ACCUREX XRV Packaged Rooftop Ventilator Instruction Manual

August 21, 2024
ACCUREX

Document 475597
Model XRV
Packaged Rooftop Ventilator

Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage!

General Safety Information

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by the person responsible for their safety. Children should be supervised to ensure they do not play with this appliance. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.

  1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electrical Code (CEC) in Canada.
  2. All moving parts must be free to rotate without striking or rubbing any stationary objects.
  3. Unit must be securely and adequately grounded.
  4. Do not spin wheel faster than maximum cataloged fan RPM. Adjustments to fan speed significantly affect motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplate amps.
  5. Verify that the power source is compatible with the equipment.
  6. Never open access doors to the unit while it is running.

WARNING
The roof lining contains high voltage wiring. To prevent electrocution, do not puncture the interior or exterior panels of the roof.

DANGER

  • Always disconnect power before working on or near this equipment. Lock and tag the disconnect switch or breaker to prevent accidental power up.
  • If this unit is equipped with optional gas accessories, turn off gas supply whenever power is disconnected.

CAUTION
This unit is equipped with a compressed refrigerant system. If a leak in the system should occur, immediately evacuate the area. An EPA Certified
Technician must be engaged to make repairs or corrections. Refrigerant leaks may also cause bodily harm.
CAUTION
When servicing the unit, the internal components may be hot enough to cause pain or injury. Allow time for cooling before servicing.

Receiving

This product may have been subject to road salt during transit. If so, immediately wash off all visible white reside from all exterior surfaces. Upon receiving the product, check to ensure all line items are accounted for by referencing the delivery receipt or packing list. Inspect each crate or carton for shipping damage before accepting delivery. Alert the carrier if any damage is detected, do not refuse shipment. The customer shall make notation of damage (or shortage of items) on the delivery receipt and all copies of the bill of lading which should be countersigned by the delivering carrier. If damaged, immediately contact your manufacturer’s representative. Any physical damage to the unit after acceptance is not the responsibility of the manufacturer.
Handling
Units are to be rigged and moved by the lifting brackets provided. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of unit to resist corrosion.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space.
Confirmation of shipment(s) must be limited to only items on the bill of lading.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a  convenience to the user.
The ideal environment for the storage of units and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Units designed for outdoor applications may be stored outdoors. All  accessories must be stored indoors in a clean, dry atmosphere.
Indoor
Maintain temperatures evenly to prevent condensation.
Remove any accumulations of dirt, water, ice, or snow and wipe dry before moving to indoor storage. To avoid condensation, allow cold parts to reach room temperature. Leave coverings loose to permit air circulation and to allow for periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off the floor. Clearance should be provided to permit air circulation and space for inspection.
Outdoor
The unit should be placed on a level surface to prevent water from leaking into the unit. The unit should be elevated so that it is above water and snow levels.
Ensure sufficient support to prevent unit from settling into soft ground. Locate parts far enough apart to permit air circulation, sunlight, and space for periodic inspection. To minimize water accumulation, place all unit parts on blocking supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these cause condensation of moisture from the air passing through heating and cooling cycles.
Inspection and Maintenance
While in storage, inspect units once per month. Keep a record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate the fan wheel by hand ten to fifteen revolutions to distribute lubricant on motor. If paint deterioration begins, consideration should be given to touch-up or repainting. Units with special coatings may require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe thoroughly clean with Tectyl® 506 (Ashland Inc.) or the equivalent. For hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive, WD-40® or the equivalent.
Removing from Storage
As units are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion until the equipment goes into operation. Prior to installing the unit and system components, inspect the unit assembly to make sure it is in working order.

  1. Check all fasteners, set screws on the fan, wheel, bearings, drive, motor base, and accessories for tightness.
  2. Rotate the fan wheel(s) by hand and assure no parts are rubbing.

Product Overview

A horizontally configured High Percentage Outdoor Air unit designed for installation either indoors or outdoors. Each unit has multiple options for cooling and/or heating. The unit is designed to replace air that is exhausted from the building and also heat and cool, as needed. The air volume produced by the unit is constant, but can be optionally modulated to provide a variable air volume (VAV) and recirculation is also offered as an option.

Cooling
Units have the following cooling options available:

  • Packaged DX
  • Split DX (thermal expansion valve is field-provided) Not available on housing sizes 10, 75, and 110.
  • Chilled water coil
  • Air-source heat pump (ASHP)

Not available on housing sizes 10, 75, and 110.
Units with packaged DX are shipped fully charged with refrigerant and are ready for operation upon arrival.

Heating
There are three different optional heat sources that can be ordered for this unit:

  • Indirect gas-fired furnace with one or two sets of heat exchangers
  • Electric heat with infinitely variable SCR control
  • Hot water coil
  • Air-source heat pump (ASHP) Not available on housing sizes 10, 75, and 110.

Airflow Arrangement
The unit is capable of Constant Air Volume (CAV), Variable Air Volume (VAV), 100% Outdoor Air and have recirculating air options.
Safety Listing
Models are listed per ANSI/UL 1995 or 60335-2-40, Heating and Cooling Equipment and are ETL Certified.

Models and Capacities

Model Cooling Capacity
XRV-10 3 to 7 tons
XRV-25 5 to 15 tons
XRV-45 15 to 30 tons
XRV-75 25 to 50 tons
XRV-110 30 to 70 tons

Subassemblies

Blower
Either one, two, or three plenum-type fans. All units are equipped with a plenum fan for Supply Air and a second may be selected for Exhaust (Relief) Air.
Coils
Evaporator coil (optional)
Condenser coil (optional, packaged DX only)
Indoor coil (optional, air-source heat pump only)
Outdoor coil (optional, air-source heat pump only)
Water coil (optional)
Reheat coil (optional)
Compressors
Each unit having packaged DX will have either one, two, three, or four refrigerant compressors. Optionally, one of the compressors may be a digital or inverter scroll type compressor. Air-source heat pump units will have one inverter scroll compressor and may contain a second staged compressor.
Dampers
Motorized intake air damper, optional motorized recirculating damper. Optional return air damper.
Optional gravity-type exhaust damper.
Optional Barometric Relief Damper
Used during economizer mode of the unit when building pressure increases, relief damper will open due to over pressurization.
Electric Heater
An SCR controlled electric heater (not shown) is available on the units. It has its own control panel and may require a separate power supply. See unit- specific wiring diagram.
Supply Filters
Housing size 110 is available with a filter bank depth of either 2,4 or 6-inch. All other housings are available with a filter bank depth of either 2 or 4-inch.
Indirect Gas-Fired Furnace
Housing sizes 10, 25 and 45, use furnace model PVG.
Housing sizes 75 use furnace models PVG 600-800 or HMA 1000-1200. Housing sizes 110/145/180 use furnace model HMA 600-1200.
Packaged DX System
Any unit may be ordered with a packaged DX system.
Housing size 10 will use one compressor; housing size 25 will include one compressor; housing size 45 will include one or two compressors; housing size 75 will include two or three compressors; housing size 110 will include four compressors; a condenser coil(s)
and evaporator coil(s) and all required components.
Units that have packaged DX are charged with R410A refrigerant. Do not use tools or parts designed for other refrigerants on these units.

Air-Source Heat Pump
Units having an air-source heat pump will include either one or two compressors, an indoor and outdoor coil, and all required components. Air- source heat pump units are charged with R410A refrigerant. Do not use tools or parts designed for other refrigerants on these units. Not available on housing sizes 10, 75, 110.
Split DX
The unit may be ordered with a split DX system for connection to a building cooling system. Thermal expansion valve (TXV) is field-provided. Not available on housing sizes 10, 75, 110.
Vestibule
Some units may be ordered with a factory-assembled vestibule that is to be field-attached to the side of the unit. See lifting instructions.

Installation

Typical Unit Weights and Dimensions

Component Access

1| Optional Inverter Compressor VFD
2| Optional Compressor/Electrical
3| Optional Gas Furnace/Optional Electric Heater
4| Electrical
5| Supply Blower
6| Coil
7| Filters
8*| Exhaust Blower/Optional Electric Preheat
9| Powered Exhaust Blower Section

  • When a powered exhaust fan is selected, door 8 will be to the immediate right of door 7.

Typical Unit Weights and Dimensions

Model| Nominal tonnage (tons)| Height (H)| Width (W)| Length (L)| Intake (A)| Condensing Section (B)| Nominal weight (lbs)| Outdoor Intake| Supply Discharge| Return Intake| Exhaust Discharge
---|---|---|---|---|---|---|---|---|---|---|---
XRV-10| 3-7| 58.1| 44.0| 829/111.57&9| 22.3| NA| 1,225| End| Bottom or Side| Bottom or End2| NA
XRV-25| 5-15| 59.3| 52.5| 98.66/149.57| 22.1| 30.1| 3,150| Bottom, End5 or Side1| End3 or Side1
XRV-45| 15-30| 72.5| 68.2| 1096/163.27| 27.1| 30.1| 4,375
XRV-75| 25-50| 101.3| 98.0| 155.2| 39/48.48| NA| 7,625| Bottom, End5| End
XRV-75  EIS*| 25-50| 101.3| 98.0| 188| 39/48.48| NA| 7,925| Side1
XRV-110| 30-70| 99.5| 96.0| 185| 45.3| NA| 7,950| Bottom or End4| Side

All dimensions are shown in inches. Weight is shown in pounds and includes largest supply and exhaust fans, PDX with reheat, largest indirect-gas fired furnace, and all dampers. Actual weights will vary based on the unit configuration.

  1. Only available with powered exhaust
  2. Only available without barometric relief
  3. Only available with barometric relief
  4. Only available without powered exhaust
  5. Only available without powered exhaust and without barometric relief
  6. Length with bottom or end return
  7. Length with powered exhaust
  8. Length with powered exhaust bumpout
  9. Optional indirect gas-fired furnace bumpout length is additional 13.3 inches
  • An EIS Unit means the return air intake is located on the side.

Service Clearances

Model| ACS Access Side| CC Control Cabinet End| OAI Outdoor Air Intake| *NA from Unit| NA from Condensing Section| NA from Piping Vestibule (not shown)
---|---|---|---|---|---|---
Other| Indoor Mounted with IG Furnace| Outdoor Mounted| Indoor Mounted
XRV-10| 50| 42| NA| 36| NA| 24| NA| NA
XRV-25| 40| 42| 72| 42| 18| 24| 18| 30
XRV-45| 36| 58| 72| 54| 18| 24| 18| 30
XRV-75| 48| 48| NA| 87| NA| 48| NA| NA
XRV-110| 48| 48| NA| 93| NA| 48| NA| NA

All dimensions are shown in inches.
*No condensing section or piping vestibule, or unit has top condensing section.

Additional Clearances for Packaged DX Units
Packaged DX units require additional clearance because they must have unrestricted air movement around the condenser coil and condenser fans. Hot air is being discharged from the condenser fans during operation. Enough clearance must be provided to avoid recirculation or coil starvation. When equipped with condenser coils, the unit should never be placed under an overhang or inside a building. A minimum of 48 inches above the condenser fans is acceptable, but unobstructed is strongly recommended.

Additional Clearances for Air Source Heat Pump
IMPORTANT
Air-source heat pumps are equipped with a defrost cycle to remove ice from the outdoor coil. During defrost cycles, melted water may drip from the bottom of the refrigeration section under the outdoor coil.
In cold climates, proper drainage/heat tape must be installed under the outdoor coil to prevent the buildup of ice on the roof.

Air-source heat pump units require additional clearance because they must have unrestricted air movement around the outdoor coil and outdoor fans. Enough clearance must be provided to avoid recirculation or coil starvation. Air- source heat pump units  should never be placed under an overhang or inside a building.
A minimum of 48-inches above the outdoor fans is acceptable, but unobstructed is strongly recommended.

Handling Concerns for Packaged DX or Air-Source Heat Pump
Units with PDX or ASHP have a system that is pressurized with refrigerant. If damage occurs, the refrigerant could leak into the atmosphere or cause bodily harm due to the extreme cold nature of expanding refrigerant. Use protective equipment such as gloves and safety glasses to minimize or prevent injury in case of a system leak during installation.
Before Lifting
Before lifting, be sure that all shipping materials have been removed from the unit.
Vestibule
Determine whether or not the unit has a vestibule that must be field-attached to the side of the unit. Vestibules are shipped assembled but detached from the unit.
They have lifting lugs on them so they can also be lifted by crane, but the installed location of the unit may make it preferable to install the vestibule on the unit prior to lifting.
Field Power Access
Determine where high voltage and low voltage wiring is to be brought into the cabinet. If wiring is to be brought into the cabinet through the floor, see Alternate Supply Entry Locations in this manual. If unit is to be installed on a roof, cut access openings in the roof deck as needed.
Temporary Use
This equipment must not be used as:

  • Temporary heating or cooling
  • Construction heating

The units should not be operated until construction is complete and the units have properly undergone the pre-start-up and start-up routines.

Lifting
WARNING
Spreader bars are required to prevent damage to the cabinet, failure to do so can result in damage that is the installer’s responsibility.

  1. Ensure that all shipping materials have been removed from unit.
  2. To assist in determining rigging requirements, weights are provided in the Unit Weights & Dimensions section of this manual.
  3. Refer to submittal for unit weight before lifting. Actual weights will vary based on unit configuration.
  4. Unit must be lifted by all lifting lugs provided at top for all housing sizes except the 75 which must be lifted from the bottom.
  5. Spreader bars must be 6-12” longer than the span of the unit to prevent damage to the cabinet by the lift cables.
  6. Never rest the spreader bar on the unit.
  7. Always test-lift the unit to check for proper balance and rigging before hoisting to desired location.
  8. Never lift unit by weatherhood.
  9. Never lift units in windy conditions.
  10. Preparation of curb and roof openings should be completed prior to lifting unit to the roof.
  11. Check to be sure that gasketing (supplied by others) has been applied to the top of the curb prior to lifting the unit and setting on the curb.
  12. Do not use forklifts for handling unit on housing sizes 25, 45, 75, or 110.
  13. If using forklift on housing 10, use forks with 48-inch length and ensure forks extend to opposite side of unit using factory-installed forklift pockets at unit base.

Rail Mounting and Layout

  • The units may be installed on rails provided and installed by others. Ensure that rails are designed to handle the weight of the unit and provide proper load distribution on building supports.
  • Make sure that rail positioning does not interfere with the openings on the unit.
  • Rails should run the length of the unit and extend beyond the unit a minimum of 12 inches on each side.
  • Unit weight and overall dimensions can be found in the Unit Weights and Dimensions section.
  • Set unit on rails, center the base rails of the unit on the steel support rails.

Roof Curb Mounting
Roof curb details, including duct locations and dimensions, are to be found in the roof curb assembly instructions.
Rooftop units require curbs to be mounted first. The duct connections must be located so they will be clear of structural members of the building.

  1. Factory-supplied roof curbs. Roof curbs are model GKD which are shipped in a knockdown kit (includes duct adapters) and require field assembly (by others) on all units except XRV-110, which are shipped assembled.
    Assembly instructions are included with the curb kit.

  2. Install curb. Locate curb over roof opening and fasten in place. Check that the diagonal dimensions are within ± 1/8 inch of each other and adjust as necessary.
    For proper coil drainage and unit operation, it is important that the installation be level. Shim the curb as required to level. Install gasketing on top surface of curb (provided by others).

  3. Install ductwork. Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines. Duct adapters are provided to support ducts prior to setting the unit.

  4. Set the unit. Lift unit to a point directly above the curb and duct openings. Guide unit while lowering to align with duct openings. Roof curbs fit inside the unit base. Make sure the unit is properly seated on the curb and level.

  5. Fasten the unit, Fasten the unit to the curb/ equipment support(s) using appropriate methods. The installer is responsible for determining appropriate support and fastening methods to ensure compliance with all applicable codes.

  6. Install vestibule. If unit was ordered with a vestibule and it has not yet been attached to the unit, caulk and attach the vestibule at this time.

Optional Piping Vestibule
If the unit was ordered with the vestibule, the NA (NonAccess side) clearance dimension must be measured from the vestibule.

Ductwork Configurations
NOTE
Downblast Discharge Ductwork – whenever downblast discharge is used, the ductwork directly beneath the unit must be connected with either a “T” or an “L” configuration and the area directly beneath the heat source must not have any openings such as louvers or grates.

Recommended Electrical and Gas Supply Entry Locations
Manufacturer recommends that electrical service and gas supply be brought into the cabinet through the end wall, as shown below. There are three penetrations into the cabinet that are required; one for high voltage supply wiring, one for low voltage control wiring and one for either gas supply or high voltage supply wiring for an electric heater.

Alternate Supply Entry Locations
Each installation is unique and as a result, alternate entry locations may be field-located. Before using any alternate entry location, verify the suitability of the location and ensure the use of an alternate location does not interfere with unit wiring, components or
functionality.
Gas Connections
If this unit is equipped with an indirect gas-fired furnace, connection to an appropriate gas supply line will be required. For complete information on installation procedures for the optional gas furnace, refer the XPVF/ XPVG Indirect Gas-Fired Heat Module Installation, Operation, and Maintenance Manual.

Optional Gas Piping
Units with indirect gas-fired furnaces require fieldsupplied and installed gas supply piping.

Housing Size| Total Heating Capacity (Input in MBH)| Gas Connection Size| Max Gas Pressure
---|---|---|---
10| 75| ¾” NPT| 14 in. wg.
100
150
200
25| 100| ¾” NPT| 14 in. wg.
200
300
45| 300| ¾” NPT| 14 in. wg.
400
500
75| 600| ¾” NPT| 14 in. wg.
800
1000| 1” NPT
1200
110| 600| 1” NPT| 13.5 in. wg.
800| 2” NPT
1000
1200

NOTE
Only applies to Heatco furnaces in the 75 housing size. A ¼” NPT condensate drain connection is provided in the flue box for duct furnaces with vertical or horizontal top mounted burner trays, to remove condensate from inside the heat exchanger. Since heat exchangers are under negative pressure, a P-trap should be used when connecting condensate drain lines. Metal condensate drain lines should have corrosion resistance at least equal to that of 304 SS.
WARNING
Never drill holes in the roof of the unit! There is high voltage wiring located between the inner and outer roof panels. Damage to the wiring could cause severe bodily harm or death.
NOTE
XRV-110 gas furnaces are designed for gas pressure of 5-13.5 in. wg for natural gas (6-inch minimum on single 500 and 600 MBH furnaces) and 11-13.5 in. wg for LP. If the gas pressure at the job location is greater than 13.5 in. wg, an additional regulator is required to reduce pressure. For other models, reference the Model XPVF and XPVG IOM.

Piping Installation

Optional Coil Piping
Chilled Water and Hot Water Configuration
Factory-installed chilled water and hot water coils are mounted in the coil section of the unit except for the XRV-10 housing in which the hot water coil will be directly downstream of the supply fan. The coil section is downstream of the supply filter bank and upstream of the supply fan.
Note: For XRV-10, XRV-75 and XRV-110 coil connections are located internal of the unit.
For XRV-25 and XRV-45 coil connections are located external through the side of the unit with the option for a piping vestibule.

Package DX/Split DX and Hot Water Configurations
Factory-installed cooling components are mounted in the coil section of the unit. Hot water coil connection location is based on housing size.
Note: For XRV-25 and XRV-45 hot water coil will be located below the supply fan for. Coil connection will be internal below the compressor/electrical compartment.
For XRV-10 hot water coil will be located directly downstream of supply fan with coil connections internal through the supply fan section.
For XRV-75, and XRV-110 the hot water coil will be located in the coil section with coil connections internal in the unit.

Water Coils

  1. Piping should be in accordance with accepted industry standards. Pipework should be supported independently of the coils. When installing couplings, do not apply undue stress to the connection extending through the unit. Use a backup pipe wrench to avoid breaking the weld between coil connection and header.

  2. Connect the water supply to the bottom connection on the air leaving side and the water return to the top connection on the air entering side. Connecting the supply and/or return in any other manner will result in very poor performance. Be sure to replace
    factory-installed grommets around coil connections if removed for piping. Failure to replace grommets will result in water leakage into the unit and altered performance.

  3. Water coils are not normally recommended for use with entering air temperatures below 40°F. No control system can be depended on to be 100% safe against freeze-up with water coils. Glycol solutions or brines are the only safe media for operation of water coils with low entering air conditions. If glycol or brine solutions are not used, coils must be drained when freezing conditions are expected. If required, vent and drain connections must be fieldpiped, external to the unit.

  4. Pipe sizes for the system must be selected on the basis of the head (pressure) available from the circulation pump. The velocity should not exceed 6 feet per second and the friction loss should be approximately 3 feet of water column per 100 feet of pipe.

  5. For chilled water coils, the condensate drain pipe should be sized adequately to ensure the condensate drains properly. Refer to Drain Trap section.

Direct Expansion (DX) Coils (Split DX)

  1. Piping should be in accordance with accepted industry standards. Pipework should be supported independently of the coils. Undue stress should not be applied at the connection to coil headers.
  2. The condensate drain pipe should be sized adequately to ensure the condensate drains properly. Refer to Condensate Drain Trap section.
  3. When connecting suction and liquid connections make sure the coil is free from all foreign material. Make sure all joints are tight and free of leakage. Be sure to replace factory-installed grommets around coil connections if removed for piping.
  4. Manufacturer does not supply compressor, condensing units, or thermal expansion valve (TXV) with standard models. For further instruction on DX coil installation and operation contact your compressor and/or condenser manufacturer.

Condensate Drain Trap
This unit is equipped with a stainless steel condensate pan with a stainless steel connection is installed underneath the cooling coil. It is important that the condensate pan drain connection must be fitted with a P trap to ensure proper drainage of condensate while maintaining internal static pressures and to prevent migration of sewer gas back into the unit.
A P trap assembly (kit) is supplied with each unit, except for housing 110 and is to be assembled and installed as local conditions require and according to the assembly instructions provided with the P trap. If local and area codes permit, the condensate may be drained back onto the roof, but a drip pad should be provided beneath the outlet. If local and area codes require a permanent drain line, it should be fabricated and installed in accordance with Best Practices and all codes.
In some climates, it will be necessary to provide freeze protection for the P trap and drain line. The P trap should be kept filled with water or glycol solution at all times and it should be protected from freezing to protect the P trap from damage. If severe weather conditions occur, it may be necessary to fabricate a P trap and drain line of metal and install a heat tape to prevent freezing.

Condensate Overflow Switch
This unit is equipped with an optional factory-mounted condensate overflow switch. In the event that a high level of condensate is detected, the microprocessor controller will trigger an alarm and shutdown the unit.

Electrical Information

WARNING
The roof lining contains high voltage wiring. To prevent electrocution, do not puncture the interior or exterior panels of the roof.
WARNING
To prevent injury or death due to electrocution or contact with moving parts, lock disconnect switch open. For units with a gas furnace, if you turn off the power supply, turn off the gas.
WARNING
RISK OF ELECTRIC SHOCK CAN CAUSE INJURY OR DEATH: System contains oversize protective earthing (grounding) terminal which shall be properly connected.
IMPORTANT
Before connecting power to the unit, read and understand the following instructions and wiring diagrams. Complete wiring diagrams are attached on the inside of the control center door(s).
IMPORTANT
All wiring should be done in accordance with the latest edition of the National Electric Code ANSI/NFPA 70 and any local codes that may apply. In Canada, wiring should be done in accordance with the Canadian Electrical Code.
IMPORTANT
The equipment must be properly grounded and bonded. Any wiring running through the unit in the airstream must be protected by metal conduit, metal clad cable or raceways.
CAUTION
If replacement wire is required, it must have a temperature rating of at least 105ºC, except for an energy cut-off or sensor lead wire which must be rated to 150ºC.
DANGER
High voltage electrical input is needed for this equipment. This work should be performed by a qualified electrician.
CAUTION
Any wiring deviations may result in personal injury or property damage. Manufacturer is not responsible for any damage to, or failure of the unit caused by incorrect final wiring.

Determine the Size of the Main Power Lines
The unit’s nameplate states the voltage and the unit’s MCA. The main power lines to the unit should be sized accordingly. The nameplate is located on the outside of the unit on the control panel side.

Determine the Size of Electric Heater Wiring
An optional electric heater may require a separate power supply. The power connection should be made to the factory-provided electric heater disconnect and must be compatible with the ratings on the nameplate, supply power voltage, phase and amperage. Consult ANSI/NFPA 70 and CSA C22.1 for proper conductor sizing.
Provide the Opening(s) for the Electrical Connections
Electrical openings vary by unit size and arrangement and are field-supplied.
Connect the Power Supplies
Connect the main power lines and electric heater power lines to the disconnect switches or terminal blocks and main grounding lug(s). Torque field connections to manufacturer’s recommendations.
Wire the Optional Convenience Outlet
The convenience outlet requires a separate 115V power supply circuit. The circuit must include short circuit protection which may need to be supplied by others.
Connect Field-Wired Low Voltage Components
Most factory-supplied electrical components are prewired. To determine what electrical accessories require additional field-wiring, refer to the unit- specific wiring diagram located on the inside of the control center access door.
The low voltage control circuit is 24 VAC and control wiring should not exceed 0.75 ohms.
Control wires should not be run inside the same conduit as that carrying the supply power. Make sure that field-supplied conduit does not interfere with access panel operation. All low voltage wiring should be run in conduit wherever it may be exposed to the weather.
If wire resistance exceeds 0.75 ohms, an industrial- style, plug-in relay should be added to the unit control center and wired in place of the remote switch (typically between terminal blocks R and G on the terminal strip.
The relay must be rated for at least 5 amps and have a 24 VAC coil. Failure to comply with these guidelines may cause motor starters to “chatter” or not pull in which can cause contactor failures and/or motor failures.
Field-Provided Disconnect
If field-installing an additional disconnect switch, it is recommended that there is at least four feet of service room between the switch and system access panels. When providing or replacing fuses in a fusible disconnect, use dual element time delay fuses and size according to the rating plate.

Control Center Components

Main Control Center Components
Image represents a typical housing 25 or 45 installation. Components and locations will vary on housing sizes 10, 75 and 110.

Electrical Cabinet

  1. Power distribution block; high voltage supply is terminated here

  2. Fuse holders

  3. Phase monitor

  4. Unit Disconnect

  5. Condensing fan motor contactors

  6. Wheel motor contactor

  7. Compressor motor contactors
    Controls Cabinet

  8. Transformer

  9. VFDs

  10. Microprocessor controller

  11. Monitoring points

  12. Low voltage terminal strip

  13. Relays

  14. Dirty filter switches

  15. Wheel pressure switch

  16. Outdoor airflow monitor

  17. Exhaust airflow monitor

  18. Digital scroll controller

Optional Indirect Gas-Fired Furnace
Note: In some models, two furnaces are installed to provide greater output. When two furnaces are installed, they are in parallel and both will operate at the same time and the same output. Both furnaces will have identical controls.

  1. Single-stage valve
  2. Modulating valve
  3. PCOE expansion board
  4. Ignition controller
  5. Transformer
  6. Combustion blower
  7. Burner manifold
  8. Collector box

For further information on the optional furnace and its control center, see the Indirect Gas-Fired Heat lOM shipped with the unit.

Component Operation

Phase Monitor
The unit control circuitry includes a phase monitor that constantly checks for phase reversal, phase imbalance, loss of phase or a power brownout. When it detects a fault, it cuts off the 24 VAC that goes to the low voltage terminal strip, thereby shutting off all motors.
Variable Frequency Drive (VFD)
If a VFD was provided and installed at the factory, it has been pre-set to control the speed of the blower motor for optimum performance. The motor speed needs to be verified during test and balance of the unit.
If the system was configured for Constant Air Volume (CAV), the VFD will operate in an ON/OFF fashion and the speed of the motor will not change. If the system was configured for Variable Air Volume (VAV), the microprocessor will constantly monitor operating conditions and provide a signal to the VFD, changing the VFD output as needed.
The VFD may alternatively be connected to an external signal such as provided by a BMS and be operated by a -10 VDC or a 4-20 mA input.
Supply Fan VFD Sequence
Optional Room CO2 Sensor: The microprocessor will modulate the supply fan based on a comparison of the CO2 set point to the actual CO2 levels reported from the sensor. Mechanical high static protection cutoffs must be installed by others to protect the system and equipment from over-pressurization.
Optional Duct Static Pressure Sensor: The microprocessor will modulate the supply fan based on a comparison of the duct static pressure set point to the actual duct static pressure level reported from the sensor. Mechanical high static protection cutoffs must be installed by others to protect the system and equipment from over-pressurization. The manufacturer does not assume responsibility for this.
Optional Building Static Pressure Sensor: The supply fan is modulated based upon the signal from a building static pressure sensor. The microprocessor will modulate the supply fan based on a comparison of the building static pressure set point to the actual building static pressure level reported from the sensor.
Optional Single Zone VAV: The microprocessor will use a space mounted temp sensor to vary heating and cooling capacity and the airflow delivered by the fan to maintain room-air temp at a desired set point.
Optional 0-10 VDC by others to VFD: Supply fan is modulated by a 0-10 VDC, field-provided by others.

Optional Component Operation
Exhaust Fan VFD Sequence
Optional Building Static Pressure Sensor: The exhaust fan is modulated based upon the signal from a building static pressure sensor. The microprocessor will modulate the exhaust fan based upon a comparison of the building static pressure level reported from the sensor.
Optional Outdoor Air Damper Tracking: The microprocessor will proportionally modulate the exhaust fan based upon the outdoor air damper position.
Optional Supply Tracking: The microprocessor will proportionally modulate the exhaust fan based upon the supply fan.
Optional 0-10 VDC by Others to VFD: The supply fan is modulated by a 0-10 VDC provided by others in the field.
Outdoor Air and Recirculated (Recirc) Air Damper Sequence
Optional Room CO2 Sensor: The microprocessor will proportionally modulate the OA/RA dampers based upon a comparison of the CO2 set point to the actual CO2 level reported from the sensor. As the CO2 rises, the controller will proportionally modulate the outdoor air damper open, between the minimum and maximum OA position.
Optional Building Pressure: The OA/RA dampers will modulate based upon the signal from a building static pressure sensor. The controller will modulate the dampers, between the minimum and maximum OA positions, based upon a comparison of the building
static pressure set point to the actual building static pressure level reported from the sensor.
Exhaust Fan Only Power
The exhaust fan will have a dedicated power circuit where in the case of a power outage, the exhaust fan will still run. A phase monitor will detect an outage or power loss and open the contact, disconnecting all power to the unit and controller. An external signal will need to be sent to a relay to power the exhaust fan, enabling the fan to run at a maximum speed. This sequence is NOT to be used for high temperature exhaust applications.
Service Lights
Service lights provide light to each of the compartments in the energy recovery unit. The lights are wired into the service outlet receptacle on the outside of the unit. The switch to turn on the lights is located in the unit control center. level

Electronically Commutated (EC)
Condenser Fans with Inverter Scroll or Digital Scroll Compressors
The EC condenser fan(s) will modulate up and down to maintain the optimal liquid line pressure using built in control sequences within the factory controller. One pressure transducer is provided with each refrigeration circuit for monitoring and the factory controller will ramp condenser fan(s) up or down based on the condenser set point.
Economizer Fault Detection Diagnostics
Provides the status and faults of the air economizer to indicate proper economizer sequence operation.
This assures the benefits of free cooling when outdoor conditions are suitable for economizer functions. The fault detection diagnostics system will indicate when free cooling is available and if the outside air damper and recirculation damper are reacting  properly. If the dampers are not functioning correctly an alarm will be generated.

Air-Source Heat Pump
Operating Conditions and Limitations
To operate in Cooling mode, the following conditions must be true:

  1. Supply air temperature above minimum low supply temperature limit (35°F)
  2. Outside air temperature above the cooling ambient lockout (55°F, adj.)

To operate in Heating mode, the following conditions must be true:

  1. Supply air temperature below maximum high supply temperature limit (120°F)
  2. Supply air temperature above 35°F
  3. Outside air temperature above the low ambient lockout (10°F, adj.)

For more information on air-source heat pump operation, reference the supplemental Reference Guide for Microprocessor Controller.

IMPORTANT
Air-source heat pumps are equipped with a defrost cycle to remove ice from the outdoor coil. During defrost cycles, melted water may drip from the bottom of the refrigeration section under the outdoor coil.
In cold climates, proper drainage/heat tape must be installed under the outdoor coil to prevent the buildup of ice on the roof.
IMPORTANT
Melted water from snow accumulation on the unit roof can be sucked into outdoor fans, resulting in ice formation on fan blades under certain conditions.
Remove snow accumulation from the unit roof and outdoor coil section after snow storms.

Airflow Monitor
IMPORTANT
For the outdoor airflow monitoring device to perform as intended, field calibration is required. Calibration of the airflow monitoring device requires an independent measurement of airflow and should be performed when the system undergoes test and balance.
A factory-wired, mounted, and powered airflow monitoring system is provided in the outdoor, supply, and/or exhaust air streams. The airflow control system displays outdoor, supply, and/or exhaust air in actual cubic feet per minute (CFM) at factory controller or can be read by a building management system if communication is established.

Operation
Outdoor airflow monitoring is accomplished using two thermal dispersion sensors that accurately measure airflow velocity down to zero feet per minute (fpm). The airflow controller takes the average measurement for two sensor configurations, and determines the outdoor airflow rate based on the effective intake area. Field calibration of the outdoor airflow monitoring device determines the effective intake area of the unit. For additional information on how to navigate through the outdoor airflow controller menus,  refer to technical manuals from GreenTrol® Automation Inc. at www.greentrol.com.
Supply and/or exhaust airflow monitoring is accomplished by measuring the pressure drop across the fan inlet venture. The airflow is then calculated by the factory controller based on the measured pressure drop and a K-Factor specific for each fan size.

Hot Gas Reheat Valve
Units equipped with a reheat coil use a three-way valve with actuator to control the supply air discharge temperature of the unit during dehumidification mode.
The unit controller provides a 0-10 VDC signal to control the amount of reheat to meet the supply temperature set point.
Controls by Others
The reheat coil needs to be purged to ensure adequate oil return. It is recommended that every six hours of reheat compressor run time should initiate a six minute purge cycle. During the purge cycle, the reheat valve should be modulated to 100% open to the reheat coil.

VFD Compressor
If the VFD compressor option is included, the compressor VFD is mounted in the end of the condensing section. Condensing section internal components are accessible via the access panel on the side of the condenser coil.
Envelope Control
The unit controller tracks the operating point of the VFD compressor within the operating envelope at all times. If the operating point is out of the envelope, the controller will take action to bring it back in. If unsuccessful, the controller will shut down the compressor. DO NOT operate the compressor VFD in hand mode because the envelope control safeties will not be in place. Refer to the controls IOM for more information on envelope control.
Electronic Expansion Valve
An electronic expansion valve is provided on the VFD compressor circuit to ensure tight superheat control throughout the compressor modulation band. The EXV acts as a liquid line solenoid valve when the compressor is off to prevent refrigerant migration.
Crankcase Heat
The VFD compressor will be heated by the compressor stator. To ensure optimal performance and reliability, do not disable stator heat. All other compressors will be provided with a crankcase heater.
Oil Return Management
The compressor VFD has an oil return purge cycle such that if the compressor has been operating below a set RPM for a set period of time, the VFD will accelerate the compressor to ensure sufficient lubrication.
DO NOT disable the oil return management function.
DO NOT operate the compressor VFD in hand mode because the oil return management will not be operational.
Pressure Relief Device
A fusible plug is included on package DX and air-source heat pump systems. This device is to allow pressure relief in the instance dangerous temperatures are occurring within the refrigeration system.
Package DX cooling or air-source heat pump systems cannot be mounted indoors.
Ultraviolet Germicidal Irradiation (UVGI)
UV-C lights are mounted downstream of the cooling coil, provide coil surface and drain pan disinfection. The lights are factory powered and are on when the supply blower is running. A kill switch on the coil access door turns the lights off when that door is open.

Needlepoint Bipolar Ionization (NPBI®)
Needlepoint bipolar ionizers are mounted on the fan inlet cone(s) and provide air disinfection. The ionizers are factory-powered and are on when there is power to the unit disconnect.
Dirty Filter Sensor
Dirty filter sensors monitor pressure drop across the outdoor air filters, exhaust air filters, or both. If the pressure drop across the filters exceeds the set point, the sensor will close a set of contacts in the unit control center. Field-wiring of a light (or other alarm) to these contacts will notify maintenance personnel when filters need to be replaced. The switch has not been set at the factory due to external system losses that will affect the switch. This switch will need minor field adjustments after the unit has been installed with all ductwork complete. The dirty filter switch is mounted in the exhaust inlet compartment next to the unit control center or in unit control center.
Microprocessor Control
The microprocessor controller is specifically designed and programmed to optimize the performance of the unit with supplemental heating and cooling. This option ensures that the outdoor air is conditioned to the desired discharge conditions. The controller and accompanying sensors are factory- mounted, wired and programmed. Default settings are pre-programmed, but are easily field-adjustable.
The microprocessor controller can be interfaced with a Building Management System through, BACnet® or ModBus.
Please refer to the Installation, Operation and Maintenance manual for detailed information.
Unoccupied Recirculation Damper
The unoccupied recirculation option provides ae recirculation damper from the return air intake to the supply airstream. If equipped with a room temperature and/or relative humidity sensor, the unit can cycle on to maintain unoccupied room set points if there is a call for unoccupied heating, cooling, or dehumidification.
During the unoccupied mode, the supply and exhaust (if equipped) fans will be off unless there is a call for cooling, heating, or dehumidification in the space.

Factory-Installed Refrigeration System Components

Packaged DX Cooling with Three Way Hot Gas Reheat and Hot Gas Bypass

1. Compressor
2. High Limit Pressure Switch
The switch opens when refrigerant pressure increases above the set point in the discharge line.
A manual reset is then required.
3. Hot Gas Reheat Valve (optional)
Units equipped with a reheat coil use a threeway valve with actuator to control the supply air discharge temperature of the unit during dehumidification mode. The unit controller provides a 0-10 VDC signal to control the amount of reheat to meet the  supply temperature set point
4. Hot Gas Reheat Coil (Optional)
5. Hot Gas Reheat Check Valve (Optional)
6. Condenser Fans
7. Condensing Coil
9. Liquid Line Filter Drier
10. Sight Glass
12. Electronic Expansion Valve (EXV) HPT
This valve controls the flow of liquid refrigerant entering the evaporative coil by maintaining a constant superheat.
13. Evaporative Coil
14. Low Pressure Transducer
15. Service Access Ports
16. High Pressure Transducer
17. Pressure Relief Device (PRD)

Air-Source Heat Pump with Three Way Hot Gas Reheat

Factory-Installed Refrigeration System Components

  1. Compressor

  2. High Limit Pressure Switch
    The switch opens when refrigerant pressure increases above the set point in the discharge line.
    A manual reset is then required.

  3. Hot Gas Reheat Valve (optional)
    Units equipped with a reheat coil use a threeway valve with actuator to control the supply air discharge temperature of the unit during dehumidification mode. The unit controller provides a 0-10 VDC signal to control the amount of reheat to meet the supply temperature set point

  4. Hot Gas Reheat Coil (Optional)

  5. Hot Gas Reheat Check Valve (Optional)

  6. Outdoor Fans

  7. Outdoor Coil

  8. Refrigeration Accumulator

  9. Liquid Line Filter Drier

  10. Sight Glass

  11. Four Way Reversing Valve
    Each compressor circuit is equipped with a reversing valve to reverse the direction of refrigerant flow, switching the unit between heating and cooling mode.

  12. Electronic Expansion Valve (EXV) or Thermostatic Expansion Valve (TXV) An expansion valve is provided on each refrigerant circuit. This valve controls the flow of liquid refrigerant entering the indoor and outdoor coils by maintaining a constant superheat. The TXV is adjustable. Both the EXV and TXV are located on the side of the outdoor coil and can be accessed through the refrigeration system access panel.

  13. Indoor Coil

  14. Low Limit Pressure Switch
    The switch is installed on the suction line and disables the DX system when the suction pressure drops below the set point. The switch will auto reset when the pressure rises above the auto-reset set point.

  15. Service Access Ports
    Typical port locations are shown. Additional valves may be present in the system.

  16. Refrigerant Pressure Transducers

  17. Pressure Relief Device (PRD)
    Typical refrigerant pressure relief location. Device includes a fuse plug that operates as a safety relief when dangerous temperature builds within the refrigeration system.

Start-Up Components

Fan
The fan should be checked for free rotation. If any binding occurs, check for concealed damage and foreign objects in the fan housing.

CAUTION
When operating conditions of the fan are to be changed (speed, pressure, temperature, etc.), consult manufacturer to determine if the unit can operate safely at the new conditions.

Supply Fan (Plenum Type)
The unit contains one or two plenum supply fans located on the end of the unit opposite the outdoor air intake and may optionally have a relief air blower which is referred to as an exhaust blower in this document. Efficient fan performance can be maintained by  having the correct offset.

Offset: Proper offset, or overlap, is adjusted by loosening the wheel hub from the shaft and moving the wheel to the desired position along the shaft.
The transition between the inlet cone and the wheel should be as shown; there is a smooth feel to the profile when moving one component to the other.

Fan Size Offset (inches) Tolerance (inches)
ER35C 5/32 ± 1/32
ER45C 3/16 ± 1/32
ER50C 13/64 ± 1/32
ER56C 1/4 ± 1/32
PDL-355 5/32 ± 1/32
PRM-450 3/16 ± 1/32
PRM-560 15/64 ± 1/32

Refer to the respective Installation, Operation and Maintenance Manual shipped with this unit for additional start-up and maintenance information regarding the plenum fan.

Fan Wheel Rotation Direction
Check for proper wheel rotation by momentarily energizing the fan. Rotation is determined by viewing the wheel from the drive side and should match the rotation decal affixed to the fan housing.
If the wheel is rotating the wrong way, direction can be reversed by interchanging any two of the three electrical leads. Check for unusual noise, vibration or overheating of the bearings. Refer to the Troubleshooting portion of this manual if a problem develops.

Supply/Exhaust Fan
The optional exhaust fan is a direct-drive plenum type.
Fan speed is controlled by a VFD which, in turn, is controlled by the microprocessor controller or by an external signal. Motor speed will be set on the VFD during the unit Test and Balance, but after that, the VFD will not normally be changed. Always check the
motor amperage rating shown on the motor nameplate when changing the fan RPM. All access doors must be installed except the control center door.

Vibration
Vibration Causes

Off axis or loose components Drive component unbalance Poor inlet / outlet conditions Foundation stiffness
Excessive vibration may be experienced during initial start-up. Left unchecked, excessive vibration can cause a multitude of problems, including structural and/ or component failure. The most common sources of vibration are listed.
Many of these conditions can be discovered by careful observation. Refer to the Troubleshooting section of this manual for corrective actions. If observation cannot locate the source of vibration, a qualified technician using vibration analysis equipment should be consulted.
Generally, fan vibration and noise is transmitted to other parts of the building by the ductwork. To eliminate this undesirable effect, the use of flexible connectors is recommended.

Discharge Air Temperature Sensor
Units are supplied with a Discharge Air Temperature Sensor that is to be field-installed prior to unit startup.
The sensor is to be installed at least three duct diameters downstream of the heat exchanger.
The sensor must be connected directly to the microprocessor controller.
All other sensors and low voltage devices are to be connected to the low voltage terminal strip in the control center. The discharge air sensor is shipped loose and can be found in the unit’s control center. See the unit- specific wiring diagram for connection locations.
Airflow Monitoring
For additional information on how to navigate through the airflow controller menus, refer to technical manuals from GreenTrol® Automation Inc. at www.greentrol. com. Also refer to the Greenheck Reference Guide for Microprocessor Controller.
Display and Navigation
The LCD screen will by default show the current airflow that is being measured. To enter the menu to set up the monitoring station the user must remove the front cover of the GreenTrol to uncover the navigation buttons. Press and hold the UP and DOWN keys at the same time for 3 seconds to enter the menu.
Enter Button Function – The ENTER button allows the user to go into the selected menu or function, as well as save the selected value.
Up/Down Button Function – The UP/DOWN buttons are used to navigate the menu and to change values in the menu.
Esc Button Function – The ESC button allows the user to exit the current menu or function.

Field Calibration

  1. Press UP/DOWN = Setup
  2. Press DOWN/ENTER = Setup Wizard
  3. Scroll Down to Field Adjust and press ENTER
  4. Run FAK wizard and press ENTER
  5. Set FAW Int and press ENTER
  6. FAW INT = 300 and press ENTER
  7. Set number of flows and press ENTER
  8. Set flow and press ENTER
  9. Set flow to actual CFM measured by Test and Balance and press ENTER
  10. Wait for calibration before cycling power
  11. Proceed to Communication Setup

Communication Setup

  1. Press the UP and DOWN keys at the same time for 3 seconds

  2. When SETUP appears on the screen press ENTER

  3. Scroll DOWN (twice) to the NETWORK menu and press ENTER

  4. When NETOUT appears on the screen, press ENTER; when SET NETOUT appears on the screen, press ENTER again

  5. Scroll UP or DOWN to set the NETOUT = MODBUS and then press ENTER

  6. Scroll DOWN to NETADDR and press ENTER, when SET NETADDR appears on the screen press ENTER again

  7. Scroll UP or DOWN to set the NETADDR to the same address that was listed for the airflow monitor in the microprocessor. For instance, the Outdoor Airflow Monitor screen above has an address of 31.
    Then press ENTER.

  8. Scroll DOWN to NETBAUD and press ENTER, when SET NETBAUD appears on the screen, press ENTER again

  9. Scroll UP or DOWN until NETBAUD = 19200, then press ENTER

  10. Scroll down to PARITY and press ENTER, when SET PARITY appears on the screen press ENTER again

  11. Scroll UP or DOWN until PARITY = NONE2, then press ENTER

  12. Once the address is set and the communication wires are connected, “Status” LED should be a steady green and the “RS485” LED should be a quick blinking green LED.

Optional Dirty Filter Switch
To adjust the switch, the unit must be running with all of the access doors in place, except for the compartment where the switch is located (exhaust intake compartment). The adjusting screw is located on the top of the switch.

  1. Open the filter compartment and place a sheet of plastic or cardboard over 50% of the filter media.
  2. Replace the filter compartment door.
  3. Check to see if there is power at the alert signal leads (refer to electrical diagram).
  4. Whether there is power or not, turn the adjustment screw on the dirty filter gauge (clockwise if you did not have power, counterclockwise if you did have power) until the power comes on or just before the power goes off.
  5. Open the filter compartment and remove the obstructing material.
  6. Replace the door and check to make sure that you do not have power at the alert signal leads. The unit is now ready for operation.

Troubleshooting – Alarms

Several of the electronic controls in the unit monitor the system for faults and will go into alarm, shutting down the unit or a single function within the unit.
Microprocessor Controller
Check the screen on the microprocessor for an alarm condition. If the microprocessor is in an alarm condition, a message will show on the microprocessor controller screen.
The microprocessor is located in the main control center. If the microprocessor is in alarm condition, the Alarm button will blink red. Press the Alarm button to see the specific condition or to reset the microprocessor. Refer to the microprocessor IOM for detailed information on fault codes and see the unitspecific wiring diagram.
Phase Monitor
The phase monitor has two LED indicator lights, one red and one green. Green indicates proper operational status, red indicates the unit has detected a fault and is in alarm condition. The alarm LED will blink to show the specific fault and there is a chart printed on the monitor that shows the code for the blinking light. The phase monitor is self-resetting once the alarm condition is corrected. It is located in the main control center.
Variable Frequency Drive (VFD)
Variable frequency drives have a display screen that will show an alarm condition. If a fault such as a voltage spike occurs, the VFD will go into alarm and will not reset until a hard restart is performed. See the unitspecific manufacturer’s manual supplied with the unit. VFDs are located in the main control center.

Troubleshooting – Unit

Symptom Possible Cause Corrective Action
Blower fails to operate Blown fuse or open circuit breaker. Replace fuse or

reset circuit breaker and check amps.
Defective motor or capacitor.| Replace.
Motor overloaded.| Reset VFD and check amps.
Electrical.| Check for On/Off switches. Check for correct supply voltage. Check Control wiring.
Motor starters “chatter” or do not pull in| Control power (24 VAC) wiring run is too long. (Resistance should not exceed 0.75 ohms).| Shorten wiring run to mechanical room or install a relay to turn unit on/off. Consult factory for relay information. Increase wire gauge size so that resistance is 0.75 ohms or less.
Incoming supply power is less than anticipated. Voltage supplied to starter coil must be within +10% / -15% of nominal voltage stated on the coil.| Need to increase supply power or use a special control transformer which is sized for the actual supply power.
Motor over amps| Static pressures are higher than design.| Check for dirty filters. Improve ductwork.
Motor voltage incorrect.| Check motor wiring. Check motor nameplate versus supplied voltage.
Motor horsepower too low.| See specifications and catalog for fan curves to determine if horsepower is sufficient.
Shorted windings in motor.| Replace motor.
Low airflow (cfm)| Unit damper not fully open.| Adjust damper linkage or replace damper motor.
System static pressure too high.| Improve ductwork to eliminate losses using good duct practices.
Blower speed too low.| Check maximum motor RPM and compare with catalog data. Verify that external control wiring is in place if required.
Fan wheels are operating backwards.| For 3-phase, see Direction of Fan Wheel Rotation Direction in Start-Up, Components section.
Dirty filter.| Replace filters or follow cleaning procedures in Routine Maintenance section of this manual.
Leaks in ductwork.| Repair.
Elbows or other obstructions may be obstructing fan outlet.| Correct or improve ductwork.
High airflow (cfm)| Blower fan speed too high.| Check for correct maximum fan RPM. Decrease maximum fan speed if necessary in the VFD.
Filter(s) not in place.| Install filters.
Insufficient static pressure (Ps). (airflow resistance)| Induce Ps into system ductwork. Make sure grilles and access doors are installed. Decrease fan speed if necessary.
Excessive noise or vibration| Fan wheel rubbing on inlet.| Adjust wheel and/or inlet cone. Tighten wheel hub or bearing collars on shaft.
Bearings.| Replace defective bearing(s). Lubricate bearings. Tighten collars and fasteners.
Loose wheel on shaft.| Tighten wheel hub.
Motor base or blower loose.| Tighten mounting bolts.
Noise being transmitted by duct.| Make sure ductwork is supported properly. Make sure ductwork metal thickness is sized for proper stiffness. Check duct size at discharge to ensure that air velocities are not too high.

Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service information.

TROUBLESHOOTING NOTE
Before any components are changed on the refrigeration system, the cause of the failure must be identified. Further problems will exist unless the true cause or problem is identified and corrected.

IMPORTANT
Do not release refrigerant to the atmosphere! If required service procedures include the adding or removing of refrigerant, the service technician must comply with all federal, state and local laws. The procedures discussed in this manual should only be performed by a qualified EPA Certified Technician.

NOTE: Unit is equipped with a phase loss/phase reversal control. If system does not start, check phase of electrical supply.
The first step in troubleshooting a refrigeration circuit is to examine the microprocessor controller and digital scroll compressor controller (if present) and see if there is a fault code. The next step is to check airflow conditions (e.g. improper ductwork, atypical wet bulb / dry bulb, etc.). After these steps have been eliminated, proceed with troubleshooting by following this guide.

Symptom Possible Cause Corrective Action
Compressor will not run or does not start Open disconnect switch or circuit
breaker. Close switch and/or breaker.
Compressor contactor not closing. Check voltage to contactor coil,

transformer, slave relay, system. Replace parts as necessary.
Blown fuse or tripped breaker.| Check for reason and repair. Replace fuse after correcting problem.
Low line voltage.| Check line voltage. If more than 10% from compressor marking, correcting is necessary.
Compressor motor protector open.| Motor thermal protector automatically resets. Allow time (2 hours) for compressor to cool down so protector will reset. Restart and check for reason overheat occurred.
Compressor defective.| Check motor for open circuit, short circuit, grounded windings, or burn out. Compressor may be seized; check refrigerant. If necessary, replace compressor.
High pressure switch open or defective.| If manual reset (high pressure), reset switch. (Switch opens at 610 psi and will not reset above 420 psi for R-410A). Replace if defective.
Low pressure switch open or defective.| See switch label for setpoint.
Open room thermostat or control. (No cooling required).| Check room temperature. If temperature is proper, wait for thermostat to close.
Loose wiring.| Check all wire terminals and tighten as necessary.
Compressor starts but cuts out on low pressure
Low pressure switch cuts out at
50 PSIG (PDX) or 25 PSIG (ASHP)| Low or loss of refrigerant charge.| Check refrigerant pressures and temperatures (subcooling.)
Airflow restricted.| Check for dirty evaporator coil, dirty filters, dampers closed, iced evaporator coil, improper belt, check motor amps, check duct design.
Restriction in refrigerant line.| Check refrigerant pressures, look for frosted tubing and components indicating a restriction. Check pressure drop across the filter drier.
Defective low pressure switch.| Replace.

Troubleshooting – Refrigeration Circuit

Symptom Possible Cause Corrective Action

Compressor starts but cuts out on high pressure switch
High pressure switch cuts out at 610 PSIG| Refrigerant overcharge.| Check pressures, charge by subcooling.
Condenser fan motor defective.| Check fan motor.
Condenser coil inlet obstructed or dirty.| Check coil and clearances. Clean coil if necessary.
Air or non-condensables in system.| Check high side equalized pressures, check expansion valves.
Defective high pressure switch.| Replace.
Restriction in discharge or liquid line.| Check refrigerant line pressures, check expansion valves, replace any defective component.
Condensing fan relay not pulling in.| Replace.
Compressor cuts out on thermal overload| Low voltage.| Check voltage.
Sustained high discharge pressure.| Check running amperage and conditions described under “low suction pressure” symptoms.
High suction and discharge pressures.| Check thermal expansion valve setting, check for air in system. Check air conditions and cfm.
Defective compressor overload.| If compressor is hot, allow compressor to cool for two hours. Recheck for open circuit.
Improper refrigerant charge.| Check subcooling.
Improperly wired.| Review wiring schematics.
Loose wiring.| Check all connections.
Defective start relay.| Replace relay.
Motor windings damaged.| Verify amp draw.
Compressor hums, but will not start| Improperly wired.| Review wiring schematics.
Low line voltage.| Check voltage.
Loose wiring.| Check all connections.
Defective start relay.| Replace relay.
Motor winding damaged.| Verify amp draws. Replace compressor if necessary.
Internal compressor mechanical damage.| Replace.
Compressor noisy or vibrating| Refrigerant overcharge.| Check pressures and subcooling.
Liquid floodback.| Check thermal expansion valve setting. Check for refrigerant overcharge.
Tubing rattle.| Dampen tubing vibration by taping or clamping. Carefully bend tubing away from contact where possible.
Scroll compressor rotating in reverse. (3-phase)| Check high and low side pressures during operation to confirm. Rewire for opposite rotation.
Damaged compressor.| Replace the compressor.
Improper mounting on unit base.| Check that compressor is properly isolated and mounting bolts are tight.
Symptom| Possible Cause| Corrective Action
---|---|---
Low discharge pressure| Insufficient refrigerant charge.| Check subcooling, check for leak. Repair leak and add refrigerant.
Defective or improperly adjusted expansion valve.| Check superheating and adjust thermal expansion valve.
Low suction pressure.| See “low suction pressure”.
Faulty condenser temperature controls. (Condensing fan cycle switch).| Check condenser controls and reset to obtain desired condensing temperature.
Compressor short cycles| Thermostat location or controls malfunction.| Check thermostat, check heat anticipator setting.
Improper refrigerant charge.| Check subcooling, verify superheat.
Defective high or low pressure control.| Check high or low pressure switch.
Poor air distribution.| Check ductwork for recirculating.
Low airflow at evaporator coil.| Check blower operation and airstream restrictions.
Incorrect unit selection (oversized).| Contact factory.
Compressor loses oil| Refrigerant leak.| Check system for leaks. Repair leaks and add refrigerant.
Short cycling.| Check low pressure control settings.
Refrigerant flood back.| Check thermal expansion valve setting. Check for refrigerant overcharge. Check crankcase heater operation.
Reheat flush cycle inadequate.| Contact factory.
Not enough capacity or lack of performance| Refrigeration undercharged.| Check subcooling. Adjust charge, if necessary.
Dirty filter or evaporating coil.| Check filter, coil and airflow.
Dirty or clogged condensing coil.| Check coil and airflow.
Air or other non-condensables in system.| Check equalized high side pressure with equivalent outdoor temperature.
Restriction in suction and liquid line.| Check for restrictions in refrigerant circuit.
Control contacts stuck.| Check wiring.
Excessive load.| Add more equipment or reduce room load.
Liquid line is frosted or wet| Restriction in liquid line.| Clear restriction upstream of point of frosting. (Note: liquid line frosting in normal on ASHP units).
Suction line is frosting| Insufficient evaporating coil airflow.| Check airflow, check filters, check VFD control signal for proper operation.
Malfunctioning or defective expansion valve.| Check bulb of thermal expansion valve.
Frost on evaporating coil (Note: Normal on ASHP units in heating mode).| Hot gas bypass valve not functioning properly (if equipped).| Check valve. If defective, replace.
Manual hot gas bypass valve closed (if equipped).| Open valve.
Low load or airflow.| Increase airflow, check filters.
Symptom| Possible Cause| Corrective Action
---|---|---
Low discharge pressure| Insufficient refrigerant charge.| Check subcooling, check for leak. Repair leak and add refrigerant.
Defective or improperly adjusted expansion valve.| Check superheating and adjust thermal expansion valve.
Low suction pressure.| See “low suction pressure”.
Faulty condenser temperature controls. (Condensing fan cycle switch).| Check condenser controls and reset to obtain desired condensing temperature.
Compressor short cycles| Thermostat location or controls malfunction.| Check thermostat, check heat anticipator setting.
Improper refrigerant charge.| Check subcooling, verify superheat.
Defective high or low pressure control.| Check high or low pressure switch.
Poor air distribution.| Check ductwork for recirculating.
Low airflow at evaporator coil.| Check blower operation and airstream restrictions.
Incorrect unit selection (oversized).| Contact factory.
Compressor loses oil| Refrigerant leak.| Check system for leaks. Repair leaks and add refrigerant.
Short cycling.| Check low pressure control settings.
Refrigerant flood back.| Check thermal expansion valve setting. Check for refrigerant overcharge. Check crankcase heater operation.
Reheat flush cycle inadequate.| Contact factory.
Not enough capacity or lack of performance| Refrigeration undercharged.| Check subcooling. Adjust charge, if necessary.
Dirty filter or evaporating coil.| Check filter, coil and airflow.
Dirty or clogged condensing coil.| Check coil and airflow.
Air or other non-condensables in system.| Check equalized high side pressure with equivalent outdoor temperature.
Restriction in suction and liquid line.| Check for restrictions in refrigerant circuit.
Control contacts stuck.| Check wiring.
Excessive load.| Add more equipment or reduce room load.
Liquid line is frosted or wet| Restriction in liquid line.| Clear restriction upstream of point of frosting. (Note: liquid line frosting in normal on ASHP units).
Suction line is frosting| Insufficient evaporating coil airflow.| Check airflow, check filters, check VFD control signal for proper operation.
Malfunctioning or defective expansion valve.| Check bulb of thermal expansion valve.
Frost on evaporating coil (Note: Normal on ASHP units in heating mode).| Hot gas bypass valve not functioning properly (if equipped).| Check valve. If defective, replace.
Manual hot gas bypass valve closed (if equipped).| Open valve.
Low load or airflow.| Increase airflow, check filters.

Routine Maintenance

DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or maintenance, turn the electrical power to the unit to OFF at disconnect switch(es). Unit may have multiple power supplies.
CAUTION
Use caution when removing access panels or other unit components, especially while standing on a ladder or other potentially unsteady base. Access panels and unit components can be heavy and serious injury may occur.

This unit requires minimal maintenance to operate properly. Maintenance requirements for this model vary for each installation and depend greatly on how much the system is used and the cleanliness of the air.
Proper maintenance will both increase the life of the system and maintain its efficiency. Maintenance must be performed by experienced technicians and in the case of refrigeration systems, must be done by an EPA certified technician.
Maintenance frequency is based on a presumed nominal use of the system. If the system is being run constantly, the frequency should be adjusted accordingly. If there is seasonal debris in the air which can be drawn into the filters and the coils, they should be checked more frequently. If the system is being used for only a few hours per day, the frequency may be reduced. Use the maintenance log at the end of this manual to record each maintenance session and observations and then establish a maintenance schedule that is appropriate for the installation. The following is provided as a guideline.

Maintenance Frequency:
Monthly

  1. External Filter
    Clean metal mesh filters

  2. Internal Filters
    Replace MERV 8 filters monthly.
    Adjust replacement schedule for MERV 13 and MERV 14 or other filters as inspection requires.

Semiannually

  1. Check motor and motor bearings
    Check for excessive heat, vibration or noise.
    Lubricate bearings in accordance with the motor manufacturer’s recommendations.

  2. Condensate Drain (if applicable)
    Inspect and clean – refill with water

  3. Heat Transfer Coils (if applicable)
    Inspect for cleanliness – clean as required

  4. Outdoor Fan Blades and Motor (if applicable)
    Check for cleanliness
    Check all fasteners for tightness
    Check for fatigue, corrosion, wear

Annually
It is recommended that the annual inspection and maintenance occur at the start of the cooling season.
After completing the checklist, follow the unit start-up checklist provided in the manual to ensure the refrigeration system operates in the intended matter.

  1. Lubrication
    Apply lubricant where required

  2. Dampers
    Check for unobstructed operation

  3. Blower Wheel and Fasteners
    Check for cleanliness
    Check all fasteners for tightness
    Check for fatigue, corrosion, wear

  4. Door Seal
    Check if intact and pliable

  5. Wiring Connections
    Check all connections for tightness

  6. Cabinet
    Check entire cabinet, inside and out, for dirt buildup or corrosion. Remove accumulated dirt, remove any surface corrosion and coat the area with appropriate finish.

  7. UV-C Lamps
    Check bulbs for cracks or damage and replace them after 1 year of use or roughly 9,000 hours.
    The effectiveness of the lights decreases after 1 year of use. If bulbs are not replaced before 9,000 hours routine maintenance needs to be more frequent to ensure lights are still functioning properly.

Maintenance Procedures:
Lubrication – Check all moving components for proper lubrication. Apply lubricant where required.
Any components showing excessive wear should be replaced to maintain the integrity of the unit and ensure proper operation.
Dampers – Check all dampers to ensure they open and close properly and without binding. Backdraft dampers can be checked by hand to determine if blades open and close freely. Apply power to motorized dampers to ensure the actuator opens and closes the damper as designed.
Gas Furnace – Maintain furnace in accordance with instructions in the Indirect Gas-Fired Heat IOM shipped with this unit.
Fan Motors – Motor maintenance is generally limited to cleaning and lubrication. Cleaning should be limited to exterior surfaces only. Removing dust and grease buildup on the motor housing assists proper cooling.
Never wash-down the motor with high pressure spray. Greasing of motors is only intended when fittings are provided. Fan motors typically have two grease fittings. Each motor manufacturer has different lubrication schedules for different models. Go to the motor manufacturer’s website and download their maintenance requirements. Do not over-lubricate motors or use an incompatible grease. Many fractional motors are permanently lubricated for life and require no further lubrication.
Fan Wheel and Fasteners – Wheels require very little attention when moving clean air. Occasionally oil and dust may accumulate on the wheel causing imbalance.
When this occurs, the wheel and housing should be cleaned to assure smooth and safe operation. Inspect fan impeller and housing for fatigue, corrosion, or wear.
Routinely check all fasteners, set screws and locking collars on the fan, bearings, drive, motor base and accessories for tightness. A proper maintenance program will help preserve the performance and reliability designed into the fan.
Internal Filter Maintenance – The unit will typically be provided with 2-inch thick pleated paper filters in the airstream. These filters should be checked according to a routine maintenance schedule and replaced as necessary to ensure proper airflow through the unit.
Replacement filters shall be of same performance and quality as factory installed filters. Filter must be pleated design with integral metal grid. Two acceptable filter replacements are Aerostat Series 400 or Farr 30/30®.
Filters upstream of the coil should be checked regularly.
If the filters are dirty, they should be cleaned or replaced. It is important the filters stay clean to maintain desired airflow.

WARNING
REFER TO GENERAL SAFETY INFORMATION
Do not operate this unit without the filters and birdscreen installed. They prevent the entry of foreign objects such as leaves, birds, etc.
Do not remove access panels or other unit components while standing on a ladder or other unsteady base. Access panels and unit components are heavy and serious injury may occur.

External Filter Maintenance – Aluminum mesh, 2-inch thick filters are located in the supply weatherhood (if the weatherhood option was purchased). These filters should be checked and cleaned on a regular basis for best efficiency. The frequency of cleaning depends upon the cleanliness of the incoming air. These filters should be cleaned by rinsing with a mild detergent in warm water prior to start-up.

Aluminum filters are
removable from either the front or side of the weatherhood.
Drain pans in any air conditioning unit will have some moisture in them, therefore, algae and other organisms will grow due to airborne spores and microbial growth. Periodic cleaning is necessary to prevent this buildup from plugging the drain and causing the drain pan to overflow. Inspect twice a year to avoid the possibility of overflow. Also, drain pans should be kept clean to prevent the spread of disease. Cleaning should be performed by qualified personnel.

Coil Maintenance – Coils must be cleaned to maintain maximum performance. Check coils once per year under normal operating conditions and if dirty, brush or vacuum clean. Soiled fins reduce the capacity of the coil, demand more energy from the fan and create an environment for odor and microbial growth to grow and spread through the conditioned zone. High pressure water (700 psi or less) may be used to clean coils with a fin thickness over 0.0095 inches thick. TEST THE SPRAY PRESSURE over a small corner of the coil to determine if the fins will withstand the spray pressure.
For coils with fragile fins or high fin density, foaming chemical sprays and washes are available. Many coil cleaners use harsh chemicals, so they must be used with caution by qualified personnel only. Care must be taken not to damage the coils, including the fins, while cleaning. Caution: Fin edges are sharp!

Routine Maintenance

Model| Outdoor Air Weatherhood (Aluminum Mesh)| Pre-Wheel Outdoor| Exhaust Filters| Supply Final Filters (Pre-coil)
---|---|---|---|---
XRV-10| (1) 16x20x1| NA| NA| (1) 12×24 + (1) 24×24
XRV-25 (5, 7, 10 tons)| (4) 20x20x2| NA| NA| (4) 20×20
XRV-25 (12.5, 15 tons)| (4) 20x20x2| NA| NA| (2) 20×20 + (2) 20×24
XRV-45| (4) 25x25x2| NA| NA| (3) 16×20 + (3) 20×20
XRV-75| (12) 16x20x2| NA| NA| (8) 20×20 + (4) 16×20
XRV-110| (8) 20x25x1| NA| NA| (6) 20×24 + (6) 20×20

Reference – Venting Connection Locations

IG Venting Location

Model| Furnace Size (MBH)| A| B| C| D| Flue Connection Size (diameter in inches)
Standard| 2-Pipe/Concentric
Exhaust| Exhaust| Intake
XRV-25| 100| 14| 23.5| 20.5| 20.5| 4| 4| 4
200| 15.2| 23.7| 31.5| 35.9| 6| 6| 6
300| 6| 6| 6
XRV-45| 300| 14.8| 23.3| 38.1| 44.1| 6| 6| 6
400| 6| 6| 6
500| 14.9| 23.6| 25.2| 57.1| 6| 6| 6

Reference – Venting Connection Locations Cont.
(Model XRV-110) NO indoor venting options available

IG Venting Location

Model| Furnace Size (MBH)| A| B| C| D| E| F| G| H| I| J| Inlet Dimensions| Outlet Dimensions
Length| Height| Edge Thickness| Length| Height
XRV-110| 600| 6| 13.8| 17.2| 20.5| 50| NA| NA| NA| NA| NA| 21.5| 6| 1| 6.5| 5.5
800| 6| 13.8| 24.7| 20.5| 49.8| 6| 13.7| 18.5| 20.5| 49.7| 20.5| 6| 1| 6.5| 5.5
1000| 6| 13.8| 17.2| 20.5| 50| 6| 13.7| 24.2| 20.5| 49.9| 21.5| 6| 1| 6.5| 5.5
1200| 6| 13.8| 17.2| 20.5| 50| 6| 13.7| 24.2| 20.5| 49.9| 21.5| 6| 1| 6.5| 5.5

Reference – Rated Airflow

Model Airflow (SCFM)
XRV-10-3I 1100
XRV-10-4I 1450
XRV-10-5I 1700
XRV-10-6I 1600
XRV-10-7I 1700
XRV-25-5I 3075
XRV-25-5A 3400
XRV-25-7(I,J) 2300
XRV-25-7.5(I,J) 2300
XRV-25-7.5A 3000
XRV-25-10(I,J) 2700
XRV-25-10A 4400
XRV-25-12.5(I,J) 2900
XRV-25-12.5A 4400
XRV-25-15(I,J) 3300
XRV-25-15A 4300
XRV-45-15(I,J) 3900
XRV-45-15A 4800
XRV-45-17.5(I,J) 4100
XRV-45-17.5A 5500
XRV-45-20(I,J) 4700
XRV-45-20A 6400
XRV-45-25(I,J) 5100
XRV-45-25A 7200
XRV-45-30(I,J) 5700
XRV-45-30A 7000
XRV-75-25(I,J) 8300
XRV-75-30(I,J) 9400
XRV-75-40(I,J) 10000
XRV-75-50(I,J) 10800
XRV-110-30(I,J) 9000
XRV-110-40(I,J) 10500
XRV-110-50(I,J) 11000
XRV-110-60(I,J) 14000
XRV-110-70(I,J) 16000

Full load rating airflow per AHRI 340/360
I = Inverter compressor
A = ASHP

Our Commitment
As a result of our commitment to continuous improvement, Accurex reserves the right to change specifications without notice.
Product warranties can be found online at accurex.com, either on the specific product page or in the Warranty section of the website at Accurex.com/Resources/Warranty.

P.O. Box 410 Schofield, WI 54476
Phone: 800.333.1400 • Fax: 715.241.6191
Parts: 800.355.5354 • accurex.com
475597 • XRV, Rev. 23, February 2024 Copyright 2024 © Accurex, LLC

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals