SENECA R-32DIDO-1-P Digital I/O Modules User Manual

September 14, 2024
SENECA

R-32DIDO-1-P Digital I/O Modules

“`html

Product Information

Specifications:

  • Series: R-P I/O with Protocol PROFINET IO
  • Manufacturer: SENECA srl
  • Model: R-P Series
  • Supported Devices: R-32DIDO-1-P, R-16DI-8DO-P, R-8AI-8DIDO-P,
    R-32DIDO-2-P, R-SG3-P, R-4AO-8DIDO-P

Product Usage Instructions:

1. Introduction:

Begin by familiarizing yourself with the product and its
capabilities as outlined in the user manual.

2. R-P Series Devices:

Learn about the supported devices and their specific
functionalities. Refer to the manual for detailed information on
each device.

2.1 Information About the PROFINET IO Protocol:

Understand the communication protocol used by the device and how
it integrates with other systems.

2.2 R-32DIDO-P:

Explore the features and specifications of the R-32DIDO-P model
as described in the manual.

3. Dip Switch:

Follow the instructions on configuring the Dip Switch settings
for optimal performance.

4. Web Server:

Access the web server for additional configuration options and
monitoring capabilities.

4.1 Access to the Web Server:

Follow the steps provided to access and navigate the web server
interface.

5. Example of Creating a Project with Siemens PLC (TIA Portal

16):

Refer to the manual for a detailed guide on integrating the
device with Siemens PLC using TIA Portal 16.

FAQ:

Q: How do I update the firmware on my device?

A: To update the firmware, follow the instructions provided in
the user manual under the relevant chapter for FW Update.

Q: What is the default IP address of the device?

A: The default IP address has been changed, refer to the latest
revision of the manual for the updated information.

“`

USER MANUAL
SERIES R-P I/O WITH PROTOCOL
PROFINET IO
SENECA S.r.l. Via Austria 26 ­ 35127 ­ Z.I. – PADOVA (PD) – ITALY Tel. +39.049.8705355 ­ 8705355 Fax +39 049.8706287
www.seneca.it
ORIGINAL INSTRUCTIONS

User Manual

R-P SERIES

CAUTION
SENECA does not guarantee that all specifications and/or aspects of the product and firmware, included in them, will meet the requirements of the actual final application even if the product referred to in this documentation is in compliance with the technological state of the art. The user assumes full responsibility and/or risk with regard to the configuration of the product to achieve the intended results in relation to the specific installation and/or end application. SENECA may, with prior agreement, provide consultancy services for the successful completion of the final application, but under no circumstances can it be held responsible for its proper functioning. The SENECA product is an advanced product, the operation of which is specified in the technical documentation supplied with the product itself and/or can be downloaded, if desired prior to purchase, from the www.seneca.it website. SENECA has a policy of continuous development and accordingly reserves the right to make and/or introduce without prior notice – changes and/or improvements to any product described in this documentation. The product described in this documentation may solely and exclusively be used by personnel qualified for the specific activity and in accordance with the relevant technical documentation, with particular attention being paid to the safety instructions. Qualified personnel means personnel who, on the basis of their training, competence and experience, are able to identify risks and avoid potential hazards that could occur during the use of this product. SENECA products may only be used for the applications and in the manner described in the technical documentation relating to the products themselves. To ensure proper operation and prevent the occurrence of malfunctions, the transport, storage, installation, assembly, maintenance of SENECA products must comply with the safety instructions and environmental conditions specified in this documentation. SENECA’s liability in relation to its products is governed by the general conditions of sale, which can be downloaded from www.seneca.it. Neither SENECA nor its employees, within the limits of applicable law, will in any case be liable for any lost profits and/or sales, loss of data and/or information, higher costs incurred for goods and/or replacement services, damage to property and/or persons, interruption of activities and/or provision of services, any direct, indirect, incidental, pecuniary and non-pecuniary, consequential damages in any way caused and/or caused, due to negligence, carelessness, incompetence and/or other liabilities arising from the installation, use and/or inability to use the product.

CONTACT US Technical support Product information

supporto@seneca.it commerciale@seneca.it

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 2

User Manual

R-P SERIES

Document revisions

DATE
20/02/2023

REVISION
0

02/03/2023

1

16/03/2023

2

NOTES
First revision Supported devices: R-32DIDO-1-P, R-16DI-8DO-P, R-8AI-8DIDO-P
Added chapter “Protection of digital outputs”
Added chapter on FW Update Moved chapter on configuring gsdml file parameters Added information on the procedure to restore the device to factory configuration
Added I/O reaction time on R-32DIDO-P Added warning for complete hardware compilation on Tia portal

AUTHOR
MM
MM MM

31/05/2023
28/11/2023 05/03/2023 15/03/2024 20/03/2024 11/07/2024

Default IP changed and Dip Switch chapter added for new firmware

MM

Deleted chapter “Restoring the device to factory configuration”.

4

Deleted chapter “CONNECTING THE DEVICE TO AN ETHERNET NETWORK”

Added R-32DIDO-2-P model

5

Replaced model R-8AI-8DIDO-P with new hardware version

MM

6

Added new info on new redesigned model of R-8AI-8DIDO-P

MM

7

Updated timing for new R-32DIDO-P firmware rev 1016, chapter 2.2 updated. Updated

MM

chapter 3.2. Updated chapter 2.4 and 3.1

8

Added new product R-SG3-P

MM

9

Added new R-4AO-8DIDO-P device

MM

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 3

User Manual

R-P SERIES

TABLE OF CONTENTS

1. INTRODUCTION……………………………………………………………………………………………..6

2. R-P SERIES DEVICES …………………………………………………………………………………….6
2.1. INFORMATION ABOUT THE PROFINET IO PROTOCOL ………………………………………………………………………………………..6 2.2. R-32DIDO-P …………………………………………………………………………………………………………………………………………………………6
2.2.1. PROTECTION OF DIGITAL OUTPUTS……………………………………………………………………………………………………………….7 2.2.2. I/O UPDATE TIME ……………………………………………………………………………………………………………………………………………7 2.3. R-16DI- 8DO-P………………………………………………………………………………………………………………………………………………………7 2.4. R-8AI- 8DIDO-P …………………………………………………………………………………………………………………………………………………….7 2.4.1. ANALOG INPUT UPDATE TIME ………………………………………………………………………………………………………………………..8 2.4.2. DIGITAL I/O UPDATE TIME ………………………………………………………………………………………………………………………………8 2.5. R-SG3-P………………………………………………………………………………………………………………………………………………………………8 2.5.1. LOAD CELL CONNECTION ………………………………………………………………………………………………………………………………9 2.5.2. 4- OR 6-WIRE LOAD CELL CONNECTION …………………………………………………………………………………………………………9 2.5.3. CHECKING THE LOAD CELL OPERATION ………………………………………………………………………………………………………..9 2.5.3.1. CHECKING CABLES WITH A DIGITAL MULTIMETER …………………………………………………………………………………….9 2.5.4. CONNECTION OF MORE LOAD CELLS IN PARALLEL ……………………………………………………………………………………..10 2.5.5. TRIMMING 4-WIRE LOAD CELLS ……………………………………………………………………………………………………………………11 2.6.1. R-4AO-8DIDO-P……………………………………………………………………………………………………………………………………………..13 2.6.2. ANALOG OUTPUT RESPONSE TIME ………………………………………………………………………………………………………………13 2.6.3. PROTECTION OF DIGITAL OUTPUTS……………………………………………………………………………………………………………..13

