Description of MCCW (Modbus Coil Cold Water)

Functional description

The MCCW module is able to control a water coil used for cooling. Together with the EXact2 control system, the module is able to regulate the output from the water coil. If necessary, a circulation pump can be started up.

The MCCW module can be used together with the following VEX/CX types:

  • VEX100
  • VEX200
  • VEX320-370
  • CX340-350
  • VEX310T-VEX350T

Simplified diagram

The MCCW module controls a 3-way motor valve connected to a water supply. The water supply provides cold water.
Simplified diagram

Mixing loop
Constant flow in the primary circuit (Supply) and in secondary circuit (Coil Cold Water)

Explanation of simplified diagram

Term Description input/output
TE-SUPPLY Measures air temperature after cooling coil. Temperature input
Capacity 0-10V Analogue outputs 0–10 V for setting of 0–100% cooling.The MCCW

module, via a temperature regulator in EXact, sends an adjustable 0–10 V signal to the regulation valve (MVM). Thus the setpoint for the supply air temperature or room temperature is maintained.| Analogue output
CP| Circulation pump 1x230V
MVM| 3-way motor valve.MVM is the general term for a motor valve.
Pump ON/OFF| 230V supply to circulation pump| Analogue output
TE-SPT| Temperature sensor measures the feed temperature to the cooling coil.| Temperature input
Coil Cold Water (CCW)| Water coil (cooling)
| Line regulating valve
*** When there is no cooling requirement, valve adjustment must be based on the required primary circuit water flow.
| Shut off valve

*) not EXHAUSTO delivery

Assembly and connection

Positioning and fitting of the MCCW module

Fitting the MCCW module

Step Action
1 Fit the module using the screw holes in each corner of the module’s

mounting box
2| Position the module in the vicinity of:- regulation valve and pipes
3| Position the temperature sensor in the supply air duct as shown below (Example from VEX200).

Position of temperature sensor (TE-SUPPLY

The temperature sensor is positioned here
The temperature

Correct fitting of feed water temperature sensor

How to mount the temperature sensor correctly on the feed water pipe to the water coil:

Step Action
1 Use heat paste to ensure good contact between the pipe and the sensor. Use

strips to secure the sensor in position.
Mount the temperature
2| Ensure there is sufficient insulation around the sensor.
Mount the temperature

Cooling coil

Connection of cooling coil

The dimensioning of valves, pipes, etc. and cooling coil connection must always be carried out by authorised fitters in accordance with applicable regulations and legislation.

Mixing loop
See the simplified diagram.

Connecting an insulated CCW
With an insulated CCW, the connection must be made with stopcocks and unions, in order to allow easy release, extraction and cleaning of the coil.

Do not connect the water coil like this!.
Connection without circulation pump risks frost damage!
Cooling coil

Bleeding
Following connection of water supply to the unit:

  • Bleed the system thoroughly using the upper bleed screw on the water coil.

Insufficient bleeding
Insufficient bleeding can result in still water forming in the system, which may result in frost-induced leaks during the winter.

Fitting motor valve
The valve must not be fitted with the motor facing down.

Insulate supply pipe and water coil
The pipes and water coil must be insulated according to applicable regulations.

Frost protection
The cooling coil can be protected against frost by mixing 25% ethylene glycol. This provides frost protection down to -13°C.

MVM valve

Definition
MVM is used as a general term for a motor valve.

Shielding
Shield the valve motor from direct sunlight. Due to heat emission, the valve motor must not be encapsulated (maximum ambient temperature: 50°C).

Insulating the valve
To ensure normal operation at ambient temperatures below 0°C, it is very important that the valve section is insulated according to current standards/procedures.

MVM-OD, valve for outdoor fitting
IIf MVM-OD used, then shielding is part of the delivery – if the valve has a K vs value below 6.3.

Regulating properties
Optimal regulation is achieved when the differential pressure is between 5–20 kPa. If the differential pressure is higher than 20 kPa, the installation of a pressure difference regulator is recommended.

Cold water supply
The cold water supply must be constant.

Operation of circulating pump

The circulation pump is operated by the EXact control system, as described below:

  1. When no cooling is required, the MVM valve operates at 0%.
  2. The circulation pump runs for another 5 minutes and then stops.
  3. EXact starts the 24-hour timer.
  4. When the 24 hours have passed, the circulation pump runs for 5 minutes.
  5. The exercise cycle is repeated once a day until a cooling requirement occurs.

Electrical installation

Connection diagrams for MCCW

Diagram
The following diagram shows the connection of supply voltage (1 x 230 V) and the cooling coil control box (MCCW).
Connection diagrams

Key to diagram

Term Description Supplied by…
-A1 Voltage supply/modbus terminal in VEX EXHAUSTO
-A2 MCCW module EXHAUSTO
-F1 Distribution board fuse Costumer25
-T2 TE-SUPPLY Supply air temperature sensor EXHAUSTO
-T4 Temperature sensor, supply EXHAUSTO
-M1 MVM Motor valve EXHAUSTO
CP Cirkulation pump Costumer
-Q1 Distribution board group switch Costumer
-Q2 Isolation switch (disconnects all poles) Costumer
* Not supplied by EXHAUSTO Costumer
CN12Terminals 1 and 3 It is possible to invert the control signal to MCCW,

i.e. 0V→10V becomes 10V→0V. This is done by fitting a jumper across terminals 1 and 3 of CN12. The change will be registered the next time the unit is powered up.| EXHAUSTO
24VDC| Strip connector for continuation of 24VDC| EXHAUSTO**

Power Supply

Power Supply

VEX size Maximum load of terminal in main board
VEX140 1,4A
VEX150-170 2A
VEX240 1,4A
VEX250-260-270-280 2A
VEX340-350-360 2A
VEX320C-330C-330H must be separately powered
VEX310T-350T 2A
Connection of Modbus devices

Diagram
Connection must be carried out according to the following diagram. Refer to the Electrical Installation Guide for the relevant VEX. (supplied with the VEX unit) for further details of how to connect standard components to the connection box.
Connection of Modbus devices

= Skærmet kabel

*Not supplied by EXHAUSTO

MHCW/MHCE Module for controlling heating coil (water or electric)
MXCU/MCCW Module for control of coil with cold water supply.
MPT DUCT Pressure measurement in duct
XXXXX Can be different modules, e.g. MIO module or additional

MPTDUCT
HMI| Control panel

Cable (type, max. length and termination)

Cable
EXHAUSTO recommends the use of 4-core, twisted pair, shielded cable. To limit voltage drop across the cable, 0.25 diameter conductor is recommended. For correct connection of shielded cable to Modbus units, refer to the Electrical Installation Guide for the relevant VEX.

Max. cable length
The overall cable length of a complete installation may not exceed 200 m.

Modbus, termination or daisy chaining
The first and last devices on the bus must be terminated. The PCB contains a jumper JP1, which can be used for termination.

If Then See diagram no.
MCCW is the first or last device on the bus it must be terminated by use
of jumper JP1 (jumper nearest terminal 1 on CN7). 1
MCCW is not the first and last device on the bus it must be daisy-
chained to the next device = default setting 2

1
Connection of Modbus devices
2Connection of Modbus devices

Commissioning

Commissioning

HMI panel Refer to the VEX unit HMI panel for menu items displayed during commissioning of the MCCW module.
See the following section for further information about the individual menu items or in the Exact Control System Basic Instructions for the relevant VEX.

Detection of MCCW

Menu 3.4 Accessories

  • Select CCW under cooling unit in menu 3.4.
    Detection of MCCW

NB Cold recovery must be active when operating with MCCW (menu 3.1.6)

Operating readings, MCCW

Menu 2.4 Temp. reg. units
Operating readings

The menu will show, e.g.,

  • output of cooling unit (A) and whether cooling is active = value > 0%

Menu 2.8 Cooling coil (CCW)
Operating readings

The menu shows:

  • Supply temperature for CCW cooling coil
  • Pump – if the circulation pump in the heating cycle is in operation

Forced start, MCCW (CCW)

Conditions for use To use the forced start menu, the unit must be set to OFF in the user menu (Ventilation).

Menu 8.3.3 Cooling unit
Operating readings

If there are no current errors for the cooling coil(“Error on unit” shown as “No”), forced start may be activated:

  • Set output for CCW. The pump starts up at an output greater than 0%.

NB When Menu 8.3 “Forced start” is exited, forced start is reset and normal operation can be resumed. When a submenu is exited, the values in the submenu are reset.

Troubleshooting

HMI panel error messages

NB An error will be displayed on the HMI panel in the event of a fault or irregular operation. To resolve the problem, refer to EXact Basic instructions for the relevant VEX.