485932 XDGX Make Up Air Direct Gas
User Guide
Microprocessor Controller
This quick start document is intended to help with getting the initial unit
startup completed, but does not replace the IOM. Please read the IOM for all
safety information and precautions before performing any work on the
equipment.
Keypad Description
| Alarm| Button will blink red, indicating an alarm condition. Press to
review current alarms. To review previous alarms, access the Alarm Menu.
---|---|---
| Down Arrow| The arrow keys allow the user to scroll through different
screens and adjust parameters.
| Up Arrow
| Enter| A. In screens with adjustable parameters, pressing the Enter key
moves the cursor from the upper left corner of the screen to the parameter.
The arrow keys can then be used to adjust the parameter.
B. To move to the next parameter on the same screen, press the Enter
button.
C. To save the change, press the Enter button until the cursor moves back
to the upper left corner of the screen.
| Escape| Allows the user to exit the current menu, jumping to the Main Menu.
| Program| Pressing the Prg (Program) button allows the user to enter the Main
Program Menu.
Main Menu Layout
Unit Enable
Unit Status
Ctrl Variables
Temp Control
Heat & Vent
Refrigeration
Evap Cooling
Damper Control
Fan Control
Occupancy
Advanced
Login
Manual Overrides
Adv. Set points
PID Tuning
Network Settings
Backup/Restore
IO Status/Offset
IO Config
Unit Config
Unit Settings
Service Info
Alarm Management
*Only available when unit is configured with these options
**Only available when logged in with the service password
MAIN SCREEN: The main screen will display the current supply temperature,
outside air temperature, space temperature (if equipped), temperature setpoint
and symbols to indicate operation. In addition the unit status line will
provide the current mode of operation.
MENU NAVIGATION: The controller will revert to the main screen after
several minutes of inactivity. Pressing the UP or DOWN arrow key from the main
screen will cycle the display through the Unit Status Menu.
Pressing the Program key allows the user to enter the Main Program menu. The
Main Program Menu consists of several menus to help guide users with altering
program parameters.
UNIT START COMMAND: The unit ships from the factory in a disabled state.
To allow the unit to operate, the controller must receive a run command.
Jumper unit terminals R – G to allow the unit to operate. The unite can then
be enabled manually in the unit enable menu.
BMS – Command the unit enable/disable point to control through BMS.
Scheduler – To use the integral time clock, configure the schedule
through the occupancy menu.
SET POINTS: To view or adjust set points and lockouts, go to the Set
point menu.
BMS Configuration: To configure BACnet or Modbus settings, login using
the service password (found in the IOM) by navigating to Ctrl Variables >
Advanced > Login. Settings such as address, baud rate, etc can then be
configured in the Network Settings menu.
UNIT TESTING: To manually override the units control loops and I/O, go to
the Ctrl Variables>Advanced menu and login with the service password found in
the controller IOM. Once logged in the manual overrides menu will be available
in the Ctrl Variables>Advanced menu.
Microprocessor Controller Quick Start Guide
Rev. 2, August 2022
Document 485932