3. DIP SWITCH …………………………………………………………………………………………………13
3.1. MEANING OF THE DIP SWITCHES FOR THE R-8AI-8DIDO-2-P MODEL ………………………………………………………………..14 3.2. MEANING OF THE DIP SWITCHES FOR THE R-32DIDO-2-P MODEL…………………………………………………………………….15 3.3. MEANING OF THE DIP SWITCHES FOR THE R-SG3-P MODEL…………………………………………………………………………….16 3.4. MEANING OF THE DIP SWITCHES FOR THE R-4AO-8DIDO-P MODEL …………………………………………………………………17

4. WEB SERVER ………………………………………………………………………………………………18
4.1. ACCESS TO THE WEB SERVER …………………………………………………………………………………………………………………………18

5. EXAMPLE OF CREATING A PROJECT WITH SIEMENS PLC (TIA PORTAL 16)…20
5.1. INSTALLING THE GSDML FILE…………………………………………………………………………………………………………………………..21 5.2. INSERTION OF THE SIEMENS PLC IN THE PROJECT …………………………………………………………………………………………22 5.3. INSERTION OF THE PROFINET SENECA IO ……………………………………………………………………………………………………….25 5.4. CONFIGURATION OF THE PARAMETERS OF THE SENECA DEVICE …………………………………………………………………..28 5.5. CONFIGURATION PARAMETERS OF THE GSDML FILE………………………………………………………………………………………29
5.5.1. R-32DIDO-P …………………………………………………………………………………………………………………………………………………..29 5.5.2. R-16DI-8DO-P………………………………………………………………………………………………………………………………………………..29 5.5.3. R-8AI-8DIDO-P ………………………………………………………………………………………………………………………………………………30 5.5.4. R-SG3-P………………………………………………………………………………………………………………………………………………………..32 5.5.5. R-4AO-8DIDO-P……………………………………………………………………………………………………………………………………………..38 5.6. R-32DIDO-P I/O DATA ………………………………………………………………………………………………………………………………………..39 5.7. R-16DI-8DO-P I/O DATA ……………………………………………………………………………………………………………………………………..43 5.8. R-8AI-8DIDO-P I/O DATA ……………………………………………………………………………………………………………………………………48

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 4

User Manual

R-P SERIES

5.9. R-SG3-P I/O DATA ……………………………………………………………………………………………………………………………………………..49 5.10. R- 4AO-8DIDO-P I/O DATA …………………………………………………………………………………………………………………………………53 5.11. COMPILATION AND SENDING OF THE PROJECT TO THE SIEMENS PLC ……………………………………………………………56
6. EXAMPLE OF CREATING A PROJECT WITH PLC CODESYS 3.5 …………………….59
6.1.1. INSERTION OF THE CODESYS PLC IN THE PROJECT ……………………………………………………………………………………59 6.1.2. INSTALLING THE GSD …………………………………………………………………………………………………………………………………..63 6.1.3. INSTALLATION OF THE SENECA PROFINET IO ………………………………………………………………………………………………65 6.1.4. CONFIGURATION OF THE PARAMETERS OF THE SENECA IO ……………………………………………………………………….66 6.1.5. READING AND WRITING THE SENECA IO FROM CODESYS ……………………………………………………………………………68
7. CABLE HARNESS FOR MODELS WITH DOUBLE ETHERNET PORT ……………….70
7.1. CHAIN ETHERNET CONNECTION (DAISY CHAIN)……………………………………………………………………………………………….70 7.2. LAN FAULT-BYPASS FUNCTION ……………………………………………………………………………………………………………………….72
8. SEARCH AND MODIFICATION OF THE DEVICE IP WITH SENECA DISCOVERY TOOL ………………………………………………………………………………………………………………… 72
9. FIRMWARE UPDATE…………………………………………………………………………………….74

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 5

User Manual

R-P SERIES

1. INTRODUCTION

ATTENTION!
This user manual extends the information from the installation manual to the configuration of the device. Use the installation manual for more information.

ATTENTION!
In any case, SENECA s.r.l. or its suppliers will not be responsible for the loss of data/revenue or consequential or incidental damages due to negligence or bad/improper management of the device,
even if SENECA is well aware of these possible damages. SENECA, its subsidiaries, affiliates, group companies, suppliers and distributors do not guarantee that the functions fully meet the customer’s expectations or that the device, firmware and software should
have no errors or operate continuously.

2. R-P SERIES DEVICES

The R series I/O devices support the Profinet IO protocol

2.1. INFORMATION ABOUT THE PROFINET IO PROTOCOL

Type of protocol: Class A Device, Cyclic Real-time (RT) and Acyclic Data
The device has been tested using the following PLCs: SIEMENS S7 1200 firmware revision 4.3 (Tia Portal 16) CODESYS Runtime 3.5 (Codesys 3.5)
2.2. R-32DIDO-P

The device allows the use of 32 digital channels that can be individually configured for input or output.

CODE R-32DIDO-2-P

ETHERNET PORTS 2 10/100 Mbit PORTS
(Switch mode)

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 6

User Manual

R-P SERIES

2.2.1. PROTECTION OF DIGITAL OUTPUTS

The outputs are protected against overload and against overtemperature, they open cyclically until the fault is repaired or the output opens.

The limit current is between 0.6 and 1.2 A.

2.2.2. I/O UPDATE TIME

The update of the 32 digital I/Os is performed every 2ms.

2.3. R-16DI-8DO-P

The devices allow the use of 16 digital input channels and 8 digital output channels (relay).

CODE R-16DI8DO-P

ETHERNET PORTS 2 10/100 Mbit PORTS
(Switch mode)

2.4. R-8AI-8DIDO-P

The devices allow the use of 8 analog input channels and 8 digital channels that can be individually configured for input or output.

CODE R-8AI-8DIDO-2-P

ETHERNET PORTS 2 10/100 Mbit PORTS
(Switch mode)

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 7

User Manual

R-P SERIES

2.4.1. ANALOG INPUT UPDATE TIME
Sampling time can be configured from 4ms to 400ms per each channel.
By activating 8 channels and setting a sampling time of 4 ms, you get an input update every: 4*8 = 32 ms.
Note (only if thermocouple channels are enabled): In the case of a thermocouple input, the Burnout check is carried out every 10 seconds. The duration of this check takes a sampling on each enabled thermocouple channel. For example, with 3 active thermocouples, every 10 seconds the following are used: 4ms x 3 channels = 12 ms for Burnout evaluation.
ATTENTION!
IF ANALOG INPUT 1 IS CONFIGURED IN RTD PT100 MODE, THE MINIMUM SAMPLING TIME FOR THIS CHANNEL TO OBTAIN A CORRECT MEASUREMENT IS 25 ms
2.4.2. DIGITAL I/O UPDATE TIME
The update time of the 8 digital I/Os is 4ms.

2.5. R-SG3-P

The device allows the use of an analogue channel for strain gauge load cells and 2 digital channels that can be individually configured for input or output.

