MIKSTER INDU 20 Temperature Recording System User Manual
- September 2, 2024
- MIKSTER
Table of Contents
INDU 20 Temperature Recording System
“`html
Technical Specifications
-
Power supply:
-
Power consumption:
-
Housing:
-
Dimensions: One-piece Front Panel 134x134x65mm
-
Mounting hole: 90x90mm
-
Weight: 500g
-
Display:
-
Keyboard:
-
Temperature measurement range:
-
Temperature measurement resolution:
-
Inputs: 1x analogue PT100/PT500/PT1000, 2x control (alarm
signaling or keyboard lockout) -
Outputs: 1x analogue 0/4..20mA, 4x relay
-
Other features: Internal vacuum sensor
-
IP rating: IP65 (front) IP20 (rear)
-
RTC: Yes
-
Communication: 1xRS485
-
Registration: 100000 records*
-
Operating conditions: AUTOSTART according to RTC, with advanced
programming (up to 10 days) -
Types of temperature control: 2 types of bistable governors and
the PID governor -
Ending of the process: Set time or manually
Product Usage Instructions
3. Start Up
NOTE: In case of power failure, the controller
remembers the mode of operation and returns to this mode upon power
supply restart (unless the time set in the 48 Setup cell
expires).
3.1 Operating Panel
The operating panel includes:
- RTC CLOCK/PROCESS TIME
- NEGATIVE PRESSURE VALUE
- KEY OF THE AUTOSTART MODE
- KEY OF THE INFO MODE
- KEY OF THE START MODE
3.4 Autostart Mode
The autostart mode is used to enter the START mode with a time
delay.
To set the autostart moment:
- Setup – HMD
- Activation after a predetermined number of hours and minutes
(F47 SETUP – HM)
To exit the AUTOSTART mode, press the AUTO/START key again. You
can transition directly from AUTOSTART to START mode by pressing
the START key when the controller is in START mode.
Frequently Asked Questions (FAQ)
Q: How do I edit the set parameters of the process?
A: To enter the mode of editing set parameters, press the
corresponding key. The mode is indicated by the pulsation of the
diode on the key EDIT. Use the keys for correction of parameters.
The parameter being edited will pulsate, and confirmation and
proceeding to the next editing field is done by the OK key.
Pressing EDIT repeatedly means exiting from the editing mode.
“`
EN
INDU 20
USER MANUAL v1.6(19)EN
ul. Wojkowicka 21, 41-250 Czelad, Poland tel. +48 32 763 77 77 fax: +48 32 763
75 94 mikster.eu
CONTENTS
User manual INDU 20 v1.6(19)EN
CONTENTS …………………………………………………………………………………………………………………………………………………………………..2 1.
TECHNICAL SPECIFICATIONS………………………………………………………………………………………………………………………………..3 2.
DIMENSIONS ………………………………………………………………………………………………………………………………………………………..4 3.
START UP …………………………………………………………………………………………………………………………………………………………….4
3.1 OPERATING PANEL……………………………………………………………………………………………………………………………………….4 3.2
EDIT MODE CHANGING OF THE SET VALUES ………………………………………………………………………………………………5
3.3 INFO MODE…………………………………………………………………………………………………………………………………………………..5 3.4
AUTOSTART MODE ……………………………………………………………………………………………………………………………………….6 3.5 START
MODE………………………………………………………………………………………………………………………………………………..6 4. FUNCTION OF
RELAYS ………………………………………………………………………………………………………………………………………….7 5. GOVERNOR OF
THE “TEMPERATURE APPROACH” …………………………………………………………………………………………………7 6. SELECTION
OF SETTINGS OF THE PID GOVERNOR ………………………………………………………………………………………………..7 7.
FUNKCJE SERWISOWE DOSTPNE DLA UYTKOWNIKA …………………………………………………………………………………………8
8. ALARMS ……………………………………………………………………………………………………………………………………………………………….8 9.
CONTROLLER SETUP ……………………………………………………………………………………………………………………………………………9 10.
EXAMPLE OF APPLICATION* ………………………………………………………………………………………………………………………………….14
| 2
www.mikster.eu
User manual INDU 20 v1.6(19)EN
1. TECHNICAL SPECIFICATIONS
Power supply:
Power consumption:
Housing:
Dimensions:
230VAC option: 24VAC, 110VAC ± 10% VAC 3 W
One-piece Front Panel 134x134x65mm
Mounting hole: Weight: Display:
Keyboard: Temperature measurement range: Temperature measurement resolution:
Inputs:
Outputs:
Other features: IP rating:
RTC: Communication:
90x90mm
500g
LED ½ ” x 4 digits LED ½ ” x 2 digits LED ½ ” x 2 digits Micro switch buttons
30°C ÷ 400°C
0,1°C od 9,9°C do 99,9°C 1°C in other ranges
1x analogue PT100/PT500/PT1000 2x control (alarm signaling or keyboard
lockout)
1x analogue 0/4..20mA 4x relay
Internal vacuum sensor
IP65 (front) IP20 (rear)
Yes
1xRS485
Registration:
Operating conditions:
100000 records*
Temperature: 0°C ÷ 55°C Humidity: 5%RH ÷ 85%RH
AUTOSTART: according to RTC, with the possibility of an advanced programming
(up to 10 days) of the controller switching on.
Types of the temperature control: 2 types of bistable governors and the PID
governor.
Ending of the process can be done either by the set time or manually.
- recording module, R – version
www.mikster.eu
| 3
2. DIMENSIONS 134mm
User manual INDU 20 v1.6(19)EN
65mm
134mm
80mm
3. START UP
After the mains are connected the controller is automatically activated. After
the welcoming words the device displays in turn: current hour and minute,
measurement in channel 1 vacuum in %, set value of the rotational speed of
the drum. Three horizontal lines indicate the lack or failure of a measuring
element. Diodes on the keys signal the mode of the device (e.g. editing or
autostart mode). Horizontal lines at the left side of the displayed measured
value signal the governor’s mode: controlled output causes that the diode
lights. Diodes on the keys indicate the controller’s mode. Possible modes of
operation are: AUTOSTART, START, INFO and EDIT. In the STOP mode, when the
START mode ended, the word ,,STOP” is displayed on the screen instead of an
hour and minute.
NOTE: in the case of power failure the controller remembers the mode of
operation and returns to this mode at the power supply restart. (unless the
time set in the 48 Setup cell expires).
3.1 OPERATING PANEL
RTC CLOCK/ PROCESS TIME
NEGATIVE PRESSURE VALUE
ROTATIONAL SPEED SET VALUE
KEY OF THE AUTOSTART MODE
KEY OF THE INFO MODE
KEY OF THE START MODE
| 4
www.mikster.eu
User manual INDU 20 v1.6(19)EN 3.2 EDIT MODE CHANGING OF THE SET VALUES
In order to enter the mode of editing the set parameters of the process the key should be pressed mode is indicated by pulsation of the diode on the key EDIT.
. Entering into the edit
Keys
are used for correction of parameters. Parameter being edited is pulsating, confirmation and proceeding
to the next editing field is done by the OK key. Consecutive pressing of the key EDIT means exit from the editing mode.
The set parameters are co:
– START mode duration (number of hours and minutes)
– Negative pressure set value
– Rotational speed set value
3.3 INFO MODE
Single pressing of the
causes the display of information in dependence of the controller’s mode of operation::
For the AUTOSTART mode Depending on the parameter in the 47 Setup cell: At selecting HMD hour, minute and twenty-four hours delay before the START mode commences, At selecting HM number of hours and minutes remaining to the START mode
Consecutive information, for all modes, are the same: · temperature measurement: the upper display shows the current temperature measurement in channel 1, the lower reads TE, · the upper display shows PSET, the middle one the negative pressure (set value), the lower display indicates the rotational speed of the drum, · current date: starting from the upper display – one can read the year, month and day, · current time: starting from the upper display – one can read hour, minute and second.
Proceeding into the next (previous) information can be done by keys should be pressed again.
. To exit the INFO mode the INFO key
www.mikster.eu
| 5
3.4 AUTOSTART MODE The autostart mode is used for entering the START mode with a time delay.
User manual INDU 20 v1.6(19)EN
Pressing
causes transition to the parameters editing of this mode.
There are two possibilities of setting the moment of the controller AUTOSTART:
Activation at the predetermined hour and minute with the possibility of adding the twenty-four hour delay (F47
SETUP – HMD).
Activation after the predetermined number of hours and minutes (F47 SETUP – HM)
To exit the AUTOSTART mode the AUTO/START key should be pressed again.
There is also a possibility of a direct transition from the AUTOSTART into the START mode. Single pressing of the START key is needed.
3.5 START MODE When all set parameters are introduced (see: EDIT MODE CHANGING OF THE SET VALUES) the process can begin, which means
the controller should be in the START mode. Beginning and ending of the START mode is done by pressing the key:
.
For the typical settings of the controller, entering the START mode activates governors and the countdown of the process time starts.
The display shows the number of hours and minutes remaining to the end of the process.
The end of the process is indicated by the internal sound signal of the controller and by controlling of the relay output REL5 (unless it is declared in the SF81 Setup as the temperature governor). If the cell SF81 value is set to 2 relays REL4, REL5 work in the Left/Right turnover.
SF81 2 REL4 and REL5 carries out the functions, which illustrate the chart.
SF75 TL – time relay attach turnover LEFT (default = 10sek.) SF76 TR – time
relay attach turnover RIGHT (default = 10sek.) SF77 Tp pause time (default =
20sek) Pressing the OK key switches off the sound signal.
| 6
www.mikster.eu
User manual INDU 20 v1.6(19)EN
4. FUNCTION OF RELAYS
REL 2: is responsible for the increase of the negative pressure and the pump
controlling (governor: simple hysteresis). REL 3: is responsible for the
decrease of the negative pressure (governor: reversed hysteresis). REL 4:
controlled in the START mode. REL 5: temperature regulation or alarm event
signaling.
5. GOVERNOR OF THE “TEMPERATURE APPROACH”
Parameters:
Tz set temperature value. Tza temperature of the governor activation; up
to this temperature the output is controlled (heating). When this temperature
is reached the governing algorithm starts.
Dout state at the digital output (high state corresponds to the heaters
being ON).
6. SELECTION OF SETTINGS OF THE PID GOVERNOR
To obtain an access to the settings of the PID governor coupled with the
particular measuring channel the MINUS key should be pressed and held and then
the INFO key. If the temperature governor is selected on the relay (REL 5) the
upper display shows the information that the governor can be adjusted the OK
key should be pressed. The edition of the selected parameter is being done on
the middle display (pulsating value). Increasing of the parameter’s value can
be done by the PLUS key, while decreasing by the MINUS key. Proceeding to the
next parameter and confirmation of changes is done by pressing OK. Exit from
the edition mode – by pressing the EDIT key.
Regulation is being done on the bases of:
To sampling period, Pr amplification of the proportional element, Ti
integration constant (doubling time), Td differential constant (advancing
time), TS set temperature, Writing 0 value for the integrating or
differentiating element causes its switching off. Due to that feature, it is
possible to obtain the arbitrary governing algorithm.
www.mikster.eu
| 7
User manual INDU 20 v1.6(19)EN
7. FUNKCJE SERWISOWE DOSTPNE DLA UYTKOWNIKA
Cell number
Description
F0
Setting of the real time clock. Next parameter is reached by the OK key.
F1
Change of the access code for the user
Range 0..9999
For 0 value checking of the access code is switched off
F2
Information concerning the current program version
F3
Switching ON/OFF of the keyboard click
OFF switching off
ON switching on
To enter the user’s mode the MINUS key should be pressed and held, the PLUS key should be pressed and held. Those functions are
accessible when the access code is given. The access code is introduced by To
switch off the checking of the access code its value should be set as zero. As
a rule the access to the user’s settings is switched off.
8. ALARMS
Controller INDU 20 signals 11 alarm events: · Err1 Failure of the internal
sensor of negative pressure, · Err2 Failure or lack of the measuring element
in the channel 1 (temperature), · Err3 · Err4 Permissible MAX negative
pressure exceeded, · Err5 Permissible MAX temperature exceeded, · Err6 · Err7
Permissible MIN negative pressure exceeded, · Err8 Permissible MIN temperature
exceeded, · Err9 · Err10 Alarm from the control input 1, · Err11 Alarm from
the control input 2.
keys.
The first step in an alarm activation is the setting of the time delay
[seconds] in SETUP (cells 71..73) between an alarm event and the alarm
activation. Then the activation of the selected alarms in SETUP (cells 60..70)
should be done.
Alarms are signaled on the display by the word Err with the adequate number,
by internal howler, and – when in Setup cell 81 the relay REL 5 is in the mode
of alarm signaling – by controlling of its output.
Alarm should be confirmed by the OK key. If the cause of an alarm is not
removed, the controller after the time delay of the alarm activation – will
again signal the alarm.
| 8
www.mikster.eu
User manual INDU 20 v1.6(19)EN
9. CONTROLLER SETUP
Nr
Default
value
Range
Description
SF0
1
0..99
Address in the MODBUS network
SF1
0
0..4
Transmission rate:
0 – 9600, 1 – 19200, 2 – 38400, 3 – 57600, 4 – 115200
SF2
1
0..12
Type of the measuring input for channel 1 · 0 PT-500 · 1 PT-100 · 2
PT1000
· 3 0..20mA · 4 4..20mA · 5 thermocouple s · 6 thermocouple b ·
7 thermocouple r · 8 thermocouple t · 9 thermocouple j · 10
thermocouple e · 11 thermocouple k · 12 thermocouple n * – current
input version ** – thermocouple servicing version
SF3
–
–
–
SF4
–
–
–
SF5
0°C
-99,0..999°C Value corresponding to 0 mA for channel 1
for 0..20 mA
SF6
100°C
-99,0..999°C Value corresponding to 20 mA for channel 1
for 0..20 mA
SF7
–
–
–
SF8
–
–
–
SF9
–
–
–
SF10
–
–
–
SF11
0°C
-99,0..999°C Value corresponding to 4 mA for channel 1
for 4..20 mA
SF12
100°C
-99,0..999°C Value corresponding to 20 mA for channel 1
for 4..20 mA
SF13
–
–
–
SF14
–
–
–
SF15
–
–
–
SF16
–
–
–
SF17
0,0°C
-20,0..20°C Temperature correction for channel 1
www.mikster.eu
User settings | 9
User manual INDU 20 v1.6(19)EN
Nr
Default
value
SF18
–
SF19
–
SF20
On
SF21
On
Range
Description
On / Off
On / Off
–
–
Negative pressure governor:
Off always
On only in the START mode
Temperature governor:
User settings
SF22
–
SF23
0
SF24
99
SF25
–
SF26
–
SF27
–
SF28
–
SF29
1
0..99%
0..99%
0..3
Off always
On only in the START mode
–
The lowest negative pressure value, which could be set by the user
The highest negative pressure value, which could be set by the user
–
–
–
–
Temperature governor coupled to relay REL 5
· 0 simple hysteresis · 1 reversed hysteresis · 2 approaching hysteresis · 3 PID
SF30
–
SF31
1
SF32
1
SF33
1
SF34
–
SF35
0
SF36
1,0°C
SF37
1,0°C
SF38
50°C
SF39
–
0..5 0..5 0..5
0..5 0,0..5,0°C 0,0..5,0°C -99..999°C
–
Lower hysteresis for the governor coupled to REL2 Lower hysteresis for the governor coupled to REL3 Lower hysteresis for the governor coupled to REL5 Upper hysteresis for the governor coupled to do REL2 Upper hysteresis for the governor coupled to do REL3 Upper hysteresis for the governor coupled to do REL5 Set temperature –
| 10
www.mikster.eu
User manual INDU 20 v1.6(19)EN
Nr
Default
value
SF40
–
SF41
20°C
SF42
–
SF43
–
SF44
1
SF45
–
SF46
1
SF47
HMD
SF48
5
SF49
1
SF50
1
SF51
°C
SF52 1 [min]
SF53
1
SF54
99
SF55 150°C
SF56
–
SF57
0
SF58
-99°C
SF59
–
SF60
Off
SF61
Off
Range
Description
0..99°C
0..100 sek 0..1
HMD/HM
0..10 godz.
1..360 min 1..360 min
°C/°F 0..99 [min] 0 .. 1
0..99% -99..999°C
0..99% -99..999°C
On / Off On / Off
–
Temperature of activation (Tza) of the governor coupled to REL 5 for the ,,
temperature approach” algorithm
–
–
Time delay of the governor [seconds] coupled to REL 5
–
Recording: · 0 continuous recording · 1 recording only in the START mode
AUTOSTART mode parameters format: · HMD hour, minute and twenty-four hours
delay before the START of the process · HM number of hours and minutes
remaining to the START mode
Maximal time (in hours) after which (when there was a power failure) the
controller does not return to the START mode
Rate of the measurements recording
Rate of alarms recording
Temperature unit
Sound signal – duration. Note! When 0 value entered, the signal can be deleted
by the OK key!
Alarm output mode of operation: · 0 interrupted signal · 1 continuous
signal
Maximal permissible negative pressure (alarm)
Maximal permissible temperature (alarm)
–
Minimal permissible negative pressure (alarm)
Minimal permissible temperature (alarm)
–
Alarm activation failure of the negative pressure sensor
Alarm activation failure of the temperature sensor
User settings
www.mikster.eu
| 11
User manual INDU 20 v1.6(19)EN
Nr
Default
value
SF62
–
SF63
Off
SF64
Off
SF65
–
SF66
Off
SF67
Off
SF68
–
SF69
0
SF70
0
SF71
60
SF72
60
SF73
60
SF74
0
SF75
10
SF76
10
SF77
20
SF78
–
SF79
1
SF80
99
SF81
0
Range
Description
–
–
On / Off Alarm activation – Max negative pressure exceeded
On / Off Alarm activation – Max temperature exceeded
–
–
On / Off Alarm activation – Min negative pressure exceeded
On / Off Alarm activation – Min temperature exceeded
–
–
0..4
Control input 1
0 – alarm switched off
1 alarm, when inputs 6-8 shorted
2 alarm, when inputs 6-8 not shorted
3 keyboard lockout when inputs 6-8 shorted
4 – keyboard lockout when inputs 6-8 not shorted
0..4
Control input 2
0 – alarm switched off
1 alarm, when inputs 7-8 shorted
2 alarm, when inputs 7-8 not shorted
3 keyboard lockout when inputs 7-8 shorted
4 – keyboard lockout when inputs 7-8 not shorted
0..999 sek Time delay in the alarm signaling, when sensors are faulty
0..999 sek
Time delay in the alarm signaling, when the permissible settings are exceeded
0..999 sek
Time delay in the alarm signaling, when there is an alarm on inputs
0..9999
Change of the access code to SETUP
0 value checking the code switched off
0..9999 sek Attach a turnover time of the relay LEFT
0..9999 sek Attach a turnover time of the relay RIGHT
0..9999 sek Pause time
–
–
-99.100
Negative pressure offset for the governor coupled to REL2
0..99
Set speed value corresponding to 20mA on the current output
0..2
Mode of operation of the REL5 relay :
· 0 alarms signaling,
· 1 – temperature governor
· 2 – relays REL4, REL5 operate in a mode
RIGHT/LEFT turnover
User settings
| 12
www.mikster.eu
User manual INDU 20 v1.6(19)EN
Nr
Default
value
SF82
1
SF83
1
SF84
1
SF85
0
SF86
1
SF87
0
Range
Description
0..1
Response to alarm: measuring sensors faulty:
0 – signaling,
1 – process stops
0..1
Response to alarm: settings exceeded
0 – signaling,
1 – process stops
0..1
Response to alarm from the control input
0 – signaling,
1 – process stops
0..1
Type of the current output:
0: 0..20 mA
1: 4..20 mA
0..1
State of the relay output REL3 (aerating valve) when the
controller is not in the START mode
0: REL3 not controlled
1: REL3 controlled (aeration)
0..1
Unit processing time
0 hours:minutes HH:MM
1 – minute:second MM:SS
User settings
www.mikster.eu
| 13
10. EXAMPLE OF APPLICATION*
User manual INDU 20 v1.6(19)EN
14
PORT1 (RS-485)
POWER
30
SUPPLY
+ 28
- The example of application should give the user a general idea only, and can not be considered the project of the control system neither as total nor as its part.
| 14
www.mikster.eu
User manual INDU 20 v1.6(19)EN
NOTES
www.mikster.eu
| 15
NOTES
User manual INDU 20 v1.6(19)EN
| 16
www.mikster.eu