EXHAUSTO 3006129 EXcon Automatic User Guide
- August 28, 2024
- EXHAUSTO
Table of Contents
EXHAUSTO 3006129 EXcon Automatic
Product Information
Specifications
- Product Name: EXcon automatic
- Manufacturer: EXHAUSTO A/S
- Model Number: 3006129-2024-05-29
- Address: Odensevej 76, DK-5550 Langeskov
- Contact: Tel. +45 65 66 12 34, Fax +45 65 66 11 10
- Email: exhausto@exhausto.dk
- Website: www.exhausto.dk
Product Usage Instructions
Alarm Log
In General
Whether an alarm will activate a shutdown will depend on the type of alarm.
A distinction is made between A alarms and B alarms, where A alarms activate a
shutdown.
Alarms
List of current alarms in the system:
- Red alarm text indicates A alarms
- Blue alarm text indicates B alarms
Press Cancel alarms to acknowledge alarms. The list and the active alarms which are still active are restored and displayed.
Frequently Asked Questions (FAQ)
-
How do I acknowledge and cancel alarms?
To acknowledge alarms, press the ‘Cancel alarms’ button. This will restore the list and display the active alarms. -
What do the different alarm text colors indicate?
Red alarm text indicates A alarms that activate a shutdown, while blue alarm text indicates B alarms that do not activate a shutdown.
Alarm log
In general
The parameters in the menu Alarm log are used to log alarms and operating data which have occur-red since the last startup of the VEX unit. A log is kept of which alarms have occurred, which alarms are nearing their limit values and operating data history. The logged alarms can be reviewed via the web user interface or the HMI Touch control panel/manual terminal. Apart from current alarms, the on-line user interface also shows impending alarms and the logged operating data. For a more detailed description of the parameters, see under: User > Alarm & log.
Alarms
Whether an alarm will activate a shutdown will depend on the type of alarm.
A distinction is made between A alarms and B alarms, where A alarms activate a
shutdown.
Alarm summery
Alarm list web server
Alarm nos. 1-99
Alarm no.| Alarm type| Alarm delay. sec.| Alarm limit| Auto reset| Unit stop| ****
Alarm text – WEB Alarm text – POP UP
---|---|---|---|---|---|---
1| A| 3| N/A| | | Fire alarm
Fire alarm via digital input
2| A| 3| N/A| | X| External fire thermostat alarm
External fire thermostat alarm via digital input
3| A| 3| N/A| | X| Internal fire alarm
High supply air/extract air temperature in air handling unit
4| B| 3| N/A| X| X| External stop activated
External stop activated via digital input
7| A| 3| N/A| X| X| Supply air EC controller: No communication
EC controller not connected to bus in FanIO connector B. Fault in bus cable.
The bus cable in EC is connected to FanIO connector A instead of B
8| A| 3| N/A| X| X| Extract air, EC controller: No communication
EC controller not connected to bus in FanIO connector B. Fault in bus cable.
The bus cable in EC is connected to FanIO connector A instead of B
9| B| 1200| N/A| X| | Airflow compensation of filter monitor is not measured
Measurement of filter pressure reference not executed. Triggered after 20
minutes.
10| B| 3| N/A| X| | Manual terminal: No communication
Manual terminal not connected to bus. Fault in bus cable
11| A| 3| N/A| X| X| FanIO 1: No communication
FanIO not connected to bus in FanIO socket A, Error in bus cable, FanIO DIP
switches wrongly set
12| A| 3| N/A| X| X| FanIO 2: No communication
FanIO not connected to bus in FanIO socket A, Error in bus cable, FanIO DIP
switches wrongly set
13| A| 3| N/A| X| X| Expansion module EXT 1: No communication
EXT 1 expansion module not connected to bus. Fault in bus cable. Address
button is wrong.
14| A| 3| N/A| X| X| Expansion module EXT 2: No communication
EXT 1 expansion module not connected to bus. Fault in bus cable. Address
button is wrong.
15| B| 3| N/A| X| | LON gateway: No communication
LON not connected to bus, fault in bus cable.
16| A| 3| N/A| X| X| Supply air freq. conv.: No communication
Frequency converter not connected to bus in FanIO connector B. Fault in the
bus cable. The bus cable in FC is connected in FanIO connector A instead of B.
17| A| 3| N/A| X| X| Extract air freq. conv.: No communication
| | | | | | Frequency converter not connected to bus in FanIO connector B.
Fault in the bus cable. The bus cable in FC is connected in FanIO connector A
instead of B.
---|---|---|---|---|---|---
18| A| 3| N/A| X| X| Rotary heat exchanger (RHX2M): No communication
RHX2M not connected to bus. Fault in bus cable
19| A| 3| N/A| X| X| Pressure transmitter (PTH): No communication
PTH not connected to bus. Fault in bus cable. Address button set wrong.
20| A| 10| N/A| X| X| Temperature sensor error: Supply air
Supply air temp. sensor disconnected/short-circuited, sensor not configured to
a temperature input.
21| A| 10| N/A| X| X| Temperature sensor error: Extract air
Extract air temp. sensor disconnected/short-circuited, sensor not configured
to a temperature input
22| A| 10| N/A| X| X| Temperature sensor error: Rooms
Room air temp. sensor disconnected/short-circuited. Sensor not configured for
a temperature input
23| A| 10| N/A| X| X| Temperature sensor error: Return
Exhaust air temp. sensor disconnected/short-circuited. Sensor not configured
for a temperature input
24| A| 10| N/A| X| X| Temperature sensor error: Outdoor air temperature
Outdoor air temp. sensor disconnected/short-circuited. Sensor not configured
for a temperature input
25| A| 10| N/A| X| X| Temperature sensor error: Water heating coil 1
Water heating coil temp. sensor disconnected/short-circuited. Sensor not
config- ured for a temperature input
26| A| 10| N/A| X| X| Temperature sensor error: Heat recovery
Recovery temp. sensor disconnected/short-circuited. Sensor not configured for
a temperature input.
27| A| 10| N/A| | X| Pump alarm: Water heating coil 1
Heating coil 1. Fault on pump.
28| A| 10| N/A| | X| Frost alarm: Water heating coil 1
Low supply temperature. Circulation pump defective. Low outdoor air
temperature
30| A| 3| N/A| | X| Supply air freq. conv.: Low supply voltage (Vlo)
Mains voltage to supply air frequency converter is low. Check supply voltage.
31| A| 3| N/A| | X| Supply air freq. conv.: High supply voltage (Vhi)
High mains supply. Stop ramp time too short
32| A| 3| N/A| | X| Supply air freq. conv.: High output current (Ihi)
Short-circuit in motor or cable. Motor blocked. Wrong motor type
33| A| 3| N/A| | X| Supply air freq. conv.: High temperature (Thi)
High ambient temperature. Overload of frequency converter
34| A| 3| N/A| | X| Supply air freq. conv.: Loss of supply phase
Mains voltage lacking a phase
35| B| 3| N/A| | | Supply air freq. conv.: High internal ripple voltage
Mains voltage unstable. Frequency converter overloaded
37| A| 3| N/A| | X| Supply air fan, alarm
---|---|---|---|---|---|---
Supply air fan, alarm
38| B| 600| N/A| | | Outdoor air filter
Pressure drop over supply air filter too high, filter blocked
39| A| 10| N/A| | X| FanIO 1: +24V DC overloaded
+24 VDC from FanIO 1 terminals 14,16,18 short-circuited. Current consumption
from FanIO 1 exceeds 0.6 A.
40| A| 3| N/A| | X| Extract air freq. conv.: Low supply voltage (Vlo)
Mains voltage to extract air frequency converter is low. Check supply voltage.
41| A| 3| N/A| | X| Extract air freq. conv.: High supply voltage (Vhi)
High mains supply. Stop ramp time too short
42| A| 3| N/A| | X| Extract air freq. conv.: High output current (Ihi)
Short-circuit in motor or cable. Motor blocked. Wrong motor type
43| A| 3| N/A| | X| Extract air freq. conv.: High temperature (Thi)
High ambient temperature. Overload of frequency converter
44| A| 3| N/A| | X| Extract air freq. conv.: Loss of supply phase
Mains voltage missing a phase
45| B| 3| N/A| | | Extract air freq. conv.: High internal ripple voltage
Mains voltage unstable. Frequency converter overloaded
47| A| 3| N/A| | X| Exhaust air/extract air fan, alarm
Exhaust air/extract air fan, alarm
48| B| 600| N/A| | | Extract air filter
Pressure drop across extract air filter too high. Filter blocked
49| A| 10| N/A| | X| FanIO 2: +24V DC overloaded
+24V DC from FanIO 1 terminals 14,16,18 short-circuited. Current consumption
from FanIO 2 exceeds 0.6 A.
50| B| 3| N/A| | | Rotary heat exchanger (RHX2M): No rotation
No pulses from rotation monitor. Belt to rotor snapped. Rotor too slow due to
mis- alignment.
51| B| 3| N/A| | | Rotary heat exchanger (RHX2M): Low supply voltage (Vlo)
Low mains supply: Check main supply
52| B| 3| N/A| | | Rotary heat exchanger (RHX2M): High supply voltage (Vhi)
High mains voltage: control mains power supply
53| B| 3| N/A| | | Rotary heat exchanger (RHX2M): High output current (Ihi)
Short-circuit in motor or cable. Motor blocked. Wrong motor type
54| B| 3| N/A| | | Rotary heat exchanger (RHX2M): High internal temperature
High ambient temperature. Overload of the RHX2M control system.
55| B| 3| N/A| | | Rotary heat exchanger (RHX2M): Torque overload
Rotor too slow due to misalignment. Step motor unable to drive the rotor at
correct rpm.
58| A| 300| N/A| | X| Frost alarm heat exchanger
| | | | | | Exhaust air temperature under frost limit, even though bypass
damper is fully open (0 V)
---|---|---|---|---|---|---
59| A| 600| N/A| | X| No heat recovery. Low temperature
Recovery temperature in liquid-connected heat recovery coil too low for more
than 10 minutes.
60| A| 600| SP-5°C| | X| Low supply air temperature
Supply air temperature has been too low for more than 10 minutes. Insufficient
heating available. Low outdoor air temperature.
61| B| 600| SP+5°C| | | High supply air temperature
Supply air temperature has been too high for more than 10 minutes.
Insufficient cooling available. High outdoor air temperature.
62| B| 1200| SP-5°C| | | Low extract air temperature
Extract air temperature has been too low for more than 20 minutes. Max. supply
air temperature too low. Airflow too low.
63| B| 1200| SP+5°C| | | High extract air temperature
Extract air temperature has been too high for more than 20 minutes. Min.
supply air temperature too high. Airflow too low.
65| B| 300| N/A| X| | Heating 1 disconnected due to low airflow
Airflow through electric heating coil too low for more than 5 minutes.
66| B| 3| N/A| | | Electric heating coil 1: Overheating alarm
Overheating thermostat in electric heating coil has cut out.
67| B| 3| N/A| | | Reduced airflow
Airflow reduced due to insufficient available heating for more than 10
minutes.
68| B| 3| N/A| | | Contactor for electric heating coil 1 is stuck
Electric heating coil 1 cannot cut out because of fault in contactor.
70| B| 1200| N/A| X| | VOC/CO2 level is too high
VOC/CO2 level too high for more than 20 minutes. Max. airflow too low.
71| A| 600| SP-10%| | X| Low supply airflow
Supply airflow too low for more than 10 minutes
72| A| 600| SP+10%| | X| High supply airflow
Supply airflow too high for more than 10 minutes
73| A| 600| SP-10%| | X| Low extract airflow
Extract airflow too low for more than 10 minutes
74| A| 600| SP+10%| | X| High extract airflow
Extract airflow too high for more than 10 minutes
75| B| 600| SP-10%| | | Low supply air pressure
Supply air pressure too low for more than 10 minutes
76| A| 600| SP+10%| | X| High supply air pressure
Supply air pressure too high for more than 10 minutes
77| B| 600| SP-10%| | | Low extract air pressure
Extract air pressure too low for more than 10 minutes
78| A| 600| SP+10%| | X| High extract air pressure
| | | | | | Extract air pressure too high for more than 10 minutes
---|---|---|---|---|---|---
80| B| 3| N/A| | | Cooling error
cooling error: Alarm from cooling appliance.
81| B| 3| N/A| | | Low cooling pressure circuit 1
Cooling circuit 1: Pressure in evaporator too low. Lack of coolant/leakage
82| B| 3| N/A| | | High cooling pressure circuit 1
Cooling circuit 1: Pressure in condenser too high. Too much coolant. High
temper- ature in condenser.
83| B| 3| N/A| | | Cooling error 1: Compressor 1 overheated circuit 1
Cooling error 1: Compressor 1 overheated circuit 1
84| B| 3| N/A| | | Cooling error 2: Compressor 2 overheated circuit 1
Cooling error 2: Compressor 2 overheated circuit 1
85| B| 3| N/A| | | Low cooling pressure circuit 2
Cooling circuit 2: Pressure in evaporator too low. Lack of coolant/leakage
86| B| 3| N/A| | | High cooling pressure circuit 2
Cooling circuit 2: Pressure in condenser too high. Too much coolant. High
temper- ature in condenser.
87| B| 3| N/A| | | Cooling error 3: Compressor 1 overheated circuit 2
Cooling error 3: Compressor 1 overheated circuit 2
88| B| 3| N/A| | | Cooling error 4: Compressor 2 overheated circuit 2
Cooling error 4: Compressor 2 overheated circuit 2
90| B| 3| N/A| | | Pressure transmitter error: DX low pressure 1
Pressure transmitter error: DX low pressure 1. Transmitter is disconnected or
short-circuited
91| B| 3| N/A| | | Pressure transmitter error: DX high pressure 1
Pressure transmitter error: DX high pressure 1. Transmitter is disconnected or
short-circuited
92| B| 3| N/A| | | Pressure transmitter error: DX low pressure 2
Pressure transmitter error: DX low pressure 2. Transmitter is disconnected or
short-circuited
93| B| 3| N/A| | | Pressure transmitter error: DX high pressure 2
Pressure transmitter error: DX high pressure 2. Transmitter is disconnected or
short-circuited
94| B| 3| N/A| X| | VOC/CO2 sensor not configured
VOC/CO2 sensor not configured
95| B| 3| N/A| X| | FanOpt. supply air not configured
FanOpt. supply air not configured
96| B| 3| N/A| X| | FanOpt. extract air not configured
FanOpt. extract air not configured
Alarm nos. 100-199
Alarm no.| Alarm type| Alarm delay. sec.| Alarm limit| Auto reset| Unit stop| ****
Alarm text – WEB Alarm text – POP UP
---|---|---|---|---|---|---
100| A| 3| N/A| X| X| Pressure transmitter 0 (PTH6202): No communication
Pressure transmitter 0 (PTH6202): No communication
101| A| 3| N/A| X| X| Pressure transmitter 1 (PTH6202): No communication
Pressure transmitter 1 (PTH6202): No communication
103| A| 3| N/A| X| X| Pressure transmitter 3 (PTH6202): No communication
Pressure transmitter 3 (PTH6202): No communication
104| A| 3| N/A| X| X| Pressure transmitter 4 (PTH6202): No communication
Pressure transmitter 4 (PTH6202): No communication
105| A| 3| N/A| X| X| Pressure transmitter 5 (PTH6202): No communication
Pressure transmitter 5 (PTH6202): No communication
106| A| 3| N/A| X| X| Pressure transmitter 6 (PTH6202): No communication
Pressure transmitter 6 (PTH6202): No communication
107| A| 3| N/A| X| X| Pressure transmitter 7 (PTH6202): No communication
Pressure transmitter 7 (PTH6202): No communication
108| A| 3| N/A| X| | Expansion module45 1 (EXT45 1): No communication
EXT45 1 not connected to bus, fault in bus cable. Address button set wrong
109| A| 3| N/A| X| | Expansion module45 2 (EXT45 2): No communication
EXT45 2 not connected to bus, fault in bus cable, address button set wrong
111| B| 3| N/A| X| | Pressure transmitter, supply air (PTH6202): No
communication
Pressure transmitter not connected to bus: Fault in bus cable. Address button
wrong.
112| B| 3| N/A| X| | Pressure transmitter, extract air (PTH6202): No
communication
Pressure transmitter not connected to bus: Fault in bus cable. Address button
wrong.
113| B| 10| N/A| X| | VOC/CO2 sensor error: Sensor disconnected/short-
circuited
VOC/CO2 sensor interrupted/short-circuited. The sensor is not configured for
an analogue input
115| A| 3| N/A| | X| Supply air, EC controller: Alarm stop
Motor stopped due to alarm from EC controller
116| A| 3| N/A| | X| Supply air, EC controller: Rotor blocked
EC motor is blocked
117| B| 3| N/A| | | Supply air, EC controller: Power restriction active
Ramp time too short. Motor overloaded. Wrong motor type
118| B| 3| N/A| | | Supply air, EC controller: Low supply voltage (Vlo)
Low mains supply
119| B| 3| N/A| | | Supply air, EC controller: High supply voltage (Vhi)
High mains supply
120| B| 3| N/A| | | Supply air, EC controller: High temperature (Thi)
High ambient temperature. Overload of EC controller
121| B| 3| N/A| | | Supply air, EC controller: High internal ripple voltage
| | | | | | Mains voltage unstable
---|---|---|---|---|---|---
122| A| 3| N/A| | X| Extract air, EC controller: Alarm stop
Motor stopped due to alarm from EC controller
123| A| 3| N/A| | X| Extract air, EC controller: Rotor blocked
EC motor is blocked
124| B| 3| N/A| | | Extract air, EC controller: Power restriction active
Ramp time too short. Motor overloaded. Wrong motor type
125| B| 3| N/A| | | Extract air, EC controller: Low supply voltage (Vlo)
Low mains supply
126| B| 3| N/A| | | Extract air, EC controller: High supply voltage (Vhi)
High mains supply
127| B| 3| N/A| | | Extract air, EC controller: High temperature (Thi)
High ambient temperature. Overload of EC controller
128| B| 3| N/A| | | Extract air, EC controller: High internal ripple voltage
Mains voltage unstable
129| B| 3| N/A| | | Supply air, EC controller: Loss of supply phase
Mains voltage lacking a phase
130| B| 3| N/A| | | Extract air, EC controller: Loss of supply phase
Mains voltage lacking a phase
131| A| 3| N/A| X| X| FanIO 1: No communication
FanIO not connected to bus in FanIO socket A, error in bus cable, FanIO DIP
switches are wrongly set
132| A| 3| N/A| X| X| FanIO 2: No communication
FanIO not connected to bus in FanIO socket A, error in bus cable, FanIO DIP
switches are wrongly set
133| A| 3| N/A| X| X| Damper motor (supply air), ID 130: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
130dec /82hex
134| A| 3| N/A| X| X| Damper motor (exhaust air), ID 131: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
131dec /83hex
135| A| 3| N/A| X| X| Damper motor (recirculation), ID 132: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
132dec /84hex
136| A| 3| N/A| X| X| Damper motor (heat exchanger), ID 133: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
133dec /85hex
137| A| 3| N/A| X| X| Damper motor (drying damper), ID 134: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
134 decimal/86 hex
138| A| 3| N/A| X| X| Damper motor (6), ID 135: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
135 decimal/87 hex
139| A| 3| N/A| X| X| Damper motor (Smoke-evacuation damper), ID 136: No
communication
---|---|---|---|---|---|---
Motor not connected to bus. Error in bus cable. Motor address must be set to
136 decimal/88 hex
140| A| 3| N/A| X| X| Damper motor (8), ID 137: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
137 decimal/89 hex
141| A| 3| N/A| X| X| Valve motor (heating 1), ID 138: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
138dec /8Ahex
142| A| 3| N/A| X| X| Valve motor (cooling), ID 139: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
139dec /8Bhex
143| A| 3| N/A| X| X| Valve motor (Heating 2), ID 140: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
140dec /8Chex
144| A| 3| N/A| X| X| Valve motor (heat exchanger), ID 141: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
141dec /8Dhex
145| A| 3| N/A| X| X| Valve motor (pre-heating), ID 142: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
142dec /8Ehex
146| A| 3| N/A| X| X| Valve motor (6) ID 143: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
143dec /8Fhex
147| A| 3| N/A| X| X| Valve motor (7) ID 144: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
144 decimal/90 hex
148| A| 3| N/A| X| X| Valve motor (8) ID 145: No communication
Motor not connected to bus. Error in bus cable. Motor address must be set to
145 decimal/91 hex
149| B| 10| N/A| X| | Damper motor (outside air): Unable to reach setpoint
Check whether damper is blocked
150| B| 10| N/A| X| | Damper motor (exhaust air): Unable to reach setpoint
Check whether damper is blocked
151| B| 10| N/A| X| | Damper motor (recirculation): Unable to reach setpoint
Check whether damper is blocked
152| B| 10| N/A| X| | Damper motor (heat exchanger): Unable to reach setpoint
Check whether damper is blocked
153| B| 10| N/A| X| | Damper motor (drying damper): Unable to reach setpoint
Check whether damper is blocked
154| B| 10| N/A| X| | Damper motor (6): Unable to reach setpoint
Check whether damper is blocked
155| B| 10| N/A| X| | Damper motor (Smoke-evacuation damper): Unable to reach
setpoint
| | | | | | Check whether damper is blocked
---|---|---|---|---|---|---
156| B| 10| N/A| X| | Damper motor (8): Unable to reach setpoint
Check whether damper is blocked
157| B| 10| N/A| X| | Valve motor (heating 1): Unable to reach setpoint
Check whether valve is blocked
158| B| 10| N/A| X| | Valve motor (cooling): Unable to reach setpoint
Check whether valve is blocked
159| B| 10| N/A| X| | Valve motor (Heating 2): Unable to reach setpoint
Check whether valve is blocked
160| B| 10| N/A| X| | Valve motor (heat exchanger): Unable to reach setpoint
Check whether valve is blocked
161| B| 10| N/A| X| | Valve motor (pre-heating): Unable to reach setpoint
Check whether valve is blocked
162| B| 10| N/A| X| | Valve motor (6): Unable to reach setpoint
Check whether valve is blocked
166| B| 360| N/A| | | Fire damper not closed
Fire damper not closed. Check damper
167| B| 360| N/A| | | Fire damper not open
Fire damper not open. Check damper
168| B| 300| N/A| X| | Heating 2 cut out due to low airflow
Airflow through the electric heating coil too low for more than 5 minutes
169| B| 30| N/A| | | Electric heating coil 2: overheating alarm
Overheating thermostat in electric heating coil 2 disconnected
170| B| 30| N/A| | | Contactor for electric heating coil 2 is stuck
Digital input “Heating coil 2 error” closed when heating relay 21 is open.
Contact surface burned in position
171| A| 10| N/A| X| X| Temperature sensor error: Water heating coil 2
Water heating coil temp. sensor disconnected/short-circuited. Sensor not
config- ured for a temperature input
172| A| 10| N/A| | X| Pump alarm, heating 2
Digital input water heating coil 2 error
173| A| 10| N/A| | X| Frost alarm water heating coil 2
Low supply temperature. Circulation pump defective. Low outdoor air
temperature
174| A| 10| N/A| X| X| Temperature sensor error: combi-coil
Combi-coil return water sensor disconnected/short-circuited. Sensor not
config- ured for a temperature input
175| A| 10| N/A| | X| Pump alarm combi-coil
Digital input “Combi-coil alarm” open. Alarm from circulation pump
176| A| 10| N/A| | X| Combi-coil heating frost alarm
Combi-coil heating frost alarm
177| A| 10| N/A| | X| Combi-coil cooling frost alarm
Combi-coil cooling frost alarm
178| B| 10| N/A| | | Alarm from heat exchanger or circulation pump
---|---|---|---|---|---|---
Digital input “Heat exchanger alarm” open or alarm from circulation pump
179| B| 10| N/A| X| | Temperature sensor error: heating pump
Air temp. sensor on heat pump condenser has been interrupted/short-circuited,
sensor not configured for a temp. input
180| A| 10| N/A| | X| Frost alarm, Air
Frost thermostat read out: Low feed temperature, Circulation pump defective,
Low outdoor air temp.
181| B| 10| N/A| X| | Pressure transmitter heat pump is not configured
Pressure transmitter for dynamic de-icing of heat pump is not configured
182| B| 1200| N/A| X| | Dynamic de-icing heat pump not measured
183| B| 10| N/A| X| | Pressure transmitter, crossflow heat exchanger is not
configured
184| B| 1200| N/A| X| | Dynamic de-icing crossflow heat exchanger is not
measured
187| B| 10| N/A| | | HWC cool/freeze pump alarm
188| B| 10| N/A| X| | HWB cool-freeze Temperature sensor before condenser
HWB cool/freeze temp. sensor disconnected/short-circuited. The sensor is not
configured for a temperature input.
189| B| 10| N/A| X| | HWB cool-freeze Temperature sensor after condenser
HWB cool/freeze temp. sensor disconnected/short-circuited. The sensor is not
configured for a temperature input.
190| B| 10| N/A| X| | Room temperature sensor 1, Alarm
Supply air temp. sensor disconnected/short-circuited, sensor not configured to
a temperature input.
191| B| 10| N/A| X| | Room temperature sensor 2, Alarm
Room temperature sensor disconnected/short-circuited, sensor not configured
for a temperature input.
192| A| 10| N/A| | X| Return water temperature sensor, Alarm
193| B| 10| N/A| X| | Return water temperature sensor is not configured.
194| B| 10| N/A| X| | Humidity sensor (HTH6202): No communication
Humidity sensor (HTH6202): No communication
195| B| 10| N/A| X| | Humidity sensor (HTH6203): No communication
Humidity sensor (HTH6203): No communication
196| B| 10| N/A| X| | Humidifier: Configuration error
Outputs to humidifier are not configured
197| B| 10| N/A| X| | Humidifier: Alarm
Alarm input from humidifier is activated
198| B| 1200| N/A| X| | High air humidity in the supply air
High air humidity in the supply air
199| B| 1200| N/A| X| | Low air humidity in the supply air
Low air humidity in the supply air
Alarm nos. 200-299
Alarm no.| Alarm type| Alarm delay. sec.| Alarm limit| Auto reset| Unit stop| ****
Alarm text – WEB Alarm text – POP UP
---|---|---|---|---|---|---
200| B| 1200| N/A| X| | High air humidity in the extract air
High air humidity in the extract air
201| B| 1200| N/A| X| | Low air humidity in the extract air
Low air humidity in the extract air
202| B| 10| N/A| X| | Sensor error in water cooling
Sensor error in water cooling
203| A| 3| N/A| X| X| Expansion module EXT 3: No communication
EXT 3 expansion module not connected to bus, fault in bus cable, address
button is wrong
204| A| 3| N/A| X| X| Expansion module EXT 4: No communication
EXT 4 expansion module not connected to bus, fault in bus cable, address
button is wrong
205| A| 3| N/A| X| X| Expansion module EXT 5: No communication
EXT 5 expansion module not connected to bus, fault in bus cable, address
button is wrong
206| A| 3| N/A| X| X| Expansion module EXT 6: No communication
EXT 6 expansion module not connected to bus, fault in bus cable, address
button is wrong
207| A| 3| N/A| X| X| Expansion module EXT 7: No communication
EXT 7 expansion module not connected to bus, fault in bus cable, address
button is wrong
208| B| 3| N/A| X| | Room control: No communication
Room control: No communication
209| B| 3| N/A| X| | VTH-6202, VOC sensor, no communication
VTH-6202, VOC sensor not connected to bus. Fault in bus cable
210| B| 600| N/A| X| | VTH-6202, VOC sensor error
VTH-6202, VOC sensor error, measured value outside measurement range
211| B| 10| N/A| X| | HTH6204, humidity sensor: No communication
HTH6204, humidity sensor not connected to bus. Fault in bus cable
212| B| 10| N/A| X| | Dew point sensor error
Dew point sensor error
213| B| 300| N/A| X| | Low recovery rate, Alarm 213
Alarm 213 triggered
214| A| 3| N/A| X| X| Expansion module EXT 8: No communication
EXT 8 expansion module not connected to bus, fault in bus cable, address
button is wrong
215| B| 30| N/A| X| | Pre-heating coil: Contactor error
Contactor for pre-heating coil is stuck
216| B| 30| N/A| X| | Pre-heating coil: Overheating alarm
Pre-heating coil: Overheating alarm
217| A| 10| N/A| X| X| Pre-heating coil, hot water sensor error
| | | | | | Pre-heating coil, hot water sensor error
---|---|---|---|---|---|---
218| A| 10| N/A| | X| Pre-heating coil, pump alarm
Pre-heating coil, pump alarm
219| A| 10| N/A| | X| Pre-heating coil, frost alarm
Pre-heating coil, frost alarm
220| A| 10| N/A| X| X| Pre-heating coil, airflow sensor error
Pre-heating coil, airflow sensor error
221| B| 300| N/A| X| | Pre-heating coil, reduced output
Pre-heating coil, reduced output
222| B| 300| N/A| X| | Heat exchanger efficiency is too low
Heat exchanger efficiency is below minimum setpoint
223| A| 3| N/A| X| X| Supply air frequency converter (ATV): No communication
ATV not connected to bus in FanIO socket, Error in bus cable
224| A| 3| N/A| X| X| Extract air freq. conv. (ATV): No communication
ATV not connected to bus in FanIO connector B, fault in bus cable
225| B| 10| N/A| | | Error ATV supply air frequency converter
An error has been registered in the ATV supply air frequency converter:
further in- formation via the ATV display
226| B| 10| N/A| | | Error ATV extract air frequency converter
An error has been registered in the ATV extract air frequency converter:
further in- formation via the ATV display
227| A| 10| N/A| | X| Frost alarm liquid connected heat exchanger
228| B| 30| N/A| | | Switch for frost protection battery stuck
229| B| 30| N/A| | | Electric frost protection battery: Overheating alarm
Overheating thermostat in electric frost protection battery disconnected
230| B| 300| N/A| X| | Reduced frost protection on frost protection battery
Power on electrical frost protection battery reduced due to low flow
231| B| 1200| | X| | De-icing pressure, rotary heat exchanger is not measured
De-icing pressure, rotary heat exchanger is not measured, dynamic pressure
con- trol cannot be used.
232| B| 3| N/A| X| | PTH sensor, rotary heat exchanger, configuration error
PTH sensor (extract air/exhaust air) rotary heat exchanger not configured
233| B| 1800| N/A| X| | Rotary heat exchanger is iced up
Rotary heat exchanger is iced up. Outdoor air temperature is lower than 0°C
and the pressure drop across the rotor has been higher than the setpoint for
more than 30 minutes
234| B| 1800| N/A| | | Rotary heat exchanger is soiled
Rotary heat exchanger is soiled. Outdoor air temperature is higher than 0°C
and the pressure drop across the rotor has been higher than the setpoint for
more than 30 minutes
235| A| 3| N/A| | X| Supply air, EC-2 controller: Alarm stop
Motor stopped due to alarm from EC-2 controller
236| A| 3| N/A| | X| Supply air, EC-2 controller: Rotor blocked
| | | | | | EC-2 motor is blocked
---|---|---|---|---|---|---
237| B| 3| N/A| | | Supply air, EC-2 controller: Power restriction active
Ramp time too short. Motor (EC-2) overloaded. Wrong motor type
238| B| 3| N/A| | | Supply air, EC-2 controller: Low supply voltage (Vlo)
Low mains supply (EC-2)
239| B| 3| N/A| | | Supply air, EC-2 controller: High supply voltage (Vhi)
High mains supply (EC-2)
240| B| 3| N/A| | | Supply air, EC-2 controller: High temperature (Thi)
High ambient temperature. Overload of EC-2 controller
241| B| 3| N/A| | | Supply air, EC-2 controller: High internal ripple voltage
Mains voltage unstable (EC-2)
242| A| 3| N/A| | X| Extract air, EC-2 controller: Alarm stop
Motor stopped due to alarm from EC-2 controller
243| A| 3| N/A| | X| Extract air, EC-2 controller: Rotor blocked
EC-2 motor is blocked
244| B| 3| N/A| | | Extract air, EC-2 controller: Power restriction active
Ramp time too short. Motor (EC-2) overloaded. Wrong motor type
245| B| 3| N/A| | | Extract air, EC-2 controller: Low supply voltage (Vlo)
Low mains supply (EC-2)
246| B| 3| N/A| | | Extract air, EC-2 controller: High supply voltage (Vhi)
High mains supply (EC-2)
247| B| 3| N/A| | | Extract air, EC-2 controller: High temperature (Thi)
High ambient temperature. Overload of EC-2 controller
248| B| 3| N/A| | | Extract air, EC-2 controller: High internal ripple voltage
Mains voltage unstable (EC-2)
249| B| 3| N/A| | | Supply air, EC-2 controller: Loss of supply phase
Mains voltage lacking a phase
250| B| 3| N/A| | | Extract air, EC-2 controller: Loss of supply phase
Mains voltage lacking a phase
251| A| 3| N/A| X| X| Supply air, EC-2 controller: No communication
EC-2 not connected to bus in FanIO connector C. Fault in bus cable. Bus cable
in EC-2 mounted in connector B instead of C
252| A| 3| N/A| X| X| Extract air, EC-2 controller: No communication
EC-2 not connected to bus in FanIO connector C. Fault in bus cable. Bus cable
in EC-2 mounted in connector B instead of C
253| B| 3| N/A| | | Temperature sensor (TTH): No communication
Temperature sensor not connected to bus. Fault in bus cable
254| B| 3| N/A| | | Temperature sensor (TTH): No communication
Temperature sensor not connected to bus. Fault in bus cable
255| B| 3| N/A| | | Supply airflow correction, temperature sensor error
Supply airflow correction, temperature sensor error
256| B| 10| N/A| X| | Temperature sensor error: Supplementary sensor 1
| | | | | | Temperature sensor error: Supplementary sensor 1
---|---|---|---|---|---|---
257| B| 10| N/A| X| | Temperature sensor error: Supplementary sensor 2
Temperature sensor error: Supplementary sensor 2
258| B| 10| N/A| X| | Temperature sensor error: Supplementary sensor 3
Temperature sensor error: Supplementary sensor 3
259| B| 10| N/A| X| | Temperature sensor error: Supplementary sensor 4
Temperature sensor error: Supplementary sensor 4
260| B| 3| N/A| | X| Supply air motor control 1 has wrong type no. or defect
Replace motor control 1
261| B| 3| N/A| | X| Supply air motor control 2 has wrong type no. or defect
Replace motor control 2
262| B| 3| N/A| | X| Return/exhaust air motor control 1 has wrong type no. or
defect
Replace motor control 1
263| B| 3| N/A| | X| Return/exhaust air motor control 2 has wrong type no. or
is defective
Replace motor control 2
264| A| 10| N/A| X| X| Room sensor (TTH-6040-W): No communication
Room sensor (TTH-6040-W): No communication
265| B| 10| N/A| X| | Low oil level in DX/HP cooling compressor
Low oil level in DX/HP cooling compressor
266| A| 10| N/A| X| | Manual fireman’s stop
Manual fireman’s stop
267| B| 10| N/A| X| | Bypass smoke evacuation is active with external fan
Bypass smoke evacuation is active with external fan
268| B| 10| N/A| X| | Room temperature from BMS is outside the range
Room temperature from BMS system is outside the min/max range – the unit is
us- ing the extract air sensor
269| B| 10| N/A| X| | Outdoor air temperature from BMS is outside the range
Outdoor air temperature from BMS system is outside the min/max range – the
unit is using another installed room sensor
270| B| 10| N/A| X| | Smoke evacuation fan error: Motor will not start
Smoke evacuation fan error: Motor will not start
271| B| 10| N/A| X| | Change outdoor air filter and reset timer for filter
change
The pre-defined time for filter change has expired – change filter and reset
filter change timer
272| B| 10| N/A| X| | Change extract air filter and reset timer for filter
change
The pre-defined time for filter change has expired – change filter and reset
filter change timer
273| B| 10| N/A| X| | Supply air frequency converter: Restricted output is
active
Supply air controller: Restricted output is active
274| B| 10| N/A| X| | Extract air frequency transformer: Restricted output is
active
Extract air controller: Restricted output is active
275| A| 10| N/A| X| | Supply air, FC-DC controller: Rotor blocked
| | | | | | FC/DV motor is blocked
---|---|---|---|---|---|---
276| A| 10| N/A| X| | Extract air FC-DV controller: Rotor blocked
FC/DV motor is blocked
277| A| 3| N/A| | X| Supply air, EC controller (OJ-EC): High output current
(Ihi)
Short-circuit in motor or cable, Motor blocked, Wrong motor type
278| A| 3| N/A| | X| Extract air, EC controller (OJ-EC): High output current
(Ihi)
Short-circuit in motor or cable, Motor blocked, Wrong motor type
279| A| 3| N/A| | X| Supply air, EC-2 controller (OJ-EC): High output current
(Ihi)
Short-circuit in motor or cable, Motor blocked, Wrong motor type
280| A| 3| N/A| | X| Extract air, EC-2 controller (OJ-EC): High output current
(Ihi)
Short-circuit in motor or cable, Motor blocked, Wrong motor type
281| B| 3| N/A| | X| Supply air fan stopped (Special SW/customer code)
Supply air fan stopped (Special SW/customer code)
282| A| 3| N/A| X| X| HMI-20T communication failure
HMI-20T communication failure
289| B| 3| N/A| | | Position of smoke evacuation damper not achieved
Position of smoke evacuation damper not achieved
290| B| 3| N/A| | | Position of bypass smoke evacuation damper not achieved
Position of bypass smoke evacuation damper not achieved
291| A| 3| N/A| X| X| Alarm PTH-6202-2 #1
Alarm PTH-6202-2 #1
292| A| 3| N/A| X| X| Alarm PTH-6202-2 #2
Alarm PTH-6202-2 #2
293| A| 3| N/A| X| X| Alarm PTH-6202-2 #3
Alarm PTH-6202-2 #3
294| A| 3| N/A| X| X| Alarm PTH-6202-2 #4
Alarm PTH-6202-2 #4
295| A| 3| N/A| X| X| Alarm PTH-6202-2 #5
Alarm PTH-6202-2 #5
296| B| 600| N/A| | | Supply air filter 2 – alarm
Supply air filter 2 – alarm
297| B| 600| N/A| | | Extract air filter 2 – alarm
Extract air filter 2 – alarm
298| B| 10| N/A| X| | Supply air filter 2 – timer expiry alarm
Supply air filter 2 – timer expiry alarm
299| B| 10| N/A| X| | Extract air filter 2 – timer expiry alarm
Extract air filter 2 – timer expiry alarm
Alarm nos. 300-399
Alarm no.| Alarm type| Alarm delay. sec.| Alarm limit| Auto reset| Unit stop| ****
Alarm text – WEB Alarm text – POP UP
---|---|---|---|---|---|---
300| B| 30| N/A| | | Alarm from gas heating coil 1, overheating
Alarm from gas heating coil 1, overheating
301| B| 30| N/A| | | Alarm from gas heating coil 2, overheating
Alarm from gas heating coil 2, overheating
302| B| 30| N/A| | | Alarm from gas heating coil, preheating, overheating
Alarm from gas heating coil, preheating, overheating
303| B| 3| N/A| X| | Zone Module no. 1 communication error
Zone Module no. 1 communication error
304| B| 3| N/A| X| | Zone Module no. 2 communication error
Zone Module no. 2 communication error
305| B| 3| N/A| X| | Zone Module no. 3 communication error
Zone Module no. 3 communication error
306| B| 3| N/A| X| | Zone Module no. 4 communication error
Zone Module no. 4 communication error
307| B| 3| N/A| X| | Zone 1 – at least one active alarm
Zone 1 – at least one active alarm
308| B| 3| N/A| X| | Zone 2 – at least one active alarm
Zone 2 – at least one active alarm
309| B| 3| N/A| X| | Zone 3 – at least one active alarm
Zone 3 – at least one active alarm
310| B| 3| N/A| X| | Zone 4 – at least one active alarm
Zone 4 – at least one active alarm
311| B| 10| N/A| X| | Temperature sensor error: Heat recovery sensor
Temperature sensor error: Heat recovery sensor
312| B| 3| N/A| X| X| CVM Mini Energy Analyzer: Communication failure
CVM Mini Energy Analyzer: Communication failure
313| B| 3| N/A| X| X| CVM Mini Cool Energy Analyzer: Communication failure
CVM Mini Cool Energy Analyzer: Communication failure
314| A| 3| N/A| X| X| Expansion module45 3: No communication
OJ – Ext45 not connected to bus, fault in bus cable, address button is wrong
315| B| 10| N/A| X| | External outdoor sensor (TTH-6040-O): No communication
External outdoor sensor (TTH-6040-O): No communication
316| A| 10| N/A| X| X| Damper actuator Back-up fan (exhaust air): No
communication
Damper actuator not connected to bus. Fault in bus cable. Motor address must
be set
317| B| 10| N/A| X| | Damper actuator Back-up fan (exhaust air), Unable to
reach setpoint.
Check whether damper is blocked
318| A| 10| N/A| X| X| Damper actuator Back-up fan (supply air): No
communication
Damper actuator not connected to bus. Fault in bus cable. Motor address must
be set
319| B| 10| N/A| X| | Damper actuator Back-up fan (supply air): Unable to
achieve setpoint
---|---|---|---|---|---|---
Check whether damper is blocked
320| B| 10| N/A| X| | Common alarm from fan wall (Fan Wall) – Supply air
Common alarm from fan wall (Fan Wall) – Supply air
321| B| 10| N/A| X| | Common alarm from fan wall (Fan Wall) – Extract air
Common alarm from fan wall (Fan Wall) – Extract air
322| B| 300| N/A| X| | Alarm Auto Zero Leakage.
Alarm Auto Zero Leakage.
323| A| 10| N/A| X| | Pressure transmitter #8 (PTH6202): No communication
Pressure transmitter #8 (PTH6202): No communication
324| B| 10| N/A| X| | Increased use of extract air damper (Unstable regulation
ALC)
Increased use of extract air damper (Unstable regulation ALC)
325| B| 10| N/A| X| | Excessive outdoor air damper utilization
Excessive outdoor air damper utilization
326| A| 30| N/A| | X| Supply backup air fan, alarm
Supply backup air fan, alarm
327| A| 30| N/A| | X| Exhaust backup air fan, alarm
Exhaust backup air fan, alarm
328| A| 30| N/A| | X| Temperature sensor fault: Extract air Heat pump
Extract air Heat pump temp. sensor disconnected/short-circuited
333| A| 10| N/A| X| | The AHU operation is blocked
The AHU operation is blocked
334| A| 10| N/A| | X| Fire thermostat in electric heating coil alarm
Fire thermostat in electric heating coil alarm
335| A| 10| N/A| | X| Fire thermostat in electric pre-heating coil alarm
Fire thermostat in electric pre-heating coil alarm
Scan code and go to addresses at www.exhausto.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>