CODE R-SG3-P

ETHERNET PORTS 1 10/100 Mbit PORT
(Switch mode)

The measurement, carried out with the 4 or 6 wire technique. The device is equipped with a new noise filter specifically developed to obtain a rapid response time.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 8

User Manual

R-P SERIES

2.5.1. LOAD CELL CONNECTION
It is possible to connect the converter to the load cell in 4- or 6-wire mode. 6-wire measurement is preferable for measurement accuracy. The load cell power supply is provided directly by the device.
2.5.2. 4- OR 6-WIRE LOAD CELL CONNECTION
A load cell can have a four-wire or six-wire cable. In addition to having the +/- excitation and +/- signal lines a six-wire cable also has the +/- sense lines. It is a common misconception to think that the only difference between 4- or 6-wire load cells is the possibility of the latter to measure the actual voltage at the load cell. A load cell is compensated to work within specifications in a certain temperature range (usually -10 – +40°C). Since the cable resistance depends on the temperature, the response of the cable to temperature changes must be eliminated. The 4-wire cable is part of the load cell temperature compensation system. The 4-wire load cell is calibrated and compensated with a certain amount of cable connected. For this reason, never cut the cable of a 4-wire load cell. The cable of a 6-wire cell, on the other hand, is not part of the load cell temperature compensation system. The sense lines are connected to the R-SG3 sense terminals, to measure and adjust the actual voltage of the load cell. The advantage of using this “active” system is the possibility of cutting (or extending) the 6-wire load cell cable to any length. It must be considered that a 6-wire load cell will not reach the performance declared in the specifications if the sense lines are not used.
2.5.3. CHECKING THE LOAD CELL OPERATION
Before starting the configuration of the device it is necessary to verify the correctness of the wiring and the integrity of the load cell.
2.5.3.1. CHECKING CABLES WITH A DIGITAL MULTIMETER
First you need to check with the load cell manual that there are about 5V DC between the +Excitation and ­ Excitation cables. If the cell has 6 wires check that the same voltage is also measured between +Sense and ­ Sense. Now leave the cell at rest (without the tare) and check that the voltage between the +Signal and ­Signal cables is around 0 V. Now unbalance the cell by applying a compression force, checking that the voltage between the +Signal and ­ Signal cables increases until it reaches the full scale (if possible) where the measurement will be approximately:
5 (cell sensitivity) mV.
For example, if the declared cell sensitivity is 2 mV/V, 5
2 = 10 mV must be obtained.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 9

User Manual

R-P SERIES

In the case of bipolar measurement only (compression/traction) it is necessary to completely unbalance the cell even in traction, in this case the same value must be measured between the +Signal and ­Signal cables but with the negative sign:

-5* (cell sensitivity) mV.

2.5.4. CONNECTION OF MORE LOAD CELLS IN PARALLEL

It is possible to connect up to a maximum of 8 load cells (and in any case without ever falling below the minimum 87 Ohms).

It is therefore possible to connect:

IMPEDANCE OF THE STATED LOAD CELL
[Ohm] 350
1000

NUMBER OF LOAD CELLS IN PARALLEL MAXIMUM NUMBER OF CONNECTABLE CELLS IN PARALLEL
4 8

For the connection of 4 load cells Seneca recommends using the SG-EQ4 product.

To connect 2 or more 4-wire cells in parallel with the SG-EQ4 junction box, use the following diagram:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 10

User Manual

R-P SERIES

To connect 2 or more 6-wire cells in parallel with the SG-EQ4 junction box use the following diagram:

For more details, refer to the SG-EQ4 Junction Box accessory manual.
2.5.5. TRIMMING 4-WIRE LOAD CELLS The figure below shows a diagram of three trimmed load cells.

A variable resistor, independent of the temperature, or a typically 20 potentiometer is inserted in the +Excitation cable of each load cell. There are two ways to trim the load cells. The first method is to adjust the potentiometers by trial, shifting the calibration weights from one corner to another.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 11

User Manual

R-P SERIES

All the potentiometers must be adjusted so as to set the maximum sensitivity for each cell, turning them all completely clockwise. Then, once the angle with the lowest output is located, act on the trimmers of the other cells until obtaining the same minimum output value. This method can be very long, especially for large scales where the use of test weights on the corners is not very practical. In these cases the second, more suitable method is to “pre-trim” the potentiometers using a precision voltmeter (at least 4 1/2 digits). You can use the following procedure: 1) Determine the exact mV/V ratio of each load cell, shown in the calibration certificate of the cell itself. 2) Determine the exact excitation voltage provided by the indicator/meter (for example Z-SG), measuring this voltage with the voltmeter (for example 10.05 V). 3) Multiply the lowest mV/V value found (point 1) by the excitation voltage (point 2). 4) Divide the trimming factor calculated in point 3 by the mV/V value of the other load cells. 5) Measure and adjust the excitation voltage of the other three load cells using the respective potentiometer. Check the results and make a final adjustment by moving a test load from corner to corner.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 12

User Manual

R-P SERIES

2.6.1. R-4AO-8DIDO-P

The device provides 4 analog output analog channels (that can be individually configured in Voltage or Current) and 8 digital channels that can be individually configured for input or output.

CODE R-4AO-8DIDO

ETHERNET PORT 2 PORTS 10/100 Mbit
(Switch mode)

2.6.2. ANALOG OUTPUT RESPONSE TIME

The analog output response time to go from 10% to 90% is 5ms.

2.6.3. PROTECTION OF DIGITAL OUTPUTS

The outputs are protected against overload and against overtemperature, they open cyclically until the fault is repaired or the output opens. The limit current is between 0.6 and 1.2 A.

3. DIP SWITCH

ATTENTION!
TO INCREASE THE DEVICE’S SECURITY FROM EXTERNAL ATTACKS, IT IS RECOMMENDED TO DISABLE ACCESS TO THE WEBSERVER THROUGH THE DIP SWITCHES

ATTENTION!
THE DIP SWITCH SETTINGS ARE READ ONLY AT THE START. AT EACH CHANGE, IT IS NECESSARY TO RESTART.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 13

User Manual

R-P SERIES

3.1. MEANING OF THE DIP SWITCHES FOR THE R-8AI-8DIDO-2-P MODEL
ATTENTION!
FROM THE 1010 FIRMWARE REVISION THE DEVICES ARE SUPPLIED WITHOUT AN IP ADDRESS (0.0.0.0).
MULTIPLE DEVICES CAN THEREFORE BE INSERTED IN THE SAME PROFINET NETWORK AND IDENTIFIED THROUGH THE SCAN OF THE PROFINET NETWORK ITSELF
TO SET AN IP ADDRESS (FOR EXAMPLE TO ACCESS THE WEBSERVER OR TO CONNECT TO THE SENECA DISCOVERY DEVICE TOOL) USE THE PROFINET CONFIGURATION ENVIRONMENT OR FORCE THE ADDRESS 192.168.90.101 WITH THE APPROPRIATE DIP SWITCH

DIP1 DIP2

MEANING

OFF OFF

Normal operation: The device loads the configuration from the flash.

ON

ON

Resets the device to its factory configuration:

(With IP address 0.0.0.0) In this case the STS LED will start flashing to indicate that

the device does not have a configured IP address.

OFF

ON

Disables access to the Web server

ON

OFF

Forces the device IP address to the standard value of SENECA Ethernet products:

192.168.90.101

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 14

User Manual

R-P SERIES

3.2. MEANING OF THE DIP SWITCHES FOR THE R-32DIDO-2-P MODEL Below is the meaning of the SW1 dip switches:

ATTENTION!
FROM THE 1010 FIRMWARE REVISION THE DEVICES ARE SUPPLIED WITHOUT AN IP ADDRESS (0.0.0.0).

MULTIPLE DEVICES CAN THEREFORE BE INSERTED IN THE SAME PROFINET NETWORK AND IDENTIFIED THROUGH THE SCAN OF THE PROFINET NETWORK ITSELF

TO SET AN IP ADDRESS (FOR EXAMPLE TO ACCESS THE WEBSERVER OR TO CONNECT TO THE SENECA DISCOVERY DEVICE TOOL) USE THE PROFINET CONFIGURATION ENVIRONMENT OR FORCE THE ADDRESS 192.168.90.101 WITH THE APPROPRIATE DIP SWITCH

DIP1 DIP2

MEANING

OFF OFF

Normal operation: The device loads the configuration from the flash.

ON

ON

Resets the device to its factory configuration:

(With IP address 0.0.0.0) In this case the STS LED will start flashing to indicate that

the device does not have a configured IP address.

OFF

ON

Disables access to the Web server

ON

OFF

Forces the device IP address to the standard value of SENECA Ethernet products:

192.168.90.101

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 15

User Manual

R-P SERIES

3.3. MEANING OF THE DIP SWITCHES FOR THE R-SG3-P MODEL Below is the meaning of the SW1 dip switches:

ATTENTION!
THE DEVICES ARE SUPPLIED WITHOUT AN IP ADDRESS (0.0.0.0).

MULTIPLE DEVICES CAN THEREFORE BE INSERTED IN THE SAME PROFINET NETWORK AND IDENTIFIED THROUGH THE SCAN OF THE PROFINET NETWORK ITSELF

TO SET AN IP ADDRESS (FOR EXAMPLE TO ACCESS THE WEBSERVER OR TO CONNECT TO THE SENECA DISCOVERY DEVICE TOOL) USE THE PROFINET CONFIGURATION ENVIRONMENT OR FORCE THE ADDRESS 192.168.90.101 WITH THE APPROPRIATE DIP SWITCH

DIP1 DIP2

MEANING

OFF OFF

Normal operation: The device loads the configuration from the flash.

ON

ON

Resets the device to its factory configuration:

(With IP address 0.0.0.0) In this case the STS LED will start flashing to indicate that

the device does not have a configured IP address.

OFF

ON

Disables access to the Web server

ON

OFF

Forces the device IP address to the standard value of SENECA Ethernet products:

192.168.90.101

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 16

User Manual

R-P SERIES

3.4. MEANING OF THE DIP SWITCHES FOR THE R-4AO-8DIDO-P MODEL Below is the meaning of the SW1 dip switches:

ATTENTION!
THE DEVICES ARE SUPPLIED WITHOUT AN IP ADDRESS (0.0.0.0).

MULTIPLE DEVICES CAN THEREFORE BE INSERTED IN THE SAME PROFINET NETWORK AND IDENTIFIED THROUGH THE SCAN OF THE PROFINET NETWORK ITSELF

TO SET AN IP ADDRESS (FOR EXAMPLE TO ACCESS THE WEBSERVER OR TO CONNECT TO THE SENECA DISCOVERY DEVICE TOOL) USE THE PROFINET CONFIGURATION ENVIRONMENT OR FORCE THE ADDRESS 192.168.90.101 WITH THE APPROPRIATE DIP SWITCH

DIP1 DIP2

MEANING

OFF OFF

Normal operation: The device loads the configuration from the flash.

ON

ON

Resets the device to its factory configuration:

(With IP address 0.0.0.0) In this case the STS LED will start flashing to indicate that

the device does not have a configured IP address.

OFF

ON

Disables access to the Web server

ON

OFF

Forces the device IP address to the standard value of SENECA Ethernet products:

192.168.90.101

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 17

User Manual

R-P SERIES

4. WEB SERVER

ATTENTION!
BEFORE ACCESSING THE WEB SERBER, DISCONNECT THE DEVICE FROM THE PROFINET NETWORK

ATTENTION!
SOME MODELS ARE SUPPLIED WITHOUT AN IP ADDRESS (0.0.0.0) IN THIS CASE THE “STS” LED FLASHES.
TO SET AN IP ADDRESS (FOR EXAMPLE TO ACCESS THE WEBSERVER OR TO CONNECT TO THE SENECA DISCOVERY DEVICE TOOL) USE THE PROFINET CONFIGURATION ENVIRONMENT OR FORCE THE ADDRESS 192.168.90.101 WITH THE APPROPRIATE DIP SWITCH

The main purpose of the web server is to: -Configure the Profinet name of the device without using an external development environment (Tia Portal, Codesys…) -Allow the device firmware update 4.1. ACCESS TO THE WEB SERVER
Access to the web server takes place using a web browser and entering the IP address of the device.
On first access the user name and password will be requested. The default values are:
User Name: admin Password: admin

ATTENTION!
DEPENDING ON THE DEVICE MODEL AND THE FIRMWARE INSTALLED IN THE DEVICE, IT MAY BE NECESSARY TO ACTIVATE THE DIP SWITCHES TO USE THE WEBSERVER

ATTENTION!
AS LONG AS THE STS LED IS FLASHING IT MEANS THE DEVICE HAS NOT SET AN IP ADDRESS. IN THIS SITUATION IT WILL NOT BE POSSIBLE TO ACCESS THE WEBSERVER

ATTENTION!
AFTER THE FIRST ACCESS CHANGE USER NAME AND PASSWORD IN ORDER TO PREVENT ACCESS TO THE DEVICE TO UNAUTHORIZED PEOPLE.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 18

User Manual

R-P SERIES

ATTENTION!
IF THE PARAMETERS TO ACCESS THE WEB SERVER HAVE BEEN LOST, IT IS NECESSARY TO RESET THE FACTORY-SET CONFIGURATION
ATTENTION!
AVOID INSERTING SPECIAL CHARACTERS IN THE PROFINET NAME OF THE DEVICE

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 19

User Manual

R-P SERIES

5. EXAMPLE OF CREATING A PROJECT WITH SIEMENS PLC (TIA PORTAL 16)
Creating a new project:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 20

User Manual

R-P SERIES

5.1. INSTALLING THE GSDML FILE
Install the GSDML file of the Seneca product (it is possible to obtain the file on the web page of the device on the www.seneca.it site):

Point to the directory where the file is and press OK, then the list of GSD files in the folder will appear:

Click on “install”.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 21

User Manual

R-P SERIES

5.2. INSERTION OF THE SIEMENS PLC IN THE PROJECT Now insert the Siemens PLC (in our example a SIEMATIC S7 1200), click on “Add new device …”:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 22

User Manual
Confirm and the PLC will be added to the rack:

R-P SERIES

Now click on the PLC and select Profinet interface -> Ethernet addresses

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 23

User Manual
Set the IP you want (in this case 192.168.90.44) and the PLC subnet:

R-P SERIES

Move on to the network view:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 24

User Manual

R-P SERIES

5.3. INSERTION OF THE PROFINET SENECA IO
On the right, select “Hardware Catalogue” and then under “Additional Field Device” -> PROFINET IO -> I/O -> Seneca R-Series-> Header module (in the example an R-16DI-8DO device is shown):

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 25

Drag the device to the network view:

User Manual

R-P SERIES

Now associate it to the PLC by clicking with the left mouse on “Not assigned” and then select the PLC:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 26

User Manual

R-P SERIES

Click twice on the Seneca device and configure the IP address here too (for example 192.168.90.48):

In Profinet the devices are identified by their name, so right click on the Seneca device and select “Assign device name”
ATTENTION!
AVOID INSERTING SPECIAL CHARACTERS IN THE PROFINET NAME OF THE DEVICE

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 27

User Manual

R-P SERIES

Scan the network with “Update list” and set (if necessary) the device name with “Assign name”.
5.4. CONFIGURATION OF THE PARAMETERS OF THE SENECA DEVICE
It is also possible to directly configure the device IO without any external software. To configure the device, click on the IO so that the “Unit parameters” appear:

At the next start, the PLC will send the desired configuration to the device.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 28

User Manual

R-P SERIES

5.5. CONFIGURATION PARAMETERS OF THE GSDML FILE
5.5.1. R-32DIDO-P
SET DIGITAL IO INPUT/OUTPUT Selects whether the selected input will work as an input or output.
SET DIGITAL INPUT NORMALLY HIGH/LOW If selected as digital input, it configures whether the input is normally high or low.
SET DIGITAL OUTPUT NORMALLY OPEN/CLOSE If selected as digital output, it configures whether the output is normally open or closed.
SET DIGITAL OUTPUT WATCHDOG If selected as digital output, it sets the output watchdog mode. If “Disabled”, it disables the watchdog function for the selected output. If “Enabled on Profinet Communication” the output goes into “Watchdog state” if there has been no generic Profinet communication within the set time.
SET DIGITAL OUTPUT WATCHDOG STATE Sets the value that the digital output must adopt if the watchdog has been triggered.
SET DIGITAL OUTPUT WATCHDOG TIMEOUT [s] Represents the watchdog time of the digital output in seconds. If the PLC stops communicating with the device within the set time, then the outputs will go into the “Watchdog state” condition (if the function is enabled).
5.5.2. R-16DI-8DO-P
SET DIGITAL INPUTS FILTER DELAY [ms] Sets the filtering of the counters, the value is expressed in [ms]. The filter cut-off frequency corresponds to: [] = 1000/ (2 []) For example, if the filter counter is 100ms the cutting frequency will be: [] = 1000/ (2 []) = 5 So all input frequencies greater than 5 Hz will be cut.
SET ALL DIGITAL INPUTS NPN/PNP Sets the input operating mode to between npn “Sink” and pnp “Source”

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 29

User Manual

R-P SERIES

ENABLE DIGITAL OUTPUTS FAULT TIMEOUT Set whether the digital output watchdog is to activated. When enabled, if within the timeout time there has been no communication from the master to the device, the outputs go into a Fail state. This mode allows to obtain a safe system in case of malfunction of the master.
SET DIGITAL OUTPUTS FAULT TIMEOUT [s] Set the watchdog time of the digital outputs.
SET DIGITAL OUTPUT FAULT STATES OPEN/CLOSE They set the states of each of the outputs under normal conditions.
SET DIGITAL OUTPUT NORMALLY OPEN/CLOSE They set the states of each of the outputs in fail conditions.
5.5.3. R-8AI-8DIDO-P
SET DIGITAL IO INPUT/OUTPUT Selects whether the selected input will work as an input or output.
SET DIGITAL INPUT NORMALLY HIGH/LOW If selected as digital input, it configures whether the input is normally high or low.
SET DIGITAL OUTPUT NORMALLY OPEN/CLOSE If selected as digital output, it configures whether the output is normally open or closed.
SET DIGITAL OUTPUT WATCHDOG If selected as digital output, it sets the output watchdog mode. If “Disabled”, it disables the watchdog function for the selected output. If “Enabled on Profinet Communication” the output goes into “Watchdog state” if there has been no generic Profinet communication within the set time.
SET DIGITAL OUTPUT WATCHDOG STATE Sets the value that the digital output must adopt if the watchdog has been triggered.
SET DIGITAL OUTPUT WATCHDOG TIMEOUT [s] Represents the watchdog time of the digital output in seconds. If the PLC stops communicating with the device within the set time, then the outputs will go into the “Watchdog state” condition (if the function is enabled).

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 30

User Manual

R-P SERIES

SET ANALOG MODE Set the type of measurement for the selected input. It is possible to choose between the following types of input: +-100mV +-30V +-24 mA Thermocouple PT100 3 wires (only for analog input 1).

SAMPLING TIME Set the sampling time of the channel, selectable between 4 ms and 400 ms, it is also possible to disconnect the input.

SET ANALOG INPUT MOVING FILTER (10 SAMPLES) Set whether or not to activate the 10-sample moving average filter.

SET ANALOG INPUTS MEASURE OFFSET Set an offset for analog measurements

SET INPUT START/END SCALE Represents the start of the electrical scale of the analog measurement used for the register of the engineering measurement. The value to enter is in the unit of measurement based on the type of input chosen [V], or [mV], or [uA], or [°C]

SET INPUT START/END ENG. SCALE Represents the electrical full scale of the analog measurement used for the engineering measurement register.

Example: ANALOG INPUT START SCALE = 4 [mA] ANALOG INPUT STOP SCALE = 20 [mA] ANALOG INPUT ENG STOP SCALE = -200 [metri] ANALOG INPUT ENG START SCALE = 200 [metri] With a 12 mA input the engineering value will be 0 metres.

SET ANALOG INPUTS TC TYPE In the case of thermocouple measurement, it allows to select the type of thermocouple between: J, K, R, S, T, B, E, N, L

SET ANALOG INPUTS TC COLD JUNCTION MODE In the case of thermocouple measurement, it enables or disables the automatic cold junction offset of the device.

SET ANALOG INPUTS TC COLD JUNCTION OFFSET

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 31

User Manual

R-P SERIES

In the case of thermocouple measurement, set an offset in the cold junction measurement in [°C]

SET ANALOG INPUTS TC BURNOUT MODE In the case of thermocouple measurement, it selects the behaviour in case of sensor failure: In the case of “Last Value” the value is stopped at the last valid value, in the case of “Fail Value” the “Burnout” value is loaded in the registers.

SET ANALOG INPUTS TC BURNOUT VALUE In the case of thermocouple measurement, if the ANALOG INPUT BURNOUT MODE = “FAIL VALUE” mode is activated and the sensor is in the “burn” state, it allows you to set a value in °C to be taken by the measurement register.

PT100 3 WIRE Allows you to choose whether the temperature value detected by input 1 is used for cold junction compensation of all TCs (which have cold junction compensation enabled) or as a temperature measurement.

5.5.4. R-SG3-P
FUNCTION MODE It allows to configure the basic operation of the device, can be set to factory calibration or to Calibration with standard weight:

FACTORY CALIBRATION It is used when a load cell with declared sensitivity is available. In this mode, calibration only consists in acquiring the tare directly in the field with a direct measurement. If it is not possible to acquire the tare with a direct measurement (for example in the case of an already filled silo) it is possible to manually enter the tare value in the desired unit of measurement (kg, t, etc.).

CALIBRATION WITH STANDARD WEIGHT It is used when a standard weight is available (as far as possible towards the load cell full scale). In this mode the calibration consists in acquiring both the tare and the standard weight directly on the field.

MEASURE TYPE It allows to configure the operation of the device between:

BALANCE (UNIPOLAR) It is used when a scale is being created in which the load cell is only compressed, in this case the maximum resolution of the compression measurement is obtained.

COMPRESSION AND TRACTION (BIPOLAR)

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 32

User Manual

R-P SERIES

It is used when a measurement system (typically of force) is being created that can both compress and extend the load cell. In this case the direction of the force can also be decided, if compression the measurement will have the + sign, if traction it will have the – sign. A typical case of use is to link the direction of the force to the analog output so that, for example, 4mA correspond to the maximum traction force and 20mA correspond to the maximum compression force (in this case the cell at rest will provide 12Ma).

MEASURE UNIT Sets the unit of measurement for the weighing in g, Kg, etc.

CELL SENSITIVITY It is the declared cell sensitivity value expressed in mV/V (in most cells it is 2mV/V).

CELL FULL SCALE It is the full scale value of the cell expressed in the selected unit of measurement.

STANDARD WEIGHT VALUE It represents the value of the standard weight that will be used in the calibration if the operating mode with standard weight has been chosen.

NOISE FILTER Enables or disables measurement filtering.

FILTER LEVEL Allows you to set the measurement filter level according to the following table:

FILTER LEVEL 0 1 2 3 4 5 6
ADVANCED

RESPONSE TIME [ms] 2 6.7 13 30 50 250 850
Configurable

The higher the filter level the more stable (but slow) the weight measurement will be. If you select the advanced filtering level (Advanced), the configuration will allow you to select the following parameters:

ADC SPEED Selects the ADC acquisition speed from 4.7 Hz to 960 Hz

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 33

User Manual

R-P SERIES

NOISE VARIATION It is the variation in ADC points due to noise alone (represents the measurement uncertainty due to noise) or how much we expect the measurement to vary (the unit of measurement is in raw ADC points).
FILTER RESPONSE SPEED Represents a parameter related to the filter response speed, it can vary from 0.001 (slowest response) to 1 (fastest response). Represents the variance of the process.
NET WEIGHT RESOLUTION It is the resolution with which the value of the net weighing is represented, it can be worth:
MAXIMUM RESOLUTION It will represent the net weight with the highest possible resolution
MANUAL It will represent the net weight with the manual resolution set (in engineering units). For example, by setting 0.1 Kg you will get that the net weight can only vary by multiples of 100g.
AUTOMATIC RESOLUTION It will represent the net weight with a calculated resolution of about 20000 points. Unlike Maximum or Manual resolution, this setting limits also the ADC value and therefore affects all measurements.

CAUTION
Keep in mind that in the “Calibration with standard weight” mode, using the “Manual Resolution”, the correct standard weight value may not be perfectly represented:

Cell full scale 15000 g Standard weight 14000 g Manual Resolution 1.5 g

For example, you have:

The value of the standard weight (14000 g) cannot be represented with the resolution in 1.5g steps (14000/1.5g = 9333.333 is not an integer value) so it will be represented as: 9333*1.5g = 13999.5g To avoid this effect, use a resolution that allows the value to be represented (for example 1g or 2g).

SAMPLE PIECE WEIGHT

Sets the weight of a single piece in technical units for the mode. By setting the net weight of a single element in this register, the converter will be able to indicate the number of pieces present in the scales special register according to the relation:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 34

User Manual

R-P SERIES

=

AUTOMATIC TARE TRACKER It allows you to enable or disable the automatic tare reset.

ADC VALUE It allows to set the number of ADC points within which to reset the tare automatically. If after 5 seconds of stable weighing condition the ADC value of the net weight deviates by less than this value then a new tare is acquired.
DELTA WEIGHT Weight variation that contributes to the definition of “Stable Weight”
DELTA TIME [x100ms] Time variation that contributes to the definition of “Stable Weight”

STABLE WEIGHT (Stable weighing condition)

The stable weighing condition is used to indicate that the net weight measurement is stable if:

The net weight remains within the weight _ over time or if the slope of the curve drawn

by the net weight is less than

_

:

You will be prompted to enter Delta Net Weight (Delta Weight) (in engineering units) and Delta Time (Delta Time) (in 0.1 seconds).

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 35

User Manual

R-P SERIES

ANALOG OUTPUT WORKING MODE Select whether the analogue output is linked to the net measurement or controlled by the Profinet io protocol.
ANALOG OUTPUT TYPE Select whether the analogue output is Voltage or Current
DIGITAL I/O MODE Configure the device’s digital I/O as input or output
FUNCTION Configure the operation if the I/O is configured as a digital input:
ACQUIRE TARE In this mode, if the digital input is activated for a time longer than 3 seconds, a new tare value is acquired (in RAM, then it is lost upon restart). It is equivalent to sending the command 49594 (decimal) in the command register.
DIGITAL INPUT The input is configured as a digital input whose value can be read from the appropriate register.

DIGITAL OUTPUT MODE In the case of configuring the I/O as a digital output it is possible to choose whether this should be configured as normally open (Normally Open) or as normally closed (Normally Close)

DIGITAL OUTPUT CONFIGURATION Here you can choose the behaviour of the digital output:
FULL SCALE CELL The digital output is activated if the cell has reached the measurement full scale.

THRESHOLD AND STABLE WEIGHT In this mode, the output activates when the net weight reaches the threshold and the weigh is in a stable weighing condition

STABLE WEIGHT

The stable weighing condition is used to indicate that the net weight measurement is stable if:

The net weight remains within the weight _ over time or if the slope of the curve

drawn by the net weight is less than

_

:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 36

User Manual

R-P SERIES

. STABLE WEIGHT In this mode the output is activated if the weighing is in the stable weighing condition.
COMMANDABLE FROM PROFINET In this mode the digital output can be controlled by the Profinet IO protocol.
THRESHOLD WITH HYSTERESIS In this mode the output is activated when the net weight reaches the threshold, the alarm is cancelled when the net weight falls below the Threshold-Hysteresis value:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 37

User Manual

R-P SERIES

5.5.5. R-4AO-8DIDO-P
SET ANALOG MODE Sets the type of output from -10 to +10 V or from 0 to 20 mA
SET ANALOG OUTPUT WATCHDOG Set the watchdog mode of the analog outputs. If “Disabled”, it disables the watchdog function for the selected output. If “Enabled on Profinet Communication” the output loads the value “AO watchdog fault value” if there has not been a Profinet communication within the set time.
SET ANALOG OUTPUT WATCHDOG TIMEOUT [s] Represents the watchdog time of the analog output in seconds. If the PLC stops communicating with the device within the set time, then the output will load the value set in “AO watchdog fault value” (if the function is enabled).
SET ANALOG WATCHDOG OUTPUT FAULT VALUE Sets the value that the analog output must adopt if the watchdog has been triggered.
SET START/END ELECTRICAL SCALE Represents the electrical start and end scale of the analog output used for the engineering measurement register (scaled). The value to enter is in the unit of measurement of output chosen [mV], or [uA] SET START/END ELECTRICAL SCALE Represents the engineering start and end scale of the analog output
Example:
ANALOG START ELECTRICAL SCALE = 4000 [uA] ANALOG END ELECTRICAL SCALE = 20000 [uA] ANALOG START ENG. SCALE = -200 [meters] ANALOG END ENG. SCALE = 200 [meters] We will have that by writing: The output at -200 will provide 4 mA The output at 0 will provide 12 mA The output at +200 will provide 20 mA
ATTENTION!

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 38

User Manual

R-P SERIES

IF YOU SET STAR/END ELECTRICAL SCALE AND START/END ENG. SCALE AT 0 THE SCALE IS NOT ACTIVE AND THE OUTPUT WILL BE DRIVEN DIRECTLY IN [mV] or [uA]

SET DIGITAL IO INPUT/OUTPUT Selects whether the selected digital input will work as an input or output.
SET DIGITAL INPUT NORMALLY HIGH/LOW If selected as digital input, it configures whether the input is normally high or low.
SET DIGITAL OUTPUT NORMALLY OPEN/CLOSE If selected as digital output, it configures whether the output is normally open or closed.
SET DIGITAL OUTPUT WATCHDOG If selected as digital output, it sets the output watchdog mode. If “Disabled”, it disables the watchdog function for the selected output. If “Enabled on Profinet Communication” the output goes into “Watchdog state” if there has been no generic Profinet communication within the set time.
SET DIGITAL OUTPUT WATCHDOG STATE Sets the value that the digital output must adopt if the watchdog has been triggered.
SET DIGITAL OUTPUT WATCHDOG TIMEOUT [s] Represents the watchdog time of the digital output in seconds. If the PLC stops communicating with the device within the set time, then the outputs will go into the “Watchdog state” condition (if the function is enabled).
5.6. R-32DIDO-P I/O DATA
Define the PLC tags directly in the “standard tag table”:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 39

User Manual
Now let’s add the variables related to the IO, the addresses are shown here:

R-P SERIES

So: The bytes from I1 to I4 contain the inputs (bit 0 is IO1, bit 1 is IO2 etc.) Bytes Q1 to Q4 contain the outputs (bit 0 is IO1, bit 1 is IO2 etc …), obviously only the outputs are writable.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 40

User Manual

R-P SERIES

Below is the default mapping of available IOs:

INPUT/OUTPUT
IO1 IO2 IO3 IO4 IO5 IO6 IO7 IO8 IO9 IO10 IO11 IO12 IO13 IO14 IO15 IO16 IO17 IO18 IO19 IO20 IO21 IO22 IO23 IO24 IO25 IO26 IO27 IO28 IO29 IO30 IO31 IO32

DEFAULT ADDRESS IO CONFIGURED AS AN
INPUT I1.0 I1.1 I1.2 I1.3 I1.4 I1.5 I1.6 I1.7 I2.0 I2.1 I2.2 I2.3 I2.4 I2.5 I2.6 I2.7 I3.0 I3.1 I3.2 I3.3 I3.4 I3.5 I3.6 I3.7 I4.0 I4.1 I4.2 I4.3 I4.4 I4.5 I4.6 I4.7

DEFAULT ADDRESS IO CONFIGURED AS AN
OUTPUT Q1.0 Q1.1 Q1.2 Q1.3 Q1.4 Q1.5 Q1.6 Q1.7 Q2.0 Q2.1 Q2.2 Q2.3 Q2.4 Q2.5 Q2.6 Q2.7 Q3.0 Q3.1 Q3.2 Q3.3 Q3.4 Q3.5 Q3.6 Q3.7 Q4.0 Q4.1 Q4.2 Q4.3 Q4.4 Q4.5 Q4.6 Q4.7

So if, for example, I need 16 inputs and 16 outputs, I can use the Booleans from I1.0 to I2.7 for the inputs (which will therefore be found in the IO1 … IO16) and the Booleans from Q3.0 to Q4.7 for the outputs (which will then be found in the IO17 … IO32).

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 41

User Manual

R-P SERIES

ATTENTION!
An IO configured as an input cannot be controlled as an output. An IO configured as an output cannot be read as an input.
Always following our example (16 inputs and 16 outputs) we define the 16 inputs and 16 outputs in the standard variables table:

Now compile, send the project and go online with the PLC.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 42

User Manual
Once online, press the glasses icon to update the status of the variables.

R-P SERIES

Under the “Control value” column you can read the I/O value in real time.
To control the outputs, it is necessary to enter “TRUE” or “FALSE” in the “Command value” column and then press the icon with the lightning bolt to order the writing. Note the status of the LED relating to the commanded output.
In the “Control value” column, the status of the outputs is also read in real time.
5.7. R-16DI-8DO-P I/O DATA
Define the PLC tags directly in the “standard tag table”:

Add the tags related to the IO (in the example it is an R-16DI-8DO that is 16 digital inputs and 8 digital outputs). The addresses are written here:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 43

User Manual
So bytes I1 and I2 contain the 16 inputs, byte Q1 the 8 outputs:

R-P SERIES

After this operation, define a new control table: Click on “Add new control table” and then insert the variables

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 44

User Manual

R-P SERIES

Since you have already defined them previously, just select the ones we want to monitor from the list:

Once you have added all of them you will get:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 45

User Manual

R-P SERIES

Now compile, send the project and go online with the PLC (all operations seen previously): Once online, press the glasses icon to update the status of the variables:

Under the “Control value” column you can read the I/O value in real time.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 46

User Manual

R-P SERIES

To control the outputs, it is necessary to enter “TRUE” in the “Command value” column and then press the icon with the lightning bolt to order the writing:

In the “Control value” column, the outputs are now correctly read to “True”.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 47

User Manual
5.8. R-8AI-8DIDO-P I/O DATA Define the PLC tags directly in the “standard tag table”:

R-P SERIES

Let’s now add the variables relating to the IO. For example the addresses are written here:

So byte I1 contains the 8 digital inputs (those as inputs), byte Q1 the 8 outputs (those configured as outputs). Bytes from I68 to I83 show the values of the 8 analog inputs (2 bytes per input). Bytes from I84 to I15 show the values of the 8 analog inputs floating point (4 bytes per input). Byte I2 shows the burnout status of the analog inputs configured by thermocouple.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 48

User Manual

R-P SERIES

Below is the default mapping of the available digital IOs:

INPUT/OUTPUT
IO1 IO2 IO3 IO4 IO5 IO6 IO7 IO8

DEFAULT ADDRESS IO CONFIGURED AS AN
INPUT I1.0 I1.1 I1.2 I1.3 I1.4 I1.5 I1.6 I1.7

DEFAULT ADDRESS IO CONFIGURED AS AN
OUTPUT Q1.0 Q1.1 Q1.2 Q1.3 Q1.4 Q1.5 Q1.6 Q1.7

The default mapping of the analog IOs is as follows:

INTEGER ANALOG INPUT AIN1 AIN 2 AIN 3 AIN 4 AIN 5 AIN 6 AIN 7 AIN 8

DEFAULT ADDRESS INPUT IW2 IW4 IW6 IW8 IW10 IW12 IW14 IW16

FLOATING POINT ANALOG INPUT
AIN1 AIN 2 AIN 3 AIN 4 AIN 5 AIN 6 AIN 7 AIN 8

DEFAULT ADDRESS INPUT ID18 ID22 ID26 ID30 ID34 ID38 ID42 ID44

5.9. R-SG3-P I/O DATA
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 49

User Manual
Define the PLC tags directly in the “standard tag table”:

R-P SERIES

Let’s now add the variables relating to the IO. For example the addresses are written here:
WEIGHT (INTEGER)

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 50

Where: DIN/DOUT

User Manual

WEIGHT INTEGER
NET WEIGHT GROSS WEIGHT TARE WEIGHT
NUM. PIECES

DEFAULT ADDRESS INPUT ID2 ID4 ID6 IW8

R-P SERIES

INPUT/OUTPUT
IO1 IO2

DEFAULT ADDRESS IO CONFIGURED AS AN
INPUT I1.0 I1.1

DEFAULT ADDRESS IO CONFIGURED AS AN
OUTPUT Q1.0 Q1.1

Optionally you can add:

ANALOGUE OUTPUT (NOT USABLE ON THE R-SG3-P MODEL)

It allows you to control the analogue voltage/current output by providing the value in uA or mV

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 51

COMMAND

User Manual

R-P SERIES

It allows you to send commands to the device: COMMAND (DECIMAL) 43948 49594 49914
50700
50773
49151 45056

FUNCTION Reboot the device Acquires the tare in RAM (at reboot
is lost) Acquires the tare in Flash for the
calibration procedure in both operating modes (factory calibration
and with sample weight) Acquires the sample weight value in Flash for calibration with standard
weight Acquires the tare value from the
register MANUAL TARE (only for the factory calibration mode)
Reset the maximum net weight Reset the register with the minimum
net weight

DIAGNOSTIC

BIT 0 LSBIT (RO) Bit 0 = 1 THRESHOLD AND STABLE WEIGHT for DIDO 1

BIT 1 (RO) Bit 1 = 1 FULL SCALE CELL

BIT 2 (RO) Bit 2 = 1 NET WEIGHT < 0

BIT 3 (RO) Bit 3 =1 THRESHOLD AND STABLE WEIGHT for DIDO 2

BIT 4 (RO) Bit 4 = 1 Stable weight
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 52

User Manual
BIT 5-6 Not used BIT 7 (RO) Bit 7 = 1 Threshold with hysteresis for DIDO 1 BIT 8 (RO) Bit 8 = 1 automatic tare tracker (if enabled) BIT 9 (RO) Bit 9 = 1 Threshold with hysteresis for DIDO 2 BIT 10..15 Not used
WEIGHT (FLOAT)

R-P SERIES

5.10. R- 4AO-8DIDO-P I/O DATA Define the PLC tags directly in the “standard tag table”:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 53

User Manual

R-P SERIES

Let’s now add the variables relating to the IO. For example the addresses are written here:

Bytes from Q64 to Q71 show the values of the 4 analog outputs in signed integer (2 bytes per output). byte I1 contains the 8 digital inputs (those configured as inputs), byte Q1 the 8 outputs (those configured as outputs). Bytes I2 and I3 show the status of the analog output.
4AO

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 54

User Manual

R-P SERIES

They represent the value to be driven of the analog output in engineering units. The data type is signed 16-bit integer.
8DIDO
Below is the default mapping of the available digital IOs:

INPUT/OUTPUT
IO1 IO2 IO3 IO4 IO5 IO6 IO7 IO8

DEFAULT ADDRESS IO CONFIGURED AS AN
INPUT I1.0 I1.1 I1.2 I1.3 I1.4 I1.5 I1.6 I1.7

DEFAULT ADDRESS IO CONFIGURED AS AN
OUTPUT Q1.0 Q1.1 Q1.2 Q1.3 Q1.4 Q1.5 Q1.6 Q1.7

AO STATUS Shows the status of the analog outputs:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 55

User Manual

R-P SERIES

5.11. COMPILATION AND SENDING OF THE PROJECT TO THE SIEMENS PLC
Now that the devices are configured, all that remains is to compile and send the configuration to the PLC.
ATTENTION!
YOU MUST ALWAYS DO A FULL HARDWARE COMPILATION BEFORE SENDING A PROJECT TO THE DEVICE:

Before sending the project to the PLC, you are asked to select the ethernet interface and start the search, in order to select the PLC and press “Load”.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 56

User Manual

R-P SERIES

Once the project has been sent, RUN the PLC: And go On-Line so as to check if there are any errors: If everything is correct you will get a green icon next to the Seneca device:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 57

User Manual

R-P SERIES

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 58

User Manual

R-P SERIES

6. EXAMPLE OF CREATING A PROJECT WITH PLC CODESYS 3.5
Create a new standard project:

6.1.1. INSERTION OF THE CODESYS PLC IN THE PROJECT Configure the PLC by selecting it in the tree on the left and then browsing the network:
Select the PLC after scanning the network:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 59

User Manual
The PLC is now connected to the system:

R-P SERIES

Now that the PLC has been detected, move on to insert a Profinet port on standard Ethernet: Right click on device and “add device”:

Then add the Profinet IO Master:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 60

User Manual

R-P SERIES

Double click on Ethernet, set the Ethernet port and the IP address of the PLC (in this case use 192.168.90.44):

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 61

User Manual
Set also the address range for the Profinet peripheral, double click on PN_Controller:

R-P SERIES

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 62

User Manual

R-P SERIES

6.1.2. INSTALLING THE GSD
Now you need to connect the Seneca slave device PROFINET IO to the profinet master (controller). First install the GSD file of the Seneca IO. Select Tools->Device Repository:

Now import the GSD file by selecting Profinet IO Slave and then Install:

Now point to the correct folder and press OK. Codesys has now added the GSD file correctly.
At this point you can scan the network in search of Slave devices (Device).

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 63

User Manual
First compile the project and log in to the PLC:

R-P SERIES

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 64

User Manual
6.1.3. INSTALLATION OF THE SENECA PROFINET IO Now that you are connected to the PLC, run the scan to find the devices:

R-P SERIES

In the list of devices, select the Seneca IO and then “Copy to project”:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 65

User Manual
At this point you have added the device to the project:

R-P SERIES

6.1.4. CONFIGURATION OF THE PARAMETERS OF THE SENECA IO If you want to change the IO configuration parameters, you can set them from here:

Check that everything is correct by compiling and running the PLC.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 66

User Manual

R-P SERIES

The PLC (Raspberry-pi) is quite slow and not real time, consequently it cannot manage the profinet at maximum speed so we modify the values by setting safety parameters:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 67

User Manual

R-P SERIES

6.1.5. READING AND WRITING THE SENECA IO FROM CODESYS
Now see how it is possible to read and write IO on the Seneca device. To write and read the status of the IO you have to insert a few code lines under PRG. In the program, read the inputs from the %IW2 address and write in the %QB0 address as it is obtained from here:

Declare an 8-bit (Word) variable for the 16 inputs and one byte for the 8 outputs. In the program, instead, read the inputs from %IW2 and write the outputs on %QB0:

Go into login and start.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 68

User Manual
The value of the inputs can be read here:

R-P SERIES

while to write the outputs you just set the byte value in the “prepared value” column, for example by writing 255 decimal = 11111111 binary all the outputs will be brought to 1:

And then with “Write values” all the outputs are activated correctly.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 69

User Manual

R-P SERIES

7. CABLE HARNESS FOR MODELS WITH DOUBLE ETHERNET PORT
Models with double Ethernet port can be connected in daisy chain and take advantage of the Lan Fault Bypass.
7.1. CHAIN ETHERNET CONNECTION (DAISY CHAIN)
Using the daisy chain connection it is not necessary to use switches to connect the devices. An example (in this case on R-16DI-8DO-P) of connection of 3 devices is as follows:

ATTENTION!
IT IS NOT POSSIBLE CREATE LOOPS WITH ETHERNET CABLES

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 70

User Manual
If it is necessary to connect the devices to the switches, correct wiring is as follows:

R-P SERIES

In the Ethernet wiring there must be no loop, otherwise the communication will not work, some examples of incorrect wiring are the following:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 71

User Manual

R-P SERIES

7.2. LAN FAULT-BYPASS FUNCTION
The LAN fault-bypass function allows you to keep the connection between the two Ethernet ports of the device ON, in the event of power failure problems. If a device turns off, the chain is not interrupted and the devices downstream of the switched-off one will still be accessible. This function has a limited duration: the connection remains active for a few days, typically 4. The Lan fault-bypass function requires that the sum of the lengths of the two cables connected to the switched off module is less than 100m.

8. SEARCH AND MODIFICATION OF THE DEVICE IP WITH SENECA DISCOVERY TOOL
When in the R series device the STS LED is on steady, it is possible to obtain the IP address which has been set using the “Seneca Discovery” tool too.
The software can be downloaded from:
https://www.seneca.it/en/linee-di-prodotto/software/easy/sdd
Pressing the “search” button starts the search for all Seneca devices present in the network even if with IP addresses not compatible with the current PC configuration:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 72

User Manual

R-P SERIES

It is now possible to change the address by pressing the “Assign” button:

The software works on layer 2 level and it is therefore not necessary to have an Ethernet configuration compatible with the device you are looking for.
ATTENTION!
AS LONG AS THE STS LED IS FLASHING IT MEANS THE DEVICE HAS NOT SET AN IP ADDRESS. IN THIS SITUATION IT WILL NOT BE POSSIBLE TO SEARCH FOR THE DEVICE WITH THE SENECA DISCOVERY TOOL SOFTWARE

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 73

User Manual
9. FIRMWARE UPDATE
The firmware update can be performed via the web server in the appropriate section.

R-P SERIES

ATTENTION!
BEFORE ACCESSING THE WEB SERVER, DISCONNECT THE DEVICE FROM THE PROFINET NETWORK
ATTENTION!
NOT TO DAMAGE THE DEVICE DO NOT REMOVE THE POWER SUPPLY DURING THE FIRMWARE UPDATE OPERATION.

ATTENTION!
THE DEVICES ARE SUPPLIED BY THE FACTORY WITHOUT AN IP ADDRESS (0.0.0.0) IN THIS CASE THE “STS” LED FLASHES.
TO SET AN IP ADDRESS (FOR EXAMPLE TO ACCESS THE WEBSERVER OR TO CONNECT TO THE SENECA DISCOVERY DEVICE TOOL) USE THE PROFINET CONFIGURATION ENVIRONMENT OR FORCE THE ADDRESS 192.168.90.101 WITH THE APPROPRIATE DIP SWITCH

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00605-9-EN

Page 74

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals