Low Fire (Offset) G31| %| 8.60| 8.90| 8.80| 8.90| 8.90| 8.80
CO| ppm| < 50 ppm
Flue Gas Temperature High Fire ΔT| °C| 171| 162| 137| 116| 132| 138
Flue Gas Temperature Low Fire ΔT| °C| 36| 40| 30| 17| 29| 26
Thermal Efficiency High Fire NCV| %| 90.98| 93.02| 91.78| 94.17| 93.35| 93.07
Thermal Efficiency Low Fire NCV| %| 98.18| 98.59| 97.99| 99.31| 98.66| 98.80
Mass Flow Rate Flue Gases High

Fire G31

| kg/h| 59.81| 86.19| 90.40| 116.00| 175.16| 227.53
Flue Pressure at Maximum Flue

Resistance

| Pa| 2| 6| 9| 18| 23| 9
Gas Valve Orifice Size| mm| 6.0| 6.8| 6.8| 7.4| 6.8 x 2| 7.4 x 2

Gas Supply – Propane

This information replaces the information given in “Section 4.10 Gas Supply” of the RHC21 4000 and RHC21 8000 Installation Manual regarding Gas Types

RHC21-P 4000 and 8000 heaters are designed to operate on propane gas (G31). Check that the gas supply, gas category and gas inlet pressure is in accordance with the information given on the unit data plate. To let the unit function at maximal heat output, the gas supply pipe MUST be correctly sized.

Gas Supply Details – Propane Gas

This table details the gas supply properties and is to be read in conjunction with the information given in “Section 4.10 Gas Supply” of the RHC21 4000 and RHC21 8000 Installation Manual regarding Gas Types

Country| Gas Category| Gas Type| Nominal Supply Pressure (mbar)| Minimum Supply Pressure (mbar)| Maximum Supply Pressure (mbar)
---|---|---|---|---|---
CZ, DK, HU, MT, NL, RO| I3P (30)| Propane Gas (G31)| 30| 25| 35
BE, CH, CZ, ES, FR, GB, GR, HR, IE, IT, LU, PL, PT, SI, SK, TR| I3P (37)| Propane Gas (G31)| 37| 25| 45
AT, BE, CH, CZ, DE, ES, FR, GB, GR, HU, NL, SK| I3P (50)| Propane Gas (G31)| 50| 42.5| 57.5

Pre-Start Checks – Propane Gas

This information must be read in addition to the information given in “Section 5.3 – Pre-Start Checks” of the RHC21 4000 and RHC21 8000 Installation Manual

Ensure RHC21 heaters have a link cable fitted between internal wiring terminals GS / GS. Do not proceed if this link is missing.
Pre-Start Checks – Propane Gas

Verify ignition controller program key matches the resistance value as shown in nominal combustion value table.

Note: model 8200 has a different program key when converted for use on propane gas. All other models use the same program key for both natural and propane gas

Gas Conversion – Propane

This information replaces in its entirety the information given in “Section 5.8 – Gas Conversion” of the RHC21 4000 and RHC21 8000 Installation Manual

RHC21-P heaters are designed to operate on propane gas type G31. To modify for use on an alternative listed gas type, contact the appliance manufacturer for further information.

Nominal Combustion Values with Service Door Closed – Propane RHC21 4000

This table replaces “Table 10 – Nominal Combustion Values with Service Door Closed” given in the RHC21 4000 Installation Manual

Model 4024-05-P 4050-06-P 4060-07-P 4075-09-P 4100-12-P
CO2 at High Fire (Throttle) G31 % 9.40 9.40 9.80 9.80
CO ppm < 50 ppm
Throttle turns from closed   2.25 out 3.5 out 4.5 out 4.5 out
CO2 at Low Fire (Offset) G31 % 8.80 8.80 9.00 9.00
CO ppm < 50 ppm
Low Fire Offset Pressure G31 Pa -50 -5 -19 -44
Flue Gas Temperature High Fire ΔT °C 168 136 139 140
Flue Gas Temperature Low Fire ΔT °C 67 17 24 24
Flue Pressure at Maximum Flue Resistance Pa 5 8 9 14
Mass Flow Rate Flue Gases High Fire G31 kg/h 30.57 64.67 71.93 84.00

109.10
Thermal Efficiency High Fire NCV| %| 91.19| 92.93| 93.02| 92.99| 93.60
Thermal Efficiency Low Fire NCV| %| 96.42| 99.30| 98.95| 98.84| 98.96
Ignition Controller Program Key Top Burner| Ω| N/A| N/A| N/A| N/A| N/A
Ignition Controller Program Key Bottom Burner| Ω| 1,000| 3,300| 4,700| 6,800| 10,000
Gas Valve Orifice Size| mm| 4.4| 6.0| 6.8| 6.8| 7.4

Nominal Combustion Values with Service Door Closed – Propane RHC21 8000

This table replaces “Table 10 – Nominal Combustion Values with Service Door Closed” given in the RHC21 8000 Installation Manual

Model| 8045-09-

P

| 8075-15-

P

| 8075-09-

P

| 8100-12-

P

| 8150M18

-P

| 8200M24

-P

---|---|---|---|---|---|---
CO2 at High Fire (Throttle) G31| %| 9.40| 9.80| 9.60| 9.70| 9.70| 9.70
CO| ppm| < 50 ppm
Throttle turns from closed Top Burner|  | N/A| N/A| N/A| N/A| 4 out| 34 in
Throttle turns from closed Bottom / Single Burner|  | 3 out| 5 out| 4 out| 21 in| 4 out| 34 in
CO2 at Low Fire (Offset) G31| %| 8.60| 8.90| 8.80| 8.90| 8.90| 8.80
CO| ppm| < 50 ppm
Low Fire Offset Pressure (G31) Top Burner| Pa| N/A| N/A| N/A| N/A| -55| -34
Low Fire Offset Pressure (G31) Bottom / Single

Burner

| Pa| -10| -58| -46| -14| -62| -23
Flue Gas Temperature High Fire ΔT| °C| 171| 162| 137| 116| 132| 138
Flue Gas Temperature Low Fire ΔT| °C| 36| 40| 30| 17| 29| 26
Thermal Efficiency High Fire NCV| %| 90.98| 93.02| 91.78| 94.17| 93.35| 93.07
Thermal Efficiency Low Fire NCV| %| 98.18| 98.59| 97.99| 99.31| 98.66| 98.80
Flue Pressure at Maximum Flue Resistance| Pa| 2| 6| 9| 18| 23| 9
Mass Flow Rate Flue Gases High Fire G31| kg/h| 59.81| 86.19| 90.40| 116.00| 175.16| 227.53
Ignition Controller Program Key Top Burner| Ω| N/A| N/A| N/A| N/A| 22,000| 56,000
Ignition Controller Program Key Bottom

Burner

| Ω| 1,000| 4,700| 3,300| 6,800| 22,000| 56,000
Gas Valve Orifice Size| mm| 6.0| 6.8| 6.8| 7.4| 6.8 x 2| 7.4 x 2

Maintenance – Propane

This information must be read in addition to the information given in “Section 7.1 – Replacement of Gas Valve” of the RHC21 4000 and RHC21 8000 Installation Manual

RHC21-P models have an orifice fitted between the gas valve and venturi. This orifice should be retained and refitted when replacing the gas valve or venturi to ensure correct appliance operation.
Maintenance - Propane

Cleaning and Replacement of Burner Probes – Propane
This information must be read in addition to the information given in “Section 7.6 – Cleaning and

Replacement of Burner Probes” of the RHC21 4000 and RHC21 8000 Installation Manual
RHC21-P models 4100-12-P, 8075-15-P, 8100-12-P and 8200M24-P have a special spark probe assembly. Dimensions for checking are as follows: –
Length of probe = 79.4mm long probe, 43.2mm short probe.
4.1mm +/- 0.5mm gap between probes.
Angle of probes 22.3°

Spare Parts – Propane

This information must be read in addition to the information given in “Section 9 – Parts Listing” of the RHC21 4000 and RHC21 8000 Installation Manual

Description Part Number Application
4.4mm gas valve orifice 1037652 4024-05-P
6.0mm gas valve orifice 03-25800-02 4050-06-P, 8045-09-P
6.8mm gas valve orifice 1037654 4060-07-P, 4075-09-P, 8075-09-P, 8150M18-P x

2
7.4mm gas valve orifice & O-ring| 1037655| 4100-12-P, 8100-12-P, 8200M24-P x 2
Propane Gas Selection (GS) Jumper| 1030922| All
Spark Probe c/w Lead| 1037848| 4100-12-P, 8075-15-P 8100-12-P, 8200M24-P x 2

ErP Table – G31 Propane RHC21 4000
This information replaces the information given in “Section 11 – ErP Tables” of the RHC21 4000 Installation Manual

Model| RHC21| 4024-

05-P

| 4050-

06-P

| 4060-

07-P

| 4075-

09-P

| 4100-

12-P

|  |  |
---|---|---|---|---|---|---|---|---|---
Item| Symbol| Units|  |  |  |  |  |  |  |
Capacity
Rated heating capacity| Pnom| kW| 24.1| 52.4| 66.2| 78.1| 103.0|  |  |
Minimum capacity| Pmin| kW| 16.5| 14.6| 20.9| 29.0| 33.6|  |  |
Electrical Power consumption
At rated heating capacity| elmax| kW| 0.040| 0.123| 0.115| 0.151| 0.174|  |  |
At minimal capacity| elmin| kW| 0.008| 0.012| 0.018| 0.021| 0.029|  |  |
In standby mode| elsb| kW| 0.001| 0.001| 0.001| 0.001| 0.001|  |  |
Useful efficiency
Useful efficiency at rated heating capacity| η th, nom| %| 83.7| 85.3| 85.3| 85.3| 85.9|  |  |
Useful efficiency at minimum capacity| η th, min| %| 88.5| 91.1| 90.8| 90.7| 90.8|  |  |
Other items
Envelope loss factor| Fenv| %| 0.0| 0.0| 0.0| 0.0| 0.0|  |  |
Flame consumption| Pign| kW| 0.0| 0.0| 0.0| 0.0| 0.0|  |  |
Emissions of nitrogen oxides (input energy GCV| NOx| Mg/kWh| 62| 67| 68| 59| 66|  |  |
Emission efficiency| η s, flow| %| 93.9| 96.7| 96.2| 96.0| 96.3|  |  |
ErP seasonal space heating energy efficiency| η s| %| 79.5| 87.1| 86.3| 85.6| 86.4|  |  |
Thermal efficiency at rated heating capacity NCV| η| %| 91.2| 92.9| 93.0| 93.0| 93.6|  |  |

ErP Table – G31 Propane RHC21 8000
This information replaces the information given in “Section 11 – ErP Tables” of the RHC21 8000 Installation Manual

Model| RHC21| 8045-

09-P

| 8075-

09-P

| 80750

15-P

| 8100-

12-P

| 8150

M18- P

| 8200

M24- P

|  |
---|---|---|---|---|---|---|---|---|---
Item| Symbol| Units|  |  |  |  |  |  |  |
Capacity
Rated heating capacity| Pnom| kW| 46.7| 78.1| 77.0| 103.7| 156.7| 204.9|  |
Minimum capacity| Pmin| kW| 15.1| 28.9| 28.8| 33.7| 57.9| 71.6|  |
Electrical Power consumption
At rated heating capacity| elmax| kW| 0.113| 0.187| 0.162| 0.187| 0.39| 0.43| |
At minimal capacity| elmin| kW| 0.014| 0.021| 0.022| 0.016| 0.050| 0.056|  |
In standby mode| elsb| kW| 0.001| 0.001| 0.001| 0.001| 0.001| 0.001|  |
Useful efficiency
Useful efficiency at rated heating capacity| η th, nom| %| 83.5| 85.3| 84.2| 86.4| 85.6| 85.4|  |
Useful efficiency at minimum capacity| η th, min| %| 90.1| 90.4| 89.9| 91.1| 90.5| 90.6|  |
Other items
Envelope loss factor| Fenv| %| 0.0| 0.0| 0.0| 0.0| 0.0| 0.0|  |
Flame consumption| Pign| kW| 0.0| 0.0| 0.0| 0.0| 0.0| 0.0|  |
Emissions of nitrogen oxides (input energy GCV| NOx| Mg/kWh| 60| 56| 69| 58| 68| 65|  |
Emission efficiency| η s, flow| %| 97.1| 96.7| 97.1| 97.0| 96.6| 96.3|  |
ErP seasonal space heating energy efficiency| η s| %| 86.2| 86.1| 85.8| 87.4| 86.1| 86.0|  |
Thermal efficiency at rated heating capacity NCV| η| %| 91.0| 93.0| 91.8| 94.2| 93.4| 93.1|  |

CUSTOMER SERVICE

NORTEK GLOBAL HVAC (UK) LTD
Fens Pool Avenue
Brierley Hill
West Midlands DY5 1QA
United Kingdom
Tel +44 (0)1384 489700
Fax +44 (0)1384 489707
reznorsales@nortek.com
www.reznor.eu
Current full Part No.
Installation Instruction Addendum
RHC21 4000 and 8000 Propane
January 2022 D301383 Issue